Maintained by BuildSolver · Updated
Calculator · Electrical
Motor circuit size calculator
A motor circuit is sized from a table current, not the nameplate. A 10 hp motor at 460 V, three phase, is 14 A in NEC Table 430.250. The conductor needs 125 percent of that, 17.5 A, and an inverse time breaker may be up to 250 percent, 35 A. If the motor will not start on it, Exception No. 2 allows up to 50 A. The overload device is set from the nameplate current instead. This page works single-phase and three-phase induction motors from 1/6 to 500 hp, and it is not for the compressor in an air conditioner, which the AC breaker size calculator covers.
- Choose single phase or three phase, the rated motor voltage and the horsepower. The page reads the full-load current from the NEC table for that motor, not from the nameplate amps.
- Pick a breaker or a fuse. To size the overload limit, enter the nameplate full-load current and its service factor group. Leave the amps blank to see the percentages only.
- The result shows the conductor at 125 percent of the table current, the largest breaker or fuse under Table 430.52, the larger size that applies if the motor will not start, and the overload limit.
Example result for the default inputs
10 hp, 460 V three-phase induction motor, inverse time breaker. NEC Article 430 as reprinted, not read in NFPA's viewer.
Table full-load current
14 A
Conductor ampacity, at least
17.5 A
Inverse time breaker, at most
35 A
| Full-load current from the table | Table 430.250 gives 14 A for a 10 hp, 460 V three-phase induction motor. The 460 V column is permitted for 440 to 480 V systems, so a 480 V supply uses it. |
|---|---|
| Branch conductor, 125 percent (430.22) | 1.25 x 14 A = 17.5 A of ampacity. The smallest size in Table 310.16 is copper 12 AWG on the 60°C (140°F) column or 14 AWG on the 75°C (167°F) column, and aluminum 10 AWG on the 60°C (140°F) column or 12 AWG on the 75°C (167°F) column. On a circuit of 100 A or less, use the 60°C (140°F) column unless every termination is rated 75°C (167°F): the controller and disconnect terminals marked for it, and the motor terminals marked for it or the motor marked design letter B, C or D (110.14(C)(1)(a)); above 100 A the 75°C (167°F) column applies (110.14(C)(1)(b)). Ambient and conductor-count corrections are not applied. |
| Inverse time breaker, Table 430.52 | 250 percent x 14 A = 35 A, which is a standard inverse time breaker rating (Table 240.6(A)), so 35 A. |
| If the motor will not start (Exception No. 2) | 400 percent x 14 A = 56 A. The largest standard size at or below that is 50 A. Use it only if the 35 A size trips on starting. |
| Other devices at the Table 430.52 percentage | Dual-element (time-delay) fuse 25 A, nontime-delay fuse 45 A, instantaneous-trip breaker 112 A setting. |
| Overload from the nameplate (430.32) | Enter the nameplate full-load current to get the limit. The device may be set at up to 125 percent of it, or 140 percent if that will not start the motor or carry the load. |
| Not worked here | The disconnect (430.110), the controller, a feeder for more than one motor (430.24, 430.62), voltage drop and the conduit. A motor that starts a hard load, a code-letter motor or a motor on a drive needs the full Article 430. |
- Table current sizes the conductor and the short-circuit device (430.6(A)(1)). Overload protection follows the nameplate current instead. Both tables are written for motors at usual speeds with normal torque, so a low-speed, multispeed or high-torque motor needs its nameplate and the code text.
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the current, the wire, the device and the overload limit are worked
Four numbers come out of a motor circuit. An NEC table gives the full-load current by horsepower and voltage, and the nameplate is not used for it. Conductors are sized at 125 percent of that table current. A breaker or fuse is limited to a percentage of the table current that depends on the device, with a rule that lets the next standard size up be used and a second rule for a motor that will not start. Overload protection is limited by a percentage of the nameplate current instead. Each result is a maximum, and a smaller device is allowed when the motor starts and runs on it.
