Outlets per circuit calculator
A 20 A, 120 V circuit carries 2,400 VA. At 180 VA per receptacle that is 13 receptacles, and on a 15 A circuit 10; with the conservative 80 percent rule they are 10 and 8. Lighting is counted at 125 percent of its VA. This page works that arithmetic and shows the spare capacity. It is an estimate: the NEC does not set a number of outlets per circuit, and in a dwelling the receptacles are counted in the general lighting load, not one by one. For the wire, see the wire size calculator; for the breaker, the standard breaker and fuse size calculator.
- Choose the breaker rating, 15 A or 20 A, and the circuit voltage. A house circuit for ordinary receptacles is 120 V.
- General-use receptacles are counted at 180 VA each. For lighting, enter the VA of one fixture; it is counted at 125 percent as a continuous load. Add any continuous load already on the circuit.
- The result shows the maximum number of outlets, the load and current at that number, the spare VA, and for receptacles both the 100 percent and the 80 percent count.
Example result for the default inputs
20 A circuit at 120 V, general-use receptacles at 180 VA each.
Maximum receptacles
13
Load at that count
2,340 VA
Current at that count
19.5 A
Spare capacity
60 VA
| Circuit capacity | 20 A x 120 V = 2,400 VA |
|---|---|
| One receptacle | 180 VA per yoke (220.14(I)), taken as a noncontinuous load at 100 percent of the circuit |
| Count | 2,400 VA / 180 VA = 13.3, rounded down to 13 |
| Both bases | 13 receptacles at 100 percent of the circuit (not continuous), 10 at 80 percent (continuous basis, the contractor's rule). |
| Dwellings | The 180 VA figure is the nondwelling rule, 220.14(I). In a dwelling unit the NEC does not set a number of receptacles per circuit; their load is counted in the general lighting load (220.14(J) and 220.12 in the 2011 to 2017 editions; the section numbers moved in later editions). Read the count above as an estimate for sizing a circuit, not as a code limit. |
| Check | 13 x 180 VA = 2,340 VA, at most 2,400 VA. |
- A count of receptacles is an estimate. The NEC counts 180 VA per yoke in a nondwelling load calculation, and Holt reads that as 13 on a 20 A circuit; the authority having jurisdiction decides. In a dwelling the NEC sets no number per circuit. Plug-in loads of known size, such as a refrigerator or a space heater, are counted at their own rating, not 180 VA.
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the count is worked
A circuit carries its breaker rating in volt-amperes: amps times volts. A receptacle outlet is counted at a fixed 180 VA in a nondwelling load calculation, and a load that runs three hours or more is counted at 125 percent, which is the same as using 80 percent of the circuit. Divide what the circuit can carry by what one outlet counts for, round down, and that is the number of outlets. It is a sizing estimate: in a nondwelling load calculation the 180 VA figure is the Code value and the authority having jurisdiction decides how it is applied to a circuit, and in a dwelling the NEC sets no number of receptacles per circuit.
- Circuit capacity
VA = breaker amps x volts20 A x 120 V is 2,400 VA; 15 A x 120 V is 1,800 VA.- One receptacle
180 VA per yoke220.14(I), nondwelling. A single, a duplex and a triplex on one yoke each count as 180 VA. At 120 V that is 1.5 A.- Receptacles, not continuous
N = floor(capacity / 180 VA)2,400 / 180 = 13.3, so 13 on 20 A (Holt, EC&M). 1,800 / 180 = 10 on 15 A.- Continuous load, 125 percent
OCPD >= noncontinuous + 1.25 x continuous210.20(A) and 210.19(A)(1). The same as 80 percent of the rating: 16 A on a 20 A circuit, 1,920 VA at 120 V.- Receptacles, 80 percent basis
N = floor(capacity / (180 VA x 1.25))2,400 / 225 = 10.7, so 10 on 20 A, and 8 on 15 A (1,440 VA / 180).- Lighting fixtures
N = floor((capacity - 1.25 x known load) / (1.25 x fixture VA))2,400 VA / (1.25 x 100 VA) = 19.2, so 19 fixtures; 25 VA is left.- Receptacles beside a known continuous load
budget = capacity - 1.25 x known load960 VA x 1.25 = 1,200 VA leaves 1,200 VA, which is 6 receptacles at 180 VA.
