Maintained by BuildSolver · Updated
Calculator · Ventilation
Whole house fan size calculator
Enter the floor area, the ceiling height and the air changes per hour, and this page gives the airflow of a whole house fan in CFM, the attic net free vent area it exhausts through and the open window area it draws from. The default 1,500 sq ft house with 8 ft ceilings at 20 ACH is 4,000 CFM, 5.3 sq ft of attic vent and 16.0 sq ft of open window. For the vent area an attic needs under the code, use the attic ventilation calculator; for the ACH of a room or a blower door test, the air changes per hour calculator.
- The conditioned floor area in square feet, all floors, and the average ceiling height in feet. The page multiplies them for the volume in cubic feet.
- The DOE Building America guideline gives 10 to 30 ACH for large propeller fans and about 5 for small damper-style fans; the Building America Solution Center gives 12 to 23. The page starts at 20, the example in the guideline's table.
- The result gives the fan airflow in CFM, the attic net free vent area at 1 sq ft per 750 CFM and the open window area at 4 sq ft per 1,000 CFM.
- Optionally type the net free area of the attic vents and the open window area you have. The page says whether each is enough and what fan it serves.
Example result for the default inputs
House 1,500 sq ft, 8 ft ceilings, 20 ACH.
Fan airflow
4,000 CFM
Attic net free vent area
5.34 sq ft, rounded up
Open window area
16.00 sq ft, rounded up
House volume
12,000 cu ft
| Volume | 1,500 sq ft x 8 ft = 12,000 cu ft |
|---|---|
| Fan airflow | 12,000 cu ft x 20 ACH / 60 = 4,000.0 CFM, 2.67 CFM per sq ft of floor |
| Fan rated at or above | 4,000 CFM (the airflow rounded up to a whole CFM) |
| Attic net free vent area | 4,000.0 CFM / 750 = 5.33 sq ft, 1 sq ft per 750 CFM, net free area of the vents |
| Open window or door area | 4,000.0 CFM x 4 / 1,000 = 16.00 sq ft, 4 sq ft per 1,000 CFM, open area only |
- Open windows before the fan runs; the guideline says a whole house fan should never be operated without them. It also says never to install one where a gas appliance has a standing pilot or draws its combustion air from inside the house or attic, and to close the fireplace damper or doors, with no fire lit.
- The ACH is your choice, not a code value. The DOE guideline gives 10 to 30 ACH for large propeller fans and about 5 for small damper-style fans; the Building America Solution Center gives 12 to 23. The fan maker's data sheet sets the vent area for a given model. This page does not pick a fan.
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the fan airflow and the openings are found
The page turns a house volume and a number of air changes per hour into the airflow of the fan, then sizes the two openings that go with it: the attic vents the air leaves through and the open windows it enters by. The ACH is your choice; the sources give a range, not one value.
- House volume
V = floor area x average ceiling height1,500 sq ft x 8 ft = 12,000 cu ft. The DOE guideline defines the volume as the total conditioned floor area times the average ceiling height.- Fan airflow
CFM = V x ACH / 60This is the guideline's ACH = 60 x Q / V solved for Q. 12,000 cu ft x 20 ACH / 60 = 4,000 CFM, 2.67 CFM per sq ft of floor. At 5 ACH the same house is 1,000 CFM.- Attic net free vent area
area = CFM / 750One square foot of net free vent area for each 750 CFM of fan capacity. 4,000 / 750 = 5.3 sq ft. It is the net free area of the vents, which a screen or louvers cut by about half.- Open window area
area = CFM x 4 / 1,000At least 4 square feet of open window or door area for each 1,000 CFM. 4,000 x 4 / 1,000 = 16.0 sq ft of open area, the part of a window that is open.- Check against the DOE table
Table 6 of the guideline, 8 ft ceilingsThe guideline lists 1,000 sq ft at 2,667 CFM and 3,000 sq ft at 8,000 CFM for 20 ACH, and 667 and 2,000 CFM for 5 ACH; the table below is the same function.
Five house sizes with 8 ft ceilings
Each row is a house with 8 ft ceilings, worked with the same function as the form and laid out as Table 6 of the DOE guideline. A 1,000 sq ft house takes 2,667 CFM at 20 ACH and 667 CFM at 5 ACH, and a 3,000 sq ft house takes 8,000 CFM and 2,000 CFM. Vent and window areas at 20 ACH fill the last two columns.
| House | Ceilings | CFM at 5 ACH | CFM at 20 ACH | Attic vent, sq ft | Open window, sq ft |
|---|---|---|---|---|---|
| 1,000 sq ft | 8 ft ceilings | 667 | 2,667 | 3.6 | 10.7 |
| 1,500 sq ft | 8 ft ceilings | 1,000 | 4,000 | 5.3 | 16.0 |
| 2,000 sq ft | 8 ft ceilings | 1,333 | 5,333 | 7.1 | 21.3 |
| 2,500 sq ft | 8 ft ceilings | 1,667 | 6,667 | 8.9 | 26.7 |
| 3,000 sq ft | 8 ft ceilings | 2,000 | 8,000 | 10.7 | 32.0 |
CFM comes from Table 6 of the guideline and the areas follow its Tables 7 and 8, at 1 sq ft of net free attic vent area per 750 CFM and 4 sq ft of open window area per 1,000 CFM. Pick the ACH with the fan maker's data sheet or the installer.