- Full-load current
I = Table 430.248 or 430.250 value for hp and voltageA 10 hp motor at 460 V, three phase, is 14 A in Table 430.250, and a 1 hp motor at 115 V, single phase, is 16 A in Table 430.248. The value is for a motor at usual speed with normal torque. 430.6(A)(1) uses it for the conductor and the short-circuit device in place of the nameplate current.- Branch conductor
ampacity at least 1.25 x I, Table 310.16430.22 asks for 125 percent of the table current for one continuous-duty motor. 10 hp at 460 V gives 1.25 x 14 A = 17.5 A, which is copper 12 AWG on the 60°C (140°F) column or 14 AWG on the 75°C (167°F) column. On a circuit of 100 A or less the 60°C (140°F) column applies unless every termination is rated 75°C (167°F), the motor by marking or by design letter B, C or D, and the controller and disconnect by marking (110.14(C)(1)(a)); above 100 A the 75°C (167°F) column applies (110.14(C)(1)(b)).- Short-circuit device, Table 430.52
maximum rating = percent x I, then the next standard size upThe percentages for a single-phase or squirrel-cage motor are 250 for an inverse time breaker, 175 for a dual-element fuse, 300 for a nontime-delay fuse and 800 for an instantaneous-trip breaker, 1100 for a Design B energy-efficient motor. A 25 hp motor at 460 V draws 34 A, so the figures are 85 A for the breaker, 59.5 A for the dual-element fuse and 102 A for the nontime-delay fuse. Exception No. 1 takes each up to the next standard size in Table 240.6(A), 90, 60 and 110 A.- Motor will not start
Exception No. 2, largest standard size at or below the limitIf the Table 430.52 size trips on starting, the device may be raised, never above 400 percent for a nontime-delay fuse of 600 A or less, 225 percent for a time-delay fuse, and for an inverse time breaker 400 percent up to 100 A of full-load current and 300 percent above it. A 50 hp motor at 460 V has 65 A, so the breaker goes from 175 A to at most 250 A. A 100 hp motor at 460 V is over 100 A at 124 A, and its limit stays 350 A. Instantaneous-trip settings go to 1300 percent, or 1700 percent for Design B energy-efficient motors.- Overload device
at most 1.25 x nameplate FLA, or 1.15 x430.32(A)(1) allows 125 percent of the nameplate current for a motor marked with a service factor of 1.15 or more or a temperature rise of 40°C (72°F) or less, and 115 percent for any other motor. A 20 A nameplate gives 25 A in the first group and 23 A in the second. If that setting will not start the motor or carry the load, 430.32(C) allows up to 140 percent and 130 percent, 28 A and 26 A here.
Eight motors through the same formula
The 7-1/2 hp, 230 V row is the EC&M example in the 2017 NEC, 22 A, 10 AWG copper in the 60°C (140°F) column and a 60 A breaker. The 25 hp, 460 V row is the 34 A motor in the IAEI article, with 8 AWG copper at 75°C (167°F). Breakers are inverse time. The last column is the largest breaker if the motor will not start on the first one.
| Motor | Table FLC, A | Conductor, A | Copper 60°C (140°F), AWG | Copper 75°C (167°F), AWG | Breaker, A | If it will not start, A |
|---|---|---|---|---|---|---|
| 10 hp, 460 V, three phase | 14 | 17.5 | 12 | 14 | 35 | 50 |
| 7-1/2 hp, 230 V, three phase | 22 | 27.5 | 10 | 10 | 60 | 80 |
| 25 hp, 460 V, three phase | 34 | 42.5 | 6 | 8 | 90 | 125 |
| 5 hp, 230 V, three phase | 15.2 | 19 | 12 | 14 | 40 | 60 |
| 50 hp, 460 V, three phase | 65 | 81.25 | 3 | 4 | 175 | 250 |
| 100 hp, 460 V, three phase | 124 | 155 | n/a | 2/0 | 350 | 350 |
| 1 hp, 115 V, single phase | 16 | 20 | 12 | 14 | 40 | 60 |
| 2 hp, 230 V, single phase | 12 | 15 | 14 | 14 | 30 | 45 |
Copper only. n/a in the 60°C column: above 100 A the 75°C (167°F) column applies (110.14(C)(1)(b)). Aluminum, the other devices and the overload limit are in the result above for the motor you pick. Sizes are the smallest in Table 310.16 for the conductor ampacity shown, with no ambient or conductor-count correction.
