For field use by EPA 608 certified technicians. Published PT charts for R-454B differ slightly from one another. When you charge a system, follow the chart and the instructions from the equipment manufacturer.

Maintained by BuildSolver · Updated

Chart · Refrigerant pressure and temperature

Refrigerant PT chart and saturation lookup

Look up where R-454B, R-410A, R-32 or R-22 boils at a given pressure, or what the gauge should read at a given saturation temperature. Blends get both the dew point and the bubble point. The full chart is printed below the calculator. To turn these numbers into a charge check with your line temperatures, use the superheat and subcooling calculator.

  1. Select the refrigerant printed on the outdoor unit data plate.
  2. Temperature to pressure gives the gauge reading for a saturation temperature. Pressure to temperature turns a gauge reading into a saturation temperature.
  3. Type the temperature in °F or the gauge pressure in psig.
  4. Leave the field blank for sea level. Above a few thousand feet, enter the job elevation so the gauge numbers match what your manifold shows.
  5. On R-454B and R-410A, use the dew point for superheat and the bubble point for subcooling.

Saturation pressure and temperature only, from -40 to 140°F. Gauge pressures are psig at sea level unless you enter an elevation.

The chart covers -40 to 140°F saturation. Gauge pressure is psig, as a manifold reads it.

Leave blank for sea level, the way printed PT charts are made. Gauges read against local air pressure, so they read higher in the mountains. If your gauge already corrects its reading to sea level, leave this blank so the correction is not applied twice.

Example result for the default inputs

R-454B · 40.0°F to pressure · sea-level gauge

Dew point, for superheat

107.5 psig

Bubble point, for subcooling

113.2 psig

Calculation details
Saturation temperature40.0°F
Bubble minus dew pressure5.7 psi
Glide at 107.5 psig2.7°F
Superheat readsDew point line, vapor
Subcooling readsBubble point line, liquid
AtmosphereSea level, 14.696 psia
Absolute pressure122.2 / 127.9 psia
Property dataCoolProp 8.0.0, checked against manufacturer PT charts

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the lookup works

The chart is a table of saturation pressure for every whole degree from -40 to 140°F, computed with CoolProp 8.0.0, an open thermophysical property library. Between whole degrees the calculator interpolates in a straight line. Going from pressure to temperature it runs the same table backwards. It never extrapolates past either end.

Pressure from temperature
P = P(T1) + (P(T2) - P(T1)) x (T - T1)T1 and T2 are the whole degrees either side of the temperature you enter. The table steps are small enough that the straight line adds less error than a gauge needle can show.
Temperature from pressure
T = T1 + (P - P(T1)) / (P(T2) - P(T1))The same table read the other way, so a round trip from temperature to pressure and back lands where it started.
Dew point and bubble point
P_bubble(T) > P_dew(T) on a blendA blend boils over a range of temperatures. The dew point line is where the last drop of liquid boils off, the bubble point line where the first bubble forms. R-22 and R-32 are single refrigerants and have one line.
Temperature glide
glide = T_dew(P) - T_bubble(P)At one pressure the dew point sits above the bubble point. On R-454B at a 107.5 psig evaporator that gap is 2.7°F. On R-410A it is a fraction of a degree.
Gauge reading at altitude
P_gauge = P_abs - p_atm, p_atm = 14.696 x (1 - 6.8754e-6 x Z)^5.2559A manifold reads pressure above the air around it. The standard atmosphere from ASHRAE Handbook Fundamentals, Chapter 1, gives p_atm in psia at elevation Z in feet. Printed charts assume 14.696 psia, which is sea level.

Readings you see on real systems

Each row runs through the same lookup the form uses. Blends show the dew point first and the bubble point second.

Five refrigerant lookups with dew and bubble point results
CaseDew pointBubble point
R-454B evaporator at 40°F107.5 psig113.2 psig
R-410A condensing at 115°F391.2 psig392.3 psig
R-32 suction gauge at 140 psig47.8°Fsame line
R-22 evaporator at 45°F76.1 psigsame line
R-410A at 40°F in Denver, 5,280 ft121.0 psig121.4 psig

On R-454B at 40°F the bubble point line sits 5.7 psi above the dew point line. Read the other way, at the 107.5 psig dew pressure the liquid starts to boil at 37.3°F, 2.7°F below the dew point. That gap is why a blend has two columns and why the line you read matters. R-454B also runs 10.9 psi lower than R-410A at the same 40°F dew point, so an R-410A chart on an R-454B system gives the wrong answer.

In Denver, at 5,280 ft, the air around the gauge is at lower pressure, so every reading comes out 2.6 psi higher than at sea level. Look that R-410A reading up on a sea-level chart and the saturation temperature comes out 1.2°F too warm, which shows up directly as an error in superheat.

Saturation pressure chart, -20 to 130°F

Gauge pressure in psig at sea level. The R-410A column is the dew point line; its bubble point line runs at most 1.2 psi higher over this range. R-32 and R-22 have one line.