Standards and data sources
- U.S. DOE, EERE Building America, Measure Guideline: Ventilation Cooling (Springer, Dakin and German, April 2012, DOE/GO-102012-3533) - Read in the PDF. The source of ACH = 60 x Q / V with the volume as the conditioned floor area times the average ceiling height; of 10 to 30 ACH for large propeller whole house fans, about 5 ACH for small damper-style fans and a minimum of 5 ACH; of Table 6 (fan capacity at 5 and 20 ACH for 1,000 to 3,000 sq ft with 8 ft ceilings); of 1 sq ft of attic net free vent area per 750 CFM (Table 7); and of 4 sq ft of open window or door area per 1,000 CFM (Table 8). It also carries the combustion appliance and fireplace cautions.
- Building America Solution Center (U.S. DOE, content by PNNL), Whole-House Fans, last updated September 29, 2022 - Read as a web page. A second, open source for the same two ratios, 1 sq ft of net-free vent area per 750 CFM and 4 sq ft of screened open window area per 1,000 CFM. It gives 12 to 23 ACH as effective, the 50 percent loss of free area to insect screens and louvers, and about 1.5 to 3 CFM per sq ft of floor with 8 ft ceilings. Its ACH range differs from the guideline's, and this page shows both.
Limitations of this calculator
- This page sizes the airflow and the two openings of a whole house fan from a volume and an ACH you choose. It is a planning aid for a quote or a conversation with an installer, not a design. The fan maker's data sheet and the installer set the model, the vent area for that model, the damper and the location.
- The ACH is not a code value. The DOE Building America guideline gives 10 to 30 ACH for large propeller fans, about 5 for small damper-style fans and a minimum of 5. The Building America Solution Center gives 12 to 23. The required ACH depends on the building envelope and its thermal mass, and the page does not estimate that.
- The attic vent area is 1 sq ft per 750 CFM of net free area, and the window area is 4 sq ft per 1,000 CFM of open area. Both are rules of thumb printed in the sources. A screen or louvers cut the free area of a vent by about half, so the vent area you type must be the net free area the maker lists, not the size of the opening.
- The page does not check the attic against a building code. The guideline notes that codes typically call for attic net free vent area of no less than 1/150 or 1/300 of the attic area and that a large fan in a small-footprint multi-story house needs the area checked. For that code minimum use the attic ventilation calculator; it is a different calculation.
- Volume is the total conditioned floor area times the average ceiling height, as the guideline defines it. Vaulted ceilings, open stairwells and unconditioned spaces are not modeled; type the average height you judge right. The guideline's table assumes 8 ft ceilings.
- Combustion safety is not assessed. The guideline says a whole house fan can depressurize the house, that it should never be installed where a gas appliance has a standing pilot or draws combustion air from inside the house or attic, that windows must be open before it runs, and that the fireplace damper or doors stay closed with no fire lit. A combustion appliance safety test and local code are for a qualified installer.
- Energy savings, run hours, noise, duct or damper loss and the right night to run the fan are not computed. A whole house fan can bring in warm air if the windows and fan are not operated correctly, as the guideline notes.
- Values outside the field ranges are not accepted: floor area 100 to 20,000 sq ft, ceiling height 6 to 20 ft, ACH 1 to 60, and a typed vent or window area up to 1,000 sq ft. Above 6,000 CFM the guideline's tables stop; the page applies the same ratios and says so. These bounds are this page's own, not a code's.
Common mistakes when sizing a whole house fan
- Opening too few windows. The fan draws its air through the open windows, 4 sq ft of open area for each 1,000 CFM. The default 4,000 CFM fan needs 16.0 sq ft of open area. A window open 3 sq ft serves a fan of 750 CFM, so that fan wants about 6 such windows. The guideline says a whole house fan should never be operated without opening windows.
- Counting the size of the vent, not its free area. A gable vent 8 sq ft overall with a screen and louvers gives about half of that as net free area, 4 sq ft. That serves 3,000 CFM at 750 CFM per sq ft, and the 4,000 CFM fan is 1.3 sq ft short of the 5.3 sq ft it needs. Use the net free area printed on the vent.
