Calculator · HVAC circuits
AC breaker size calculator
There is no breaker size for a tonnage. The unit's nameplate prints a minimum circuit ampacity for the wire and a maximum overcurrent protection for the breaker, and those two numbers decide the circuit, and everything else on the run, from the disconnect to the wire, follows from them. This page works the same numbers from the compressor and fan currents, so you can check a nameplate or size a circuit when the plate is not at hand. Electric heat strips get their own mode. Pair it with the AC wire size calculator for the conductor.
- Find the minimum circuit ampacity (MCA) and the maximum overcurrent protection (MOCP) on the unit's data plate. If they are printed, they govern.
- Type the largest compressor's rated-load current and the fan and other motor amps, or the heater kW and voltage. The nameplate numbers go in the optional fields.
- The result shows the MCA, the largest breaker or fuse, and the smallest breaker at or above the MCA. The largest is the nameplate MOP when you enter it. With only the nameplate MCA entered, the page asks for the MOP. With neither, it is worked by the manufacturer method when a compressor is the largest load.
Example result for the default inputs
Compressor circuit, largest compressor 17.6 A, other loads 1.2 A. NEC 2023 Article 440. These are the page example values, from a published worked example and not a typical unit. Replace them with the currents on the nameplate.
Minimum circuit ampacity (worked from the fields)
23.2 A
Maximum breaker or fuse (worked, manufacturer's method)
40 A
Smallest breaker at or above the MCA
25 A
| MCA, 440.33 | 1.25 x 17.6 A + 1.2 A = 23.2 A |
|---|---|
| Maximum, the manufacturer's method | 2.25 x 17.6 A + 1.2 A = 40.8 A, rounded down to the standard size 40 A. This is the method one manufacturer publishes for UL listing (Titus, for terminal units). A compressor maker's own figure may differ, and the nameplate governs. 225 percent is the top of what NEC 440.22(A) allows. |
| NEC 440.22(A) basic limit, a reference line | 1.75 x 17.6 A + 1.2 A = 32 A. This is the basic limit NEC 440.22(A) starts from, without an allowance for starting the compressor. The code lets the rating go higher, up to 225 percent, when the compressor will not start on the smaller breaker. A breaker at 175 percent can trip at start, and then the nameplate value is the one to use. |
| What to install | A standard breaker from 25 A to 40 A. If the nameplate prints an MOP, that number is the limit and governs. A breaker at the 175 percent reference line can trip when the compressor starts, and then the nameplate value is the one to use. |
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the circuit is worked
Two things set the circuit for a compressor. The wire has to carry the minimum circuit ampacity, and the breaker has to be small enough to protect the circuit yet big enough to let the compressor start. Article 440 of the NEC treats them separately, which is why the breaker can be larger than the wire would suggest.
- Minimum circuit ampacity (MCA)
MCA = RLA of every compressor + full-load amps of the other motors + 25 percent of the highest of themNEC 440.33 adds 25 percent of the highest motor-compressor or motor current in the group to the sum of all the loads. Usually that is the compressor, and the MCA is 1.25 x its RLA plus the rest. Here the fan and other motors are one field, so when their total is the highest the page takes it as one motor, which can only raise the MCA. The worked example, a 17.6 A compressor with a 1.2 A fan, comes to 23.2 A.- Maximum breaker or fuse (MOP)
limit = 2.25 x RLA of the largest compressor + a second compressor + other motors, rounded down to a standard size, then raised to the size of the MCA and to 15 A if lowerThe method one manufacturer publishes for UL listing (Titus, for terminal units), and a compressor maker's own figure may differ. 225 percent is also the top of what NEC 440.22(A) allows. In the worked example 2.25 x 17.6 A + 1.2 A is 40.8 A, so 40 A. It is worked only when nothing from the nameplate is entered and a compressor is the largest load.- NEC basic limit, a reference line
1.75 x RLA of the largest compressor + a second compressor + other motorsThe basic limit NEC 440.22(A) starts from, without an allowance for starting the compressor. The code allows more, up to 225 percent, when the compressor will not start on the smaller breaker. In the worked example it is 32 A. A breaker at 175 percent can trip at start, and then the nameplate value is the one to use.- Standard sizes
NEC Table 240.6(A), from 10 A up440.22(A) also says the device is not required to be smaller than 15 A, and the manufacturer method prints no less, so a worked maximum is never below 15 A. A nameplate MOP below 15 A is shown as the standard breaker it allows, with a warning to check the plate.- Heat strips
I = kW x 1,000 x V / Vrated squared; conductor at 1.25 x I; elements in groups of 48 A or lessNEC 424.4(B) for the 125 percent on the conductors, and 424.22(B) for the heating elements, which are protected at no more than 60 A and subdivided into groups of 48 A or less when the equipment is rated above 48 A. A 10 kW strip at 240 V draws 41.7 A, so its circuit needs 52.1 A of conductor and a 60 A breaker. A heater circuit is also held to the small-conductor limits of 240.4(D), which the result shows.