Table 430.52 percentages used
Percent of the table full-load current for single-phase and squirrel-cage motors, as reprinted. The first column is the Table 430.52 maximum, and the second is the largest rating if the motor will not start on it (Exception No. 2). An inverse time breaker is held to 300 percent in the second column when the full-load current is above 100 A, and the 400 percent for a nontime-delay fuse applies up to 600 A; fuses rated 601 to 6,000 A are held to 300 percent. A time-delay Class CC fuse takes the nontime-delay fuse row. Design B energy-efficient applies to three-phase motors only.
| Device | Table 430.52, percent | Exception No. 2, percent |
|---|---|---|
| Inverse time breaker | 250 | 400 |
| Dual-element (time-delay) fuse | 175 | 225 |
| Nontime-delay fuse | 300 | 400 |
| Instantaneous-trip breaker | 800 (1100 Design B energy-efficient) | 1300 (1700 Design B energy-efficient) |
Standards and data sources
- NEC 2023, Tables 430.248 and 430.250, 430.6(A), 430.22, 430.32, 430.52 and Table 430.52, Table 310.16, Table 240.6(A) and 110.14(C) - the table full-load currents, the conductor, overload and short-circuit rules and the standard sizes. The NEC text was not read in NFPA's viewer, which needs a login. Wording and numbers come from the reprints below, and in the 2023 edition Table 430.52 is numbered Table 430.52(C)(1) and the two exceptions are 430.52(C)(1)(a) and (b), as Mike Holt Enterprises reports.
- 2011 NEC pages 70-337 and 70-338 (Tables 430.248, 430.249 and 430.250), as scanned by NECA-IBEW and Trask Instrumentation - every full-load current on this page, read cell by cell off two scans of the printed 2011 pages and checked against reuven.tools and electriciancalc.com, which print the same numbers, and against a 2023 table at voltcal.com for the 460 V column. The 200 V columns have fewer independent checks than the rest.
- Mike Holt in EC&M, Stumped by the Code? Code Requirement for Sizing the Overcurrent Protection of Conductors (2018, 2017 NEC) - the worked motor example this page reproduces, a 7-1/2 hp, 230 V, three-phase motor at 22 A, with a conductor of at least 28 A on 10 AWG copper in the 60°C (140°F) column and an inverse time breaker of 22 x 2.50 = 55 A taken up to 60 A.
- IAEI Magazine, Overcurrent Protection Part 2 (2007) - the 34 A motor example, 42.5 A of conductor on 8 AWG at 75°C (167°F), a dual-element fuse of 1.75 x 34 = 59.5 A taken up to 60 A, a nontime-delay fuse of 110 A and an inverse time breaker of 90 A.
- Jade Learning, Understanding Motor Branch-Circuit Overcurrent Protection Devices and Motor Calculations Part IV - the Table 430.52 percentages, the next-size-up exception, the 400, 225, 300 and 1300 percent limits for a motor that will not start, and the 50 A, 60 A and 60 A worked answers for 28 A, 21 A and 27 A motors.
- Mike Holt in EC&M, Motor Calculations Part 2, and the EC&M Code Quiz on overload devices for continuous-duty motors - the 125 and 115 percent overload limits from the nameplate, the 140 and 130 percent limits of 430.32(C), and the 1 hp, 115 V and 5 hp, 230 V single-phase examples.
Limitations of this calculator
- This page gives preliminary numbers for estimating and for checking a drawing or a quote. A licensed electrician or engineer sizes and installs the circuit under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
- NFPA's own viewer was not used to read the NEC text. Table currents come from two scans of the printed 2011 pages and were checked against web reprints, and the rules for the conductor, the short-circuit device and the overload come from EC&M, IAEI and Jade Learning. Fewer independent checks exist for the 200 V columns than for the rest. Section numbers moved in the 2023 edition, and the 2023 table pages were not opened. Check the edition and the local amendments your AHJ uses.
