Heating cost only, from the prices, AFUE and COP you enter. Prices change, the COP of a heat pump falls in the cold, and equipment, service, fixed charges and time-of-use rates are not counted. A comparison of running cost, not a quote or a payback.

Maintained by BuildSolver · Updated

Calculator · HVAC

Heat pump vs furnace cost calculator

Heat from gas, propane, oil and electricity is sold in different units, so compare them as dollars per million BTU of heat that reaches the house. A furnace delivers its AFUE share of the fuel, resistance heat delivers all of the electricity, and a heat pump delivers its COP times the electricity. With the example prices on this page, gas costs $15.79 per MMBtu, a heat pump at COP 2.5 costs $21.50, and the heat pump breaks even with gas at a COP of 3.40. The prices are examples, not a forecast, so type your own. This page is heating only; for cooling cost use the SEER2 energy cost calculator, and for the COP to enter, the SEER, EER and COP conversion calculator.

  1. Type the annual heat need in MMBtu, the electricity price per kWh, and the gas price per therm. Add propane and heating oil prices if you want them compared, and clear both fields of a fuel to leave it out.
  2. Give the AFUE of each furnace or boiler from its nameplate, and a winter-average COP for the heat pump. HSPF2 divided by 3.412 gives a seasonal COP.
  3. The result shows dollars per million BTU of delivered heat and dollars per year for each option, which is cheapest, and the COP at which the heat pump costs the same as each fuel.

Heating only. Prices, AFUE and COP are yours, and the defaults are examples. EIA heat contents. No cooling, no equipment cost, no time-of-use rates.

Heat delivered to the rooms, not fuel burned. 1 MMBtu is 1,000,000 BTU. 60 is an example; take yours from a Manual J heat loss and degree days, or from past bills times the furnace AFUE.

Defaults to $0.1834, the U.S. residential average from the EIA Electric Power Monthly for June 2026. Use the all-in rate on the customer's bill, energy charge plus the per-kWh parts of delivery.

Heat out divided by electricity in, averaged over the heating season. HSPF2 / 3.412 is the seasonal rating as a COP, and the conversion calculator does it. The COP at 47F is not the winter average, and it falls as the outdoor air gets colder.

From the gas bill: the total divided by the therms, with the fixed charge left out. 1 therm is 100,000 BTU. An example price, not a forecast. If the bill is in ccf, 1 ccf is about 1.04 therms.

The percent of the fuel's heat that reaches the house over a season, on the nameplate or the AHRI directory. 80 is a basic furnace, 95 and up is condensing.

Clear both propane fields to leave propane out. An example price, not a forecast. The price on the delivery ticket, tax and fees included.

Needed whenever a propane price is entered.

Clear both oil fields to leave oil out. An example price, not a forecast. No. 2 heating oil at the delivered price.

Needed whenever an oil price is entered. ENERGY STAR oil furnaces start at 87.

Example result for the default inputs

60 MMBtu of heat a year, electricity $0.1834 per kWh, heat pump COP 2.50, gas $1.50 per therm at 95% AFUE.

Heat pump

$1,290 per year

Gas furnace

$947 per year

Heat pump against gas

$343 more per year

Break-even COP against gas

3.40 COP

Calculation details
Natural gas furnace$15.79 per MMBtu, $947 a year. $1.50 per therm x 10 therms per MMBtu / 95% AFUE
Propane furnace$33.38 per MMBtu, $2,003 a year. $2.90 per gallon x 1,000,000 / 91,452 BTU / 95% AFUE
Heating oil furnace or boiler$32.28 per MMBtu, $1,937 a year. $3.80 per gallon x 1,000,000 / 138,500 BTU / 85% AFUE
Electric resistance$53.75 per MMBtu, $3,225 a year. $0.1834 per kWh x 1,000,000 / 3,412 BTU, efficiency 1
Heat pump$21.50 per MMBtu, $1,290 a year. $0.1834 per kWh x 1,000,000 / 3,412 BTU / COP 2.50
CheapestNatural gas furnace is cheapest at $15.79 per MMBtu, $947 a year. Next is heat pump at $21.50, $343 a year more.
Break-even COP against gas3.40 = $53.75 per MMBtu of electricity / $15.79. Your COP of 2.50 is below it, so natural gas furnace is the cheaper of the two.
Break-even COP against propane1.61 = $53.75 per MMBtu of electricity / $33.38. Your COP of 2.50 is at or above it, so the heat pump is the cheaper of the two.
Break-even COP against heating oil1.67 = $53.75 per MMBtu of electricity / $32.28. Your COP of 2.50 is at or above it, so the heat pump is the cheaper of the two.
Heat contents usedEIA: 1 kWh = 3,412 BTU, 1 therm = 100,000 BTU, propane 91,452 BTU per gallon, heating oil 138,500 BTU per gallon.
What this leaves outHeat pump COP falls on the coldest days, and the winter average is yours to enter. Service, equipment cost, fixed monthly charges, delivery fees and time-of-use or demand rates are not included. Prices change; these are the ones you entered.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the cost of heat is worked out

Every fuel is priced the same way: what a million BTU of the fuel costs to buy, divided by how much of it ends up as heat in the house. A furnace or boiler delivers its AFUE share of the fuel. Electric resistance delivers all of it. A heat pump delivers its COP times the electricity it uses, because it moves heat as well as making it. The heat content of each fuel comes from the U.S. Energy Information Administration. The prices and efficiencies are yours.

Electricity
$/MMBtu = price per kWh x 1,000,000 / 3,4121 kWh is 3,412 BTU (EIA), so a million BTU of electricity is 293.1 kWh. At $0.1834 per kWh that is $53.75 per MMBtu.
Natural gas
$/MMBtu = price per therm x 101 therm is 100,000 BTU (EIA), so a million BTU is 10 therms. $1.50 a therm is $15.00 per MMBtu before the furnace efficiency is applied.
Propane
$/MMBtu = price per gallon x 1,000,000 / 91,452EIA lists propane at 91,452 BTU per gallon. $2.90 a gallon is $31.71 per MMBtu, about twice the gas price per unit of heat at these examples.
Heating oil
$/MMBtu = price per gallon x 1,000,000 / 138,500EIA lists heating oil at 138,500 BTU per gallon, so a gallon carries about 1.5 times the heat of a gallon of propane.
Furnace or boiler
delivered $/MMBtu = fuel $/MMBtu / (AFUE / 100)AFUE is the share of the fuel's heat that becomes space heat. The example gas furnace at 95% AFUE turns $15.00 of fuel into $15.79 per MMBtu of delivered heat.
Electric resistance
delivered $/MMBtu = electricity $/MMBtuAll of the electricity becomes heat, an efficiency of 1, so the delivered cost is $53.75 per MMBtu at the example rate.
Heat pump
delivered $/MMBtu = electricity $/MMBtu / COPCOP is heat out over electricity in. At a COP of 2.5 the example is $53.75 / 2.5 = $21.50 per MMBtu, 117.2 kWh for each million BTU.
Cost a year
$/year = delivered $/MMBtu x MMBtu a yearAt 60 MMBtu of heat a year the example gas furnace costs $947, the heat pump $1,290 and resistance heat $3,225.
Break-even COP
COP = electricity $/MMBtu / fuel delivered $/MMBtuThe COP at which the heat pump costs the same as the fuel. Against the example gas furnace it is 3.40, and in this example a heat pump averaging below that costs more to run than gas.

Seven price and COP cases for the same house

Each row heats the same 60 MMBtu a year. Row one is the example this page opens on: gas $15.79 and a heat pump $21.50 per MMBtu. Each later row changes one thing at a time, the electricity price, the furnace AFUE, the heat pump COP or the gas price, so you can see which input moves the answer. Prices here are examples, not a forecast.

Cost of heat for gas and a heat pump in seven cases
CaseWhat changesGas, $/MMBtuHeat pump, $/MMBtuGas, $/yearHeat pump, $/yearBreak-even COP
Example prices$0.1834/kWh, gas $1.50/therm, 95% AFUE, COP 2.5$15.79$21.50$947$1,2903.40
Cheap electricity$0.10/kWh, the rest as above$15.79$11.72$947$7031.86
Expensive electricity$0.30/kWh, the rest as above$15.79$35.17$947$2,1105.57
Older 80% furnace80% AFUE gas, the rest as the example$18.75$21.50$1,125$1,2902.87
Mild climate, COP 3.5COP 3.5, the rest as the example$15.79$15.36$947$9213.40
Cold winter, COP 1.8COP 1.8, the rest as the example$15.79$29.86$947$1,7923.40
Gas at $2.20 a thermgas $2.20/therm, the rest as the example$23.16$21.50$1,389$1,2902.32

Carry the break-even COP to a customer as the single number: if the heat pump's winter average is above it, the heat pump is cheaper to run on these prices, and if it is below, gas is. It moves with the electricity price and the gas price, and it is the reason a heat pump pays in one house and not in the next.

Standards and data sources

Limitations of this calculator

  • Prices are the numbers you type. The defaults are examples to show the arithmetic, not a forecast and not a survey, and fuel and electricity prices change by the month and by the utility or supplier. Use the latest bill or delivery ticket.
  • A heat pump's COP is not one number. It falls as the outdoor air gets colder, and below the balance point backup heat takes over at a COP of 1. Enter a winter-season average for your climate, and see the heat pump balance point calculator for how much of the load the compressor carries.
  • The result is a cost of heat at the average COP and AFUE you give. It does not simulate hourly weather, defrost cycles, or a variable-speed unit's changing efficiency.
  • Furnace blower electricity, ignition and pilot energy, and the standby use of a heat pump are left out. A gas furnace also uses some electricity, and AFUE does not count it, so a gas furnace's true cost is slightly higher than shown.
  • Rates with tiers, time-of-use periods or demand charges are not modeled, and neither are fixed monthly charges and delivery fees. Use an all-in average $/kWh and $/therm, with the fixed charge taken out unless the choice would remove the meter.
  • Equipment price, installation, service, maintenance, rebates, tax credits and the cost of leaving a fuel service are not included, so this is a running-cost comparison only, not a payback or a life-cycle cost.
  • Heat contents are EIA sample values. Propane and heating oil as delivered vary by a few percent, and gas is billed by the therm only after the utility applies its own heating value to the volume measured.
  • The annual heat need is an input. This page does not work out a heat loss. It is heat delivered to the rooms, so a bill in fuel units must be multiplied by the furnace's AFUE first.
  • Heating only. Cooling cost is on the SEER2 energy cost calculator. Preliminary estimate for comparing fuels, not an energy audit.

Common mistakes when comparing heating costs

  1. Comparing the price per unit. A therm of gas at $1.50 and a gallon of propane at $2.90 look close. Per million BTU they are $15.00 and $31.71, more than twice apart, because a gallon of propane holds 91,452 BTU and a therm 100,000. Convert every fuel to dollars per MMBtu first.
  2. Leaving out the furnace efficiency. Gas at $1.50 a therm is $15.00 per MMBtu in the pipe. Through a 95% AFUE furnace it is $15.79 per MMBtu in the house, and through an 80% furnace $18.75. That is $178 a year at 60 MMBtu.
  3. Using the rated COP as the winter COP. Spec sheets quote COP at a mild point such as 47F. A COP of 3.5 gives $921 a year in the example, and 1.8, a cold winter average, gives $1,792. The gas furnace is $947 either way. Use a seasonal figure, HSPF2 / 3.412, or less.
  4. Entering the heat bought instead of the heat delivered. The heat need is what reaches the rooms. A house that needs 60 MMBtu burns 63.2 MMBtu of gas in a 95% furnace, 631.6 therms. Entering the 63.2 MMBtu of fuel as the heat need overstates every yearly cost by about 5 percent. Convert a fuel bill to heat with the AFUE.
  5. Using a cooling rating for heating. SEER2 and EER2 describe cooling. The heating side of a heat pump is rated in HSPF2 and COP. Entering a SEER2 as a COP makes the heat pump look far better than it is. Convert the heating rating instead.
  6. Using the headline rate and ignoring tiers and fixed charges. The electricity price is the lever. At $0.10 per kWh the heat pump is $11.72 per MMBtu, under the $15.79 for gas. At $0.30 it is $35.17. Use the average rate the customer pays for the extra winter kWh, not the lowest tier.

Common questions about heat pump and furnace running cost

How do you compare the cost of heat from different fuels?

Put every fuel on the same basis: dollars per million BTU of heat delivered to the house. That is the fuel price per unit, converted with its heat content, divided by the efficiency. In the example, gas is $15.79 per MMBtu, a heat pump at COP 2.5 is $21.50, heating oil is $32.28, propane is $33.38 and electric resistance is $53.75.

How many BTU are in a therm, a gallon of propane, a gallon of heating oil and a kWh?

The EIA gives 1 therm = 100,000 BTU, 1 gallon of propane = 91,452 BTU, 1 gallon of heating oil = 138,500 BTU and 1 kWh = 3,412 BTU. A cubic foot of natural gas is about 1,036 BTU. These are sample values, and a delivery can differ by a few percent.

What COP does a heat pump need to cost less than gas?

The break-even COP is the electricity price per MMBtu divided by the gas cost per delivered MMBtu. At $0.1834 per kWh and gas at $1.50 a therm through a 95% AFUE furnace it is 3.40. At $0.10 per kWh it falls to 1.86, and at $0.30 it rises to 5.57. A winter-average COP above the break-even means the heat pump is cheaper to run.

What is AFUE and how does it enter the cost?

AFUE is the percentage of the heat in the fuel that is converted to space heat instead of being lost, measured by the federal test method. The delivered cost is the fuel cost divided by the AFUE. Gas costs $15.79 per delivered MMBtu through a 95% AFUE furnace and $18.75 through an 80% one.

Is a heat pump always cheaper than electric resistance heat?

Yes, at any COP above 1, because it delivers more heat for the same electricity. At COP 2.5 the heat pump costs $21.50 per MMBtu against $53.75 for resistance heat, about 40 percent of the cost. Below the balance point, backup strips run at a COP of 1.

What COP should I enter for a heat pump?

A winter-season average, not the rating at 47F. HSPF2 divided by 3.412 turns the seasonal rating into a COP: an HSPF2 of 8.5 is 2.49. Colder climates average lower because the compressor works at lower outdoor temperatures and the backup heat runs. Use the SEER, EER and COP conversion calculator to do the conversion.

Where do the default prices come from?

Electricity is priced at $0.1834 per kWh, the EIA residential average for June 2026. Gas, propane and oil prices are round examples chosen to show the arithmetic. They are not a forecast or a survey of any region. Replace all of them with the customer's own bills.

Does this include the cost of buying and installing the equipment?

No. It compares running costs only. Equipment price, installation, rebates, maintenance and the cost of removing a fuel service are separate, and a payback needs them. Take the yearly difference from this page to that comparison.

Is this the same as the dual-fuel switchover temperature?

No. A dual-fuel switchover is the outdoor temperature below which a hybrid system turns off the heat pump and fires the furnace. It follows the same cost comparison with a COP that changes with temperature. This page uses one average COP. The balance point calculator covers where the heat pump stops keeping up.

Used on the same job