Seven circuits worked the same way
The currents below are illustrations and published worked examples, not typical values for any equipment. Each row runs through the same function the form uses.
| Circuit | Conductor ampacity, A | Breaker, A |
|---|---|---|
| 17.6 A compressor, 1.2 A fan (an example from a published article) | 23.2 | 25 to 40 |
| 20 A compressor, 2.5 A fan | 27.5 | 30 to 45 |
| 18 A compressor alone | 22.5 | 25 to 40 |
| Two compressors, 20 A and 15 A, 3 A of fans | 43 | 45 to 60 |
| 10 kW heat strips at 240 V | 52.1 | 60 |
| 15 kW heat strips at 240 V | 39.1 per group | 40, on each of 2 groups |
| 10 kW (240 V element) on a 208 V supply | 45.1 | 50 |
For the 20 A compressor with a 2.5 A fan, 225 percent comes to 47.5 A, so the maximum is 45 A. That follows the method one manufacturer publishes for UL listing, and a compressor maker's own figure may differ. The NEC basic limit of 175 percent, 37.5 A, is a reference line. NEC 440.22(A) allows more, up to 225 percent, when the compressor will not start on the smaller breaker, and a breaker sized at 175 percent can trip at start. In that case the nameplate value is the one to use. On heat strips, the same 10 kW element draws 41.7 A on 240 V and 36.1 A on 208 V, because it makes 7.51 kW there.
Standards and data sources
- NEC 2023, Article 440, Air-Conditioning and Refrigerating Equipment - 440.22(A) for the breaker or fuse limit, 440.32 and 440.33 for the conductor ampacity, 440.4(B) for the nameplate markings, and 440.34 where other loads share the circuit.
- NEC 2023, Article 424, Fixed Electric Space-Heating Equipment - 424.4(B) for the 125 percent conductor sizing and 424.22(B) for dividing the resistance elements of a heater rated above 48 A into groups of 48 A or less, protected at no more than 60 A.
- NEC 2023, 110.3(B) and Table 240.6(A) - 110.3(B) for installing listed equipment according to its instructions and markings, and Table 240.6(A) for the standard ampere ratings of breakers and fuses.
Limitations of this calculator
- The nameplate comes first. When the unit prints a minimum circuit ampacity (MCA) and a maximum overcurrent protection (MOP or MOCP, sometimes called max fuse), those two printed numbers govern the installation. Without them the page works both figures from the currents; once you enter them, it shows the printed values, checks them against the currents and does not print a worked maximum beside them. NEC 110.3(B) has listed equipment installed according to its listing and labeling, and 440.4(B) has multimotor equipment marked with these values.
- This page gives preliminary numbers for estimating and for checking a quote. A licensed electrician sizes, installs and signs off the circuit under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
- No typical RLA, MCA or MOCP is given for any tonnage or model. They differ between manufacturers and between two units of the same tonnage, so you type in the numbers from the data plate. The default example is a published worked example, not a typical unit.
- The calculation follows the 2023 edition of the NEC. Your state or city may have adopted another edition or added amendments. NFPA committee documents show that the 2023 cycle added an exception to 440.22(A) about the next higher standard size. The final 2023 text was not read, and this page does not use it. Check the edition your AHJ enforces.
- The maximum follows the method one manufacturer publishes for UL listing (Titus, for terminal units): 225 percent of the largest motor plus the other loads, rounded down, never below the MCA's size and never below 15 A. A compressor maker's own figure may differ, which is one more reason the printed MOP governs. The 175 percent line is the NEC basic limit, shown for reference. The worked maximum appears only when nothing from the nameplate is entered and a compressor is the largest load. When the fan and other motors total more, NEC 440.22(B)(2) sets the maximum, which the page does not model, so it gives none. A nameplate MOP is shown as the breaker it allows, even below 15 A, and as per nameplate when it is above what 225 percent of the currents gives.
- The smallest breaker shown, the smallest standard size at or above the MCA, is this calculator's convention for a sensible lower end. The code sets a maximum for the compressor device, and it does not name a minimum here.
- The standard sizes are the ones in Table 240.6(A) from 10 A up. The extra fuse-only sizes of 1, 3, 6 and 601 A are not offered.
- Compressor mode takes one or two compressors and works in amps, so it does not depend on the number of phases. Heat strip mode is single phase only. A three-phase heater needs a different current formula that this page does not carry.
- A heater kit inside an air handler has its own MCA and MOCP on the unit's nameplate, with the blower motor counted in. Use those numbers. The heat strip mode is for a stand-alone resistance heater or a kit you are checking by itself.
- Above 48 A the heating elements are divided into groups of 48 A or less, and the page splits them evenly, which real kits often do not, for example 15 kW as 10 kW + 5 kW. The groups, and how many supply circuits feed them, are on the heater's nameplate. The sizes shown are for one branch circuit per group, and a kit with a single supply circuit uses its own nameplate numbers.
- Cord-and-plug room air conditioners (Article 440, Part VII), motor circuits that are not hermetic compressors (Article 430), disconnects, ground-fault and arc-fault protection, and the equipment grounding conductor are not covered.
Common mistakes sizing an AC breaker
- Sizing the breaker from the wire. For a compressor circuit the breaker is not chosen from the conductor's ampacity. Article 440 sets its own limit from the compressor current, and the nameplate prints the result as MOCP. A breaker larger than the wire's ampacity can be correct there. A heater circuit is different, because it is not an Article 440 circuit and the small-conductor limits of 240.4(D) hold the breaker down on 14, 12 and 10 AWG.
- Using the MCA as the breaker size. The MCA is a floor for the wire. The breaker has a ceiling, the MOCP. A breaker equal to the MCA is the least that carries the load, and one above the MOP is never allowed. Read the plate.
- Using the motor tables of Article 430. A hermetic compressor is worked from its rated-load current under Article 440, with different factors from an ordinary motor. Use Article 440 for the compressor and Article 430 only for motors that are not hermetic compressors.
- Stopping at 175 percent. The NEC's 175 percent figure is where 440.22(A) starts, and the code allows up to 225 percent when the compressor will not start on the smaller breaker. A breaker at 175 percent can trip at start. In the worked example the page shows 40 A against a 32 A basic limit. Where the plate prints an MOP, install to it.
- A rule of thumb per ton. Two 3 ton units can print different MCA and MOCP, because the compressor, the fan motors and the efficiency differ. Read the plate on the unit you are wiring.
- Treating a large heat strip as one load. Above 48 A the heating elements are divided into groups of 48 A or less. A 15 kW strip at 240 V draws 62.5 A, which is two groups of 31.3 A each. Real kits often divide unevenly, for example 15 kW as 10 kW + 5 kW, and the 10 kW group needs a 60 A breaker. The heater's nameplate has the groups and the supply.
- Forgetting that 240 V ratings fall on 208 V. A heater rated in kW at 240 V makes about three quarters of that on 208 V. The current drops too, so work the circuit at the voltage that will really be there.