Eight circuits through the same formulas
The first four rows are receptacles on a 15 A and a 20 A circuit, first as a noncontinuous load at 180 VA, 13 on 20 A in the Holt example, then on the 80 percent basis. Two rows are 100 VA lighting fixtures. One row has 960 VA of continuous load already on the circuit, and the last is a 277 V lighting circuit.
| Circuit | Worked as | Capacity, VA | Outlets | Load, VA | Load, A | Spare, VA |
|---|---|---|---|---|---|---|
| 20 A, receptacles, not continuous | 2,400 VA / 180 VA | 2,400 | 13 | 2,340 | 19.5 | 60 |
| 15 A, receptacles, not continuous | 1,800 VA / 180 VA | 1,800 | 10 | 1,800 | 15 | 0 |
| 20 A, receptacles, 80 percent | 2,400 VA / 225 VA | 2,400 | 10 | 1,800 | 15 | 150 |
| 15 A, receptacles, 80 percent | 1,800 VA / 225 VA | 1,800 | 8 | 1,440 | 12 | 0 |
| 20 A, 100 VA fixtures | 2,400 VA / 125 VA | 2,400 | 19 | 1,900 | 15.8 | 25 |
| 15 A, 100 VA fixtures | 1,800 VA / 125 VA | 1,800 | 14 | 1,400 | 11.7 | 50 |
| 20 A, receptacles beside 960 VA continuous | 960 VA x 1.25 taken off first | 2,400 | 6 | 2,040 | 17 | 120 |
| 20 A at 277 V, 100 VA fixtures | 5,540 VA / 125 VA | 5,540 | 44 | 4,400 | 15.9 | 40 |
The load column is the nameplate VA of the outlets plus any known load. The spare column is what is left of the breaker rating once everything is counted at its weighted value, 125 percent for lighting and for the 80 percent basis. A spare of zero means the count fits exactly.
Standards and data sources
- Mike Holt, EC&M Code Quandaries (March 2005): maximum receptacle outlets on a 20 A circuit, NEC 220.14(I) - 180 VA per receptacle outlet, 120 V x 20 A = 2,400 VA, divided by 180 VA is 13 receptacles. The worked example this page opens on, and the NEC Handbook note that general-purpose receptacles are not a continuous load.
- ExpertCE, How Many Outlets on a 15-Amp or 20-Amp Circuit: 180 VA per yoke, 100 percent and 80 percent counts - 10 on 15 A and 13 on 20 A at full capacity, 8 and 10 with the 80 percent factor, and the point that a fixed count has no basis in the NEC. The golden counts in the tests.
- IAEI Magazine, May 2012, Article 220 Branch-Circuit, Feeder, and Service Calculations (220.14) - 180 VA per receptacle yoke for banks and offices, and why a dwelling's receptacles are lumped into the general lighting load under 220.14(J) instead of counted one by one.
- EEPower, National Electrical Code Basics, Sizing and Protecting Branch-circuit Conductors (210.19(A)(1), 210.20(A)) - The noncontinuous load plus 125 percent of the continuous load, equal to 80 percent of the circuit rating, and the 20 A example with 16 A of continuous load that this page tests.
Limitations of this calculator
- The count is an estimate. The NEC counts 180 VA per receptacle yoke in a nondwelling load calculation, 220.14(I), and Holt reads that as 13 receptacles on a 20 A circuit. The NEC does not state a number of receptacles per circuit, and a fixed cap such as 10 or 13 is a reading of that figure. The authority having jurisdiction (AHJ) and the design govern the real number.
- In a dwelling unit there is no NEC limit on the number of general-use receptacles or lighting outlets on a circuit. Their load is counted in the general lighting load (220.12 and 220.14(J) in the 2011 to 2017 editions; the section numbers moved in later editions), and the Code requires a minimum number of circuits and an even spread of the load. The counts here are for planning, not a dwelling rule.
- The 13 and 10 counts treat general-purpose receptacles as a noncontinuous load, which is the reading of the NEC Handbook quoted by Holt. The 80 percent counts, 10 and 8, are the conservative contractor's rule, not a Code requirement for receptacles. Show both to the client when the use is unknown.
- A receptacle for a known appliance, such as a refrigerator, a space heater, a window air conditioner, a microwave or a workstation bank, is counted at the appliance's rating, not at 180 VA. A heater or a motor on a general circuit can use up the whole circuit alone.
- Lighting is counted at 125 percent of the fixture's VA, as a load that runs three hours or more. Enter the VA of the fixture with its driver or ballast, not the lamp watts alone. A lighting load that is not continuous may be counted at 100 percent; this page does not offer that.
- Only the breaker rating is checked. The wire size and its ampacity, the voltage drop over a long run, the box fill at each outlet, GFCI and AFCI protection, and the rules on which loads a 15 A or 20 A circuit may serve are separate checks.
- Counts are of identical outlets on one circuit. A mix of receptacles and fixtures, or several known loads, is not worked: enter the known continuous load, or count each kind on its own circuit.
- Feeder and service loads are not worked here. Receptacle and lighting demand factors for a panel or a service are a different calculation under Article 220.
Common mistakes when counting outlets
- Treating the count as a Code limit in a house. A dwelling's receptacles have no NