Preliminary sizing from published examples and open commentary. The NEC text is paid and was not read; the rules are stated as Fischer (2005 NEC, Annex D), Holt in EC&M and other sources restate them. The adopted edition and the authority having jurisdiction govern, and this is not a load calculation for a permit. A licensed electrician designs and installs the service.

Maintained by BuildSolver · Updated

Calculator · Electrical

Dwelling load calculator, NEC standard method

The standard method of Article 220 Part III adds a dwelling one rule at a time. NEC Annex D, Example D1(a) is a 1,500 sq ft house with a 12 kW range and a 5.5 kW dryer: 5,100 VA of general load after Table 220.42, 8,000 VA for the range and 5,500 VA for the dryer make 18,600 VA, which is 77.5 A at 240 V and a 100 A service after the 100 A minimum. This page works those steps, with fixed appliances, the larger of heating and air conditioning and the largest motor on top. The optional method of 220.82 gives a different total; it is on the home electrical service load calculator. For a range or dryer circuit alone, see the electric range and dryer circuit calculator.

  1. Give the floor area and the number of small-appliance and laundry circuits. The general load is 3 VA per square foot plus 1,500 VA for each circuit, reduced by Table 220.42.
  2. Enter the range and dryer nameplates in kW, the fixed appliances as a count and a total, and the air conditioning and electric heating in VA. Only the larger of heating and air conditioning counts. Add the largest motor and any other loads at 100 percent.
  3. The result shows the load after demand in VA, the current at 240 V and the least standard service rating at or above it, never under 100 A, with every line of the calculation.

One-family dwelling, 120/240 V single phase, 3-wire, standard method of Article 220 Part III. Preliminary sizing. No optional method, no existing-dwelling additions, no neutral or conductor sizes.

Outside dimensions of the living space. Leave out open porches, garages, an unfinished attic and a cellar that cannot be finished later. Counted at 3 VA per sq ft.

At least two in a dwelling. Each counts 1,500 VA.

Each counts 1,500 VA. A dryer on its own 240 V circuit is entered below, not here.

Rating plate in kW, or watts divided by 1,000. A range of 3.5 to 12 kW counts 8,000 VA from Table 220.55 Column C; Note 3 lets ranges under 8.75 kW use Columns A or B, which give less, and this page does not. Leave blank, or 0, for gas. A cooktop and wall ovens on one circuit are added together and entered as one range.

Rating plate in kW, 1 to 12. A dryer under 5 kW counts 5,000 VA. Leave blank, or 0, for gas.

Water heater, dishwasher, disposal, built-in microwave and the like, fastened in place. Not the range, dryer, heating or air conditioning, and not small fans or lights. Four or more are counted at 75 percent; check how the adopted edition defines the appliances that count.

Add the nameplates of the appliances counted above. Leave blank when there are none.

Nameplate volts x rated load amps of the condenser plus the air handler or furnace fan.

Total nameplate of electric space heating. A heat pump with strip heat that runs with the compressor goes here as one sum. The larger of heating and air conditioning counts.

Nameplate volts x amps of the biggest motor, such as a well pump. It must already be inside the fixed appliances, the other loads or the air conditioning above. 25 percent of it is added.

EV charger at the larger of 7,200 VA or its nameplate (220.57 as it is restated; the 125 percent applies to the branch circuit, not to this load), hot tub, pool equipment, shop. Add them together.

Example result for the default inputs

1,500 sq ft dwelling, 120/240 V single phase, 3-wire. NEC Article 220 Part III standard method.