Common questions about AC breaker sizing
What size breaker do I need for a 3 ton AC unit?
There is no breaker size that goes with a tonnage. Two 3 ton units can have different compressors, fan motors and efficiencies, so each prints its own numbers on the data plate. The minimum circuit ampacity (MCA) is the least the wire has to carry, and the maximum overcurrent protection (MOCP) is the largest breaker or fuse allowed. Read both off the plate on the outdoor unit. If the plate is not in front of you, type the compressor's rated-load current and the fan's amps into this page for a cross-check.
What is the difference between MCA and MOCP?
MCA is the minimum circuit ampacity. It is the lowest ampacity the wire to the unit may have, and it comes from the sum of the loads plus 25 percent of the highest of them, usually the compressor. MOCP is the maximum overcurrent protection, the largest breaker or fuse the manufacturer allows. The method one manufacturer publishes for UL listing (Titus, for terminal units) works it from 225 percent of the largest compressor plus the other loads, rounded down to a standard size, and a compressor maker's own figure may differ. The wire is chosen up from the MCA and the breaker is chosen at or below the MOP.
Can the breaker be bigger than the wire is rated for?
For an air conditioner it can, within the nameplate. NEC 240.4(G) sends air-conditioning circuit conductors to Article 440, so a compressor circuit follows 440.22 instead of the ordinary small-conductor limits. In the worked example the MCA is 23.2 A, and the breaker may be as large as 40 A. The wire still has to carry the MCA. Electric heat strips are not covered by that rule, so a breaker on 12 AWG copper there stops at 20 A and on 10 AWG copper at 30 A.
How do I size a breaker for electric heat strips?
Find the heater current from kW and voltage, then take 125 percent for the conductors. A 10 kW strip at 240 V draws 41.7 A, so its circuit needs 52.1 A of conductor and a 60 A breaker. At 15 kW the strip draws 62.5 A, above 48 A, so its heating elements are divided into two groups of 31.3 A, which come to 40 A breakers if each group has its own circuit and the load is divided evenly. Real kits often divide unevenly, for example 15 kW as 10 kW + 5 kW, and the 10 kW group draws 41.7 A and needs a 60 A breaker. The groups come from the heater's nameplate. A kit may also use a single supply circuit. Inside an air handler the MCA and MOCP on its nameplate apply, and those govern.
How is the maximum breaker worked out?
This page repeats the method one manufacturer publishes for UL listing (Titus, for terminal units), and a compressor maker's own figure may differ. Take 225 percent of the largest compressor's current, add the other loads, round down to a standard size, and never go below the size of the MCA or below 15 A. The page works this only when a compressor is the largest load and no nameplate value is entered. For the worked example 2.25 x 17.6 A + 1.2 A is 40.8 A, so 40 A. For a 20 A compressor with a 2.5 A fan it is 47.5 A, so 45 A. 225 percent is also the top of what NEC 440.22(A) allows. The nameplate MOP governs over this number.
What is the 175 percent rule, then?
NEC 440.22(A) starts from 175 percent of the largest compressor's current plus the other loads, and allows more up to 225 percent where that will not start the compressor. The page shows the 175 percent figure as a reference line, the basic limit without an allowance for starting. For the worked example it is 32 A. A breaker at 175 percent can trip when the compressor starts, and then the nameplate value is the one to use. For the 18 A compressor alone it is 31.5 A against a maximum of 40 A.
What if the nameplate and this page disagree?
Go with the nameplate. The equipment is listed and tested for the values printed on it, and NEC 110.3(B) has the installer follow them. A manufacturer works its MOP by its own method, so the plate can differ from this page for good reasons, such as a branch-circuit selection current or its own rounding. If the gap is large, recheck the currents you typed. Trust the plate.
Do I need an electrician for this?
Yes. This page is for estimating and for checking numbers on a quote. A licensed electrician sizes and installs the circuit under a permit, and the local authority having jurisdiction inspects it.