- The page works one general-purpose motor on its own branch circuit, single phase (Table 430.248) or three-phase induction (Table 430.250). Synchronous, wound-rotor, direct-current and two-phase motors, 2300 V motors, 115 V three-phase motors and multispeed motors are not covered. A motor with a variable-frequency drive, a motor in a hazardous location and a hermetic compressor each have their own rules.
- A hermetic refrigerant compressor, as in an air conditioner or a heat pump, is sized from its nameplate under Article 440 and not from these tables. The AC breaker size calculator covers that case.
- Wire sizes are the smallest in Table 310.16 for 125 percent of the table current, for copper and aluminum in the 60°C (140°F) and 75°C (167°F) columns, up to 4/0 AWG. Ambient and conductor-count corrections, voltage drop and conduit are not worked, and a larger motor can need a size above 4/0 AWG, which the page flags. The small-conductor limits of 240.4(D) are not applied, because Table 240.4(G) sends motor circuits to Article 430.
- Short-circuit results are a maximum under Table 430.52 and its exceptions, for single-phase and squirrel-cage motors. Exception No. 2 is for a motor that will not start on the first size, and the page does not decide that for you. A time-delay Class CC fuse takes the nontime-delay fuse percentages (a note to Table 430.52 and Exception No. 2), so pick the nontime-delay fuse for it, and an instantaneous-trip breaker is allowed only in a listed combination motor controller. Wound-rotor, synchronous and direct-current rows of the table are not used.
- Overload limits are a percentage of the nameplate current you enter. 430.32(A) is read in the sources for continuous-duty motors over 1 hp without built-in thermal protection, so a motor of 1 hp or less (430.32(B) when automatically started, 430.32(D) when started by hand) and a motor with a built-in protector follow other parts of 430.32. Percentages from 430.32(A)(1) and (C) are shown, and no relay or heater is chosen.
- Disconnect sizing (430.110), the controller, a feeder or a short-circuit device for more than one motor (430.24, 430.62), a combination starter and a capacitor are outside this page. Table full-load current is not the starting current, and a motor with a high-inertia load or a code letter can need engineering.
Common mistakes with motor circuits
- Sizing the wire from the nameplate. A 10 hp, 460 V, three-phase motor is 14 A in Table 430.250, and the conductor is 125 percent of that, 17.5 A. The nameplate of an actual motor can read higher or lower. 430.6(A)(1) takes the table value for the conductor and the short-circuit device, and the nameplate current is kept for the overload device.
- Reading Table 430.52 as the size to install. A 7-1/2 hp motor at 230 V works out to 55 A on an inverse time breaker, and 60 A is the next standard size, which Exception No. 1 allows. These percentages are maximums. A smaller standard breaker is allowed if the motor starts on it, and a larger one is not allowed until Exception No. 2 applies.
- Raising the device before the motor has failed to start. Exception No. 2 exists for a motor that trips the device on its first size. A 50 hp motor at 460 V takes a 175 A breaker from Table 430.52, and the exception lifts the limit to 250 A. The larger device protects the circuit less, so it is a step taken after the smaller one has been tried.
- Picking the column from the supply voltage instead of the motor. The tables list rated motor voltages and permit each column for a range of system voltages. A 480 V system uses the 460 V column and a 240 V system the 230 V column. The 208 V column is for motors rated 208 V, so the nameplate voltage picks the column and not the voltage at the panel. The same 10 hp motor is 14 A at 460 V and 28 A at 230 V.
- Setting the overload relay from the table current. The overload device is sized from the nameplate. For a nameplate of 20 A the limit is 25 A when the motor is marked service factor 1.15 or more, and 23 A for any other motor. The table value of 14 A for the same motor would give 17.5 A, which belongs to the conductor and not to the relay.
- Using a motor table for an air-conditioner compressor. A hermetic refrigerant compressor in an air conditioner or heat pump has its own nameplate rules in Article 440, with a minimum circuit ampacity and a maximum overcurrent protection marked on the unit. These Article 430 tables do not apply to it. The AC breaker size calculator works from that nameplate.
Common questions about motor circuit sizing
What size breaker does a 10 hp, 460 V, three-phase motor need?