- Forgetting the ceiling height. Airflow follows volume, not floor area. The same 1,500 sq ft house at 9 ft ceilings holds 13,500 cu ft, and at 20 ACH the fan is 4,500 CFM against 4,000 CFM at 8 ft, with 6.0 sq ft of attic vent and 18.0 sq ft of open window.
- Using the central fan rule of 4.5 ACH. The guideline's rule of thumb of 4.5 ACH, about 0.6 CFM per sq ft, is for central fan systems that run the air handler, not for whole house fans. On this house it is 900 CFM against 4,000 CFM at 20 ACH. A whole house fan is sized from the 10 to 30 ACH of the propeller fans, or about 5 ACH for a damper-style fan, which is 1,000 CFM here.
- Assuming the attic already has the vent area. The guideline says codes typically call for attic net free vent area of no less than 1/150 or 1/300 of the attic area, and that a large fan in a multi-story house with a small footprint needs the area verified. A 1,500 sq ft two-story house has an attic floor of about 750 sq ft: 1/150 of it is 5.0 sq ft and 1/300 is 2.5 sq ft, against the 5.3 sq ft the 4,000 CFM fan needs.
- Running the fan with a combustion appliance on. The guideline warns that a whole house fan can depressurize the house and pull combustion gases from gas water heaters, furnaces, fireplaces and wood stoves that use indoor air. It says never to install one where a gas appliance has a standing pilot or takes combustion air from inside the house or attic, and to keep fireplace doors or the damper closed with no fire lit. Have the appliances checked before the fan goes in.
Common questions about whole house fans
What size whole house fan do I need for a 1,500 sq ft house?
With 8 ft ceilings the volume is 12,000 cu ft. At 20 ACH, the example in the DOE guideline's Table 6, the fan is 4,000 CFM. At 5 ACH, the figure for small damper-style fans, it is 1,000 CFM. A range of 12 to 23 ACH gives 2,400 to 4,600 CFM. Pick a fan rated at or above the number you choose.
How many CFM per square foot does a whole house fan need?
It depends on the ceiling height and the ACH. At 8 ft ceilings, CFM per sq ft is 8 x ACH / 60, so 20 ACH is 2.67 CFM per sq ft, 12 ACH is 1.60 and 23 ACH is 3.07. The Building America Solution Center states about 1.5 to 3 CFM per sq ft of floor for 8 ft ceilings. The page works from volume and ACH instead of a flat figure.
How is a whole house fan sized from air changes per hour?
ACH = 60 x CFM / volume in cubic feet, so CFM = volume x ACH / 60. A 2,000 sq ft house with 8 ft ceilings is 16,000 cu ft: 1,333 CFM at 5 ACH and 5,333 CFM at 20 ACH. Those are the 1,333 and 5,333 CFM of the guideline's Table 6. Choosing the ACH is up to you: the guideline gives 10 to 30 for large propeller fans and a minimum of 5.
How much attic vent area does a whole house fan need?
Both the DOE guideline and the Building America Solution Center give 1 sq ft of net free vent area for each 750 CFM of fan capacity. The default 4,000 CFM fan needs 5.3 sq ft, a 3,000 sq ft house at 20 ACH (8,000 CFM) needs 10.7 sq ft. It is net free area, so a screen or louvers cut the size of the vent by about half. The fan maker's data sheet may list its own figure.
How many windows do I need to open for a whole house fan?
Both sources give 4 sq ft of open window or door area for each 1,000 CFM, and only the open part of a window counts. The default 4,000 CFM fan needs 16.0 sq ft; with each window open 3 sq ft that is about 6 windows. Interior doors to rooms with open windows should stay open, the guideline adds, and the fan should never run without windows open.
What is the difference between this and the attic ventilation calculator?
The attic ventilation calculator finds the vent area an attic needs from its floor area under IRC R806, 1/150 or 1/300. This page finds the fan airflow of a whole house fan from the house volume and an ACH, and the attic vent area for that fan, 1 sq ft per 750 CFM. For the default fan that is 5.3 sq ft of net free area. Check a fan's vent area against both.
Is it safe to run a whole house fan with a gas furnace or water heater?
Not without checking. The DOE guideline says a whole house fan can depressurize the house and back-draft gas water heaters, furnaces, fireplaces and wood stoves that use indoor air for combustion. It says a fan should never be installed where a gas appliance has a standing pilot or takes combustion air from inside the house or attic, that windows must be open before the fan runs, and that a fireplace should have no fire and its damper or doors closed. Many local codes require a control that stops the furnace and the fan running together. Ask a qualified installer.
Does this calculator choose a fan model?
No. It gives the airflow in CFM that follows from the volume and the ACH you enter, and the attic vent and window areas that go with it. The model, its rated CFM at the pressure it will see, its damper and its vent area come from the fan maker's data sheet and the installer.