Calculated load

18,600 VA

Current at 240 V

77.5 A

Service size

100 A

Calculation details
General lighting, 220.123 VA x 1,500 sq ft = 4,500 VA
Small-appliance and laundry circuits, 220.523 circuits x 1,500 VA = 4,500 VA (2 small-appliance, 1 laundry)
General load before demand4,500 + 4,500 = 9,000 VA
General load after demand, Table 220.423,000 VA at 100 percent + 35 percent x 6,000 VA = 2,100 VA, total 5,100 VA
Range, Table 220.5512 kW is not over 12 kW: Column C, one range, 8 kW = 8,000 VA
Dryer, 220.54The nameplate, 5,500 VA, is at or over 5,000 VA, so the nameplate is used
Fixed appliances, 220.53None, 0 VA
Heating or air conditioning, 220.60None entered, 0 VA
Total calculated load5,100 + 8,000 + 5,500 = 18,600 VA
Current at 240 V18,600 VA / 240 V = 77.5 A
Service size100 A. The least standard rating at or above 77.5 A is 80 A (Table 240.6(A)), raised to the 100 A minimum of 230.79(C).
  • The calculated current is 77.5 A, under 100 A. A one-family dwelling service is rated at least 100 A (230.79(C)), so 100 A is the answer.
  • The percentages here are the Article 220 Part III standard method as Annex D, Mike Holt and other open sources print them. Section numbers follow the 2020 NEC; commentary reports 220.41 and Table 220.45 in the 2023 NEC and Article 120 in the 2026 edition. Use the edition your jurisdiction adopted. This is not a load calculation for a permit.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the load is worked

The standard method adds the loads of a dwelling one rule at a time, each with its own demand. Lighting at 3 VA per square foot plus 1,500 VA for each small-appliance and laundry circuit make the general load, which Table 220.42 reduces: the first 3,000 VA at 100 percent and the rest at 35 percent. Table 220.55 gives the range, the dryer is 5,000 VA or its nameplate, four or more fixed appliances take 75 percent, and only the larger of the heating and the air conditioning counts. A quarter of the largest motor is added. The total divided by 240 V is the current, and the service is the least standard rating at or above it, never under 100 A. This is the method of Annex D, Example D1(a). The optional method of 220.82 is on a separate page.

General load
3 VA x sq ft + 1,500 VA x (small-appliance + laundry circuits)In Annex D1(a), 4,500 VA of lighting + 3,000 VA of small-appliance circuits + 1,500 VA of laundry = 9,000 VA. A dwelling has at least two small-appliance circuits.
General load after demand
first 3,000 VA x 1.00 + (3,001 to 120,000 VA) x 0.35 + (over 120,000 VA) x 0.25Table 220.42. In D1(a), 3,000 + 0.35 x 6,000 = 3,000 + 2,100 = 5,100 VA. The 35 percent tier runs to 120,000 VA and ends at 43,950 VA; a general load of 130,000 VA is 46,450 VA.
Range
Table 220.55 Column C: 8 kW x (1 + 0.05 x kW over 12)A 12 kW range counts 8,000 VA, as in D1(a). A 14 kW range counts 8,800 VA. The range page works the table in full.
Dryer
max(5,000 VA, nameplate)220.54. D1(a) has a 5.5 kW dryer: 5,500 VA. A 4.5 kW dryer counts 5,000 VA.
Fixed appliances
nameplate total x 0.75 when there are four or more, else x 1.00220.53, as Holt and Portlandia restate it. Four appliances of 8,100 VA are 6,075 VA. Two appliances of 5,700 VA stay at 5,700 VA. The range, dryer, heating and air conditioning are not in this group.
Heating or air conditioning
the larger of the two loads220.60. In the 3,500 sq ft house, heating 12,000 VA against air conditioning 6,000 VA: 12,000 VA counts. With 4,000 VA of air conditioning and no heating it is 4,000 VA.
Largest motor
+ 0.25 x largest motor VA430.24 as it is restated; its text was not read. A 1,440 VA well pump adds 360 VA on top of what it already counts in its own entry.
Total and current
I = total VA / 240 VIn D1(a), 18,600 VA / 240 V = 77.5 A. Portlandia's first house: 27,800 VA, 115.8 A.
Service size
least standard rating at or above I, at least 100 ATable 240.6(A) and 230.79(C). 77.5 A is an 80 A size, and the 100 A minimum makes the service 100 A. 115.8 A gives 125 A.

Seven houses through the same formulas

Row one is NEC Annex D, Example D1(a) as Fischer prints it, 18,600 VA. Portlandia Electric Supply's worked houses fill the next three rows, 27,800, 30,225 and 45,975 VA, and use the 75 percent factor and the larger of heating and air conditioning. The last three are worked by the rules above and have no published figure to compare with.