At most 35 A for an inverse time breaker. Table 430.250 gives 14 A for a 10 hp motor at 460 V, Table 430.52 allows 250 percent of it, and 14 x 2.50 = 35 A is a standard size. If the motor will not start on it, Exception No. 2 allows up to 400 percent, which is a 50 A breaker.
What wire size does a 10 hp, 460 V motor need?
The conductor needs at least 125 percent of the table current, 17.5 A (430.22). In Table 310.16 that is copper 12 AWG on the 60°C (140°F) column or 14 AWG on the 75°C (167°F) column. At this current the 60°C (140°F) column is the one to use unless the controller and disconnect terminals are marked for 75°C (167°F) and the motor is too, by marking or by design letter B, C or D (110.14(C)(1)(a)). Voltage drop and conduit fill are separate checks.
Why does the NEC use a table current and not the nameplate?
430.6(A)(1) says to use the full-load current in Tables 430.247 to 430.250, not the nameplate, for the conductor, the short-circuit device and the disconnect. The overload device is the exception, and it is set from the nameplate current (430.6(A)(2)). The tables hold a typical current so that the circuit does not change when a motor is replaced by another of the same horsepower.
What are the percentages in Table 430.52?
For single-phase and squirrel-cage motors, the maximum is 300 percent of the full-load current for a nontime-delay fuse, 175 percent for a dual-element time-delay fuse, 800 percent for an instantaneous-trip breaker (1100 percent for a Design B energy-efficient motor) and 250 percent for an inverse time breaker. For the 34 A motor at 25 hp and 460 V that is 102 A for a nontime-delay fuse, 59.5 A for a dual-element fuse, 85 A for an inverse time breaker and 272 A for an instantaneous-trip setting. The page reads these from reprints of the table, not from NFPA's text.
What do Exception No. 1 and Exception No. 2 allow?
Exception No. 1 lets the result be taken up to the next standard size when it does not land on one. A 55 A result is a 60 A device, and 59.5 A is 60 A. Exception No. 2 applies when that size will not let the motor start. It raises the limit to 400 percent for a nontime-delay fuse of 600 A or less, 225 percent for a time-delay fuse, and for an inverse time breaker 400 percent when the full-load current is 100 A or less and 300 percent above that. The result is the largest standard size at or below the limit, 60 A for a 20 hp, 460 V motor on dual-element fuses.
How big can the overload protection be?
It is set from the nameplate current. For a motor marked with a service factor of 1.15 or more, or a temperature rise of 40°C (72°F) or less, the limit is 125 percent of the nameplate amps, and for any other motor 115 percent (430.32(A)(1)). A 20 A nameplate gives 25 A and 23 A. If the motor will not start or carry its load on that, 430.32(C) allows up to 140 percent and 130 percent, 28 A and 26 A. A motor of 1 hp or less, or one with built-in thermal protection, follows other parts of the section.
Which voltage column do I use for a 480 V or 240 V motor?
The tables list the 230, 460 and 575 V columns, and say each is permitted for system voltages of 220 to 240, 440 to 480 and 550 to 600 V. A 480 V supply uses the 460 V column, which is 14 A for a 10 hp motor, and a 240 V supply uses the 230 V column, 28 A. A motor rated 208 V or 200 V has its own column.
Should I use a breaker or a fuse for the motor branch circuit?
Either works if it stays within Table 430.52. A dual-element fuse is limited to 175 percent and an inverse time breaker to 250 percent, so for a 25 hp motor at 460 V the fuse tops out at 60 A and the breaker at 90 A. Nontime-delay fuses can go to 110 A, but they need a motor that starts without a long inrush, so many installers choose the time-delay type. An instantaneous-trip breaker is allowed only as part of a listed combination motor controller.
Is this the same as sizing an air-conditioner breaker?
No. A hermetic refrigerant compressor in an air conditioner or heat pump is sized under Article 440 from the minimum circuit ampacity and the maximum overcurrent protection on its nameplate. This page covers general-purpose motors under Article 430, such as pumps, fans, conveyors and shop machines.
Does this replace an electrician?
No. This page is for estimating and for checking numbers on a drawing or a quote. A licensed electrician or engineer sizes and installs the circuit under a permit, and the local authority having jurisdiction inspects it.