Saturation pressure in psig at sea level for R-410A, R-32, R-22 and R-454B, -20 to 130 degrees F
SaturationR-410AR-32R-22R-454B dewR-454B bubble
-20°F26.226.810.222.724.7
-15°F31.031.713.227.129.4
-10°F36.337.116.532.034.5
-5°F42.042.920.137.240.0
0°F48.249.324.042.945.9
5°F54.956.128.349.152.4
10°F62.263.532.855.759.3
15°F70.071.437.862.966.8
20°F78.480.043.170.674.8
25°F87.489.248.878.983.5
30°F97.099.155.087.892.7
35°F107.3109.761.597.3102.6
40°F118.4121.068.6107.5113.2
45°F130.1133.076.1118.3124.5
50°F142.6145.884.1129.9136.4
55°F156.0159.592.6142.2149.2
60°F170.1174.0101.6155.3162.7
65°F185.1189.5111.2169.2177.1
70°F201.1205.8121.4183.9192.3
75°F217.9223.2132.2199.5208.4
80°F235.7241.5143.6216.0225.4
85°F254.6260.9155.7233.5243.4
90°F274.5281.3168.4251.9262.3
95°F295.4302.9181.8271.4282.3
100°F317.6325.7195.9291.9303.3
105°F340.8349.6210.8313.5325.4
110°F365.4374.9226.4336.3348.6
115°F391.2401.4242.8360.3373.0
120°F418.3429.3260.0385.5398.6
125°F446.8458.7278.0412.1425.5
130°F476.8489.5296.9440.0453.6

The chart is printed from the same tables the calculator reads, so the two cannot disagree.

Data sources and check charts

Limits of this chart

  • The table runs from -40 to 140°F saturation. Outside it the calculator refuses instead of guessing. Below 0 psig a gauge is in vacuum, and this chart has no entry for it.
  • R-22, R-410A and R-32 values agree with the Daikin chart within 0.5 psi across the range, and R-22 and R-410A agree with the Honeywell Genetron chart within the same 0.5 psi.
  • Published R-454B charts do not agree with each other. Honeywell and Chemours use different property models for the blend, and near condensing pressures their charts are about 2 psi apart. Our R-454B values are within 0.5 psi of the Daikin chart up to 100°F and within 1 psi up to 140°F. Against Honeywell and Chemours they are within 2.5 psi, except the Chemours bubble line at condensing temperatures, where the gap is up to 3.5 psi.
  • When you charge a system, the chart and the installation instructions from the equipment manufacturer come first. This page looks up a reading and does not overrule them.
  • The altitude correction uses the standard atmosphere. Weather moves the local barometer too, and a high or low pressure system shifts the gauge zero by a few tenths of a psi.
  • The chart gives saturation only. A line temperature above or below saturation is superheat or subcooling, which the superheat and subcooling calculator works out from your readings.
  • Non-condensables, a mixed or contaminated charge, or the wrong refrigerant in the system put the pressure off the chart for any temperature. A PT chart cannot tell you which of those you have.

Common PT chart mistakes

  1. Reading superheat off the R-454B liquid column. At 107.5 psig the R-454B dew point is 40°F and the bubble point is 2.7°F lower. Superheat read off the bubble line comes out that much too high, and a tech charging by superheat adds refrigerant the system does not need.
  2. An R-410A chart on an R-454B system. The two run at different pressures. An R-454B evaporator at a 40°F dew point reads 107.5 psig, which an R-410A chart calls 35.1°F. Check the data plate and set the digital manifold to the refrigerant that is actually in the system.
  3. Forgetting the elevation. In Denver a gauge reads about 2.6 psi higher than at sea level for the same refrigerant. On an R-410A evaporator at 40°F, a sea-level chart puts that reading about 1.2°F too warm.
  4. Mixing up psig and psia. Manifolds and field PT charts read psig. Engineering tables and some property software print psia, which is 14.7 psi higher at sea level. Mixing the two moves the saturation temperature by several degrees at evaporator pressures.
  5. Reading saturation off a system that is not running. With the compressor off, the pressure settles toward the saturation pressure of the coolest place liquid is sitting. It tells you the refrigerant is there and roughly what it is, not how the system is charged.

Questions about PT charts

What is the pressure of R-454B at 40°F?

About 107.5 psig on the dew point line and 113.2 psig on the bubble point line, at sea level. Use the dew point number for superheat on the suction side and the bubble point number for subcooling on the liquid side.

Why does R-454B have two pressures at the same temperature?

R-454B is a blend of R-32 and R-1234yf that boils over a range of temperatures, called glide. At 40°F the bubble point line sits 5.7 psi above the dew point line. R-410A is a blend too, but at 40°F its two lines are within half a psi of each other, so many charts print one column.

How does R-454B compare with R-410A on a PT chart?

R-454B runs lower. At 40°F R-410A is about 118.4 psig and R-454B about 107.5 psig on the dew point line. The two are not interchangeable, and a system is charged only with the refrigerant on its data plate.

What is the R-32 and R-22 pressure at 40°F?

About 121.0 psig for R-32 and 68.6 psig for R-22, at sea level. Both are single refrigerants, so there is one saturation line and no glide.

Do I need to correct a PT chart for altitude?

Yes, once you are well above sea level. Printed charts assume sea-level air pressure, while your manifold reads pressure relative to the thinner air around it, so at 5,280 ft the gauge shows about 2.6 psi more for the same refrigerant temperature. Enter the elevation. The calculator does the rest.

Why does another PT chart show a slightly different number?

Every chart is computed from a property model, and for R-454B the models disagree. Near condensing pressures the Honeywell and Chemours charts sit about 2 psi apart. This page uses CoolProp 8.0.0, checked against the Daikin, Honeywell and Chemours charts. On a charge, the equipment manufacturer's chart wins.

Can a PT chart tell me if the system is charged right?

Not by itself. Saturation is only half of the check. Superheat compares the suction line temperature with the dew point, and subcooling compares the liquid line temperature with the bubble point. The superheat and subcooling calculator on this site does that math from your gauge and clamp readings.

Can the BuildSolver chat look up refrigerant pressures?

No. The chat has no PT chart tool, so use this page for saturation lookups. The chat runs whole-house Manual J loads, design conditions by ZIP code, dew point and psychrometrics.