Calculated load, current and service size for seven dwellings at 240 V
DwellingChecked againstLoad, VACurrent, AService, A
1,500 sq ft, Annex D1(a)Fischer, Annex D1(a)18,60077.5100
1,500 sq ft, two appliances, A/CPortlandia, 27,800 VA27,800115.8125
2,000 sq ft, three appliances, A/CPortlandia, 30,225 VA30,225125.9150
3,500 sq ft, electric heat, EVPortlandia, 45,975 VA45,975191.6200
1,500 sq ft, 14 kW range, 4.5 kW dryerRules applied by hand18,90078.8100
1,200 sq ft, all gasRules applied by hand4,78519.9100
2,400 sq ft, five appliances, well pumpRules applied by hand32,155134.0150

The service is the least standard rating at or above the current, and never under 100 A. D1(a) shows the minimum at work: 77.5 A is an 80 A size, and the service is 100 A. The all-gas house is 19.9 A and also 100 A.

Standards and data sources

Limitations of this calculator

  • The NEC text is paid and was not read. The rules are stated as Fischer (2005 NEC, Annex D), Holt in EC&M and a commercial article restate them. The 25 percent of the largest motor (430.24) shows up with numbers in Annex D, Example D1(b), which this page does not use as a test, so its tests are rule arithmetic and the page asks you to check it against the adopted edition.
  • Section numbers and percentages move between editions. The numbers on this page (220.12, Table 220.42, 220.53, Table 220.55) follow the 2020 NEC and earlier, as the examples above print them. Commentary reports that the 2023 NEC renumbers some of them, for example 220.41 and Table 220.45 for the lighting and general-load demand, and that the 2026 edition moves Article 220 to Article 120 and may change the lighting load per square foot. Use the edition your jurisdiction has adopted and match each number to it.
  • Not a load calculation for a permit. A permit office, an engineer or the authority having jurisdiction (AHJ) may require its own form or the optional method, and a licensed electrician designs and installs the service.
  • One-family dwelling at 120/240 V single phase, 3-wire. Not worked: the optional method of 220.82 (see the service size calculator), 220.83 for loads added to an existing dwelling, 120/208 V, three phase, multifamily, the neutral of 220.61, conductor sizes and a load management system.
  • Heating is entered as one total. A heat pump whose compressor runs with its strip heat is one load, so enter the sum; the page does not model a lockout. The larger of heating and air conditioning counts, which assumes they are not run together.
  • Fixed appliances are one total and a count. The 75 percent factor needs four or more and leaves out the range, dryer, heating and air conditioning, as Holt and Portlandia restate it. The page cannot check what you count, so a water heater, a dishwasher and a disposal are three, and a countertop microwave on a kitchen receptacle is already in the small-appliance circuits.
  • Floor area is the outside dimensions of the living space from 100 to 20,000 sq ft. Above that the page asks for an engineered calculation; the 25 percent tier of Table 220.42 over 120,000 VA is in the formula but the form cannot reach it.
  • The service rating is the least standard size of Table 240.6(A) at or above the current, never under 100 A (230.79(C)). Service conductor sizes, the 83 percent rule for dwelling service conductors and the utility's own limits are separate checks.
  • A calculated load is a minimum for sizing, not a measure of what the house draws. A utility may ask for a larger service, and a house with an EV charger, a heat pump and a range may be a case for a load management device instead of a bigger panel.

Common mistakes in the standard method

  1. Applying 35 percent to the whole general load. The first 3,000 VA counts at 100 percent. D1(a) is 9,000 VA of general load: 3,000 at 100 percent plus 35 percent of 6,000 is 5,100 VA, not 3,150 VA.
  2. Leaving the small-appliance and laundry circuits out of the general load. The 3 VA per sq ft for 1,500 sq ft is 4,500 VA, and the three circuits add 4,500 VA before Table 220.42 is applied. Without them the house is 3,525 VA of general load instead of 5,100 VA.
  3. Taking the range at its nameplate. A 12 kW range is 8,000 VA in the load calculation, not 12,000 VA. Table 220.55 gives 8 kW for one range up to 12 kW and adds 5 percent for each kW over, so a 14 kW range is 8,800 VA.
  4. Using the 5,000 VA dryer floor when the plate says more. A dryer is 5,000 VA or its nameplate, whichever is larger. D1(a) has a 5.5 kW dryer and counts 5,500 VA. A 4.5 kW plate counts 5,000 VA.
  5. Taking 75 percent for fewer than four appliances. The factor applies to four or more fixed appliances. Two appliances of 5,700 VA count 5,700 VA, not 4,275 VA. Four appliances of 8,100 VA count 6,075 VA. The range, dryer, heating and air conditioning do not belong in the group.
  6. Adding both the air conditioning and the heating. 220.60 counts only the larger of two loads that do not run together. With 12,000 VA of heating and 6,000 VA of air conditioning the house counts 12,000 VA, not 18,000 VA. A heat pump with strip heat that runs together is one load and is added.

Common questions about the standard method

How do you calculate a dwelling load by the NEC standard method?

Add the general load, 3 VA per sq ft plus 1,500 VA for each small-appliance and laundry circuit, and reduce it with Table 220.42: the first 3,000 VA at 100 percent, the rest at 35 percent. Then add the range from Table 220.55, the dryer at 5,000 VA or its nameplate, the fixed appliances (75 percent for four or more), the larger of heating and air conditioning, and 25 percent of the largest motor. Annex D1(a) is 18,600 VA, 77.5 A at 240 V.

What is the Annex D1(a) example?

A one-family dwelling of 1,500 sq ft with a 12 kW range and a 5.5 kW dryer. The general load is 9,000 VA, 5,100 VA after Table 220.42, the range is 8,000 VA and the dryer 5,500 VA, for 18,600 VA. At 240 V that is 77.5 A, and the book says the service is at least 100 A. This page opens on those numbers.

What is the difference between the standard method and the optional method?

The standard method of Article 220 Part III reduces each class of load on its own, as above. Optional method 220.82 takes 3 VA per sq ft, the circuits, the range, the dryer, the water heater and the other fixed appliances together at 100 percent of the first 10 kVA and 40 percent of the rest, plus the heating or air conditioning. One house gives different totals, and the optional method is often smaller. This page is the standard method; the service size calculator on this site works the optional one.

Why does the first 3,000 VA count at 100 percent?

Table 220.42, as Fischer's example applies it, takes the first 3,000 VA of the general lighting and receptacle load in full and 35 percent of the part from 3,001 to 120,000 VA. In D1(a) that is 3,000 VA plus 35 percent of 6,000 VA, which is 2,100 VA, for 5,100 VA.

When does the 75 percent factor for fixed appliances apply?

When four or more appliances are fastened in place, as Holt and Portlandia restate 220.53; the range, dryer, heating and air conditioning are left out of the group. Four appliances of 8,100 VA count 6,075 VA. With three or fewer they count at 100 percent: two appliances of 5,700 VA stay at 5,700 VA.

Do you add the air conditioning and the heating?

No. Under 220.60 only the larger of two loads that will not run together counts. A house with 12,000 VA of electric heating and 6,000 VA of air conditioning counts 12,000 VA. A heat pump whose compressor runs with its strip heat is one load, so enter the sum as heating.

What service size does the standard method give?

The total divided by 240 V, then the least standard rating of Table 240.6(A) at or above it, never under 100 A (230.79(C)). D1(a) is 77.5 A, an 80 A size, so 100 A. The 27,800 VA house is 115.8 A and 125 A, and the 45,975 VA house with electric heat is 191.6 A and 200 A. Final sizing is for the utility and the AHJ.

How is the largest motor counted?

The motor is already counted in its own entry, and 25 percent of the largest one is added on top, 430.24 as it is restated; its text was not read here. A 1,440 VA well pump adds 360 VA. Do not enter the motor of a heating or air conditioning load that 220.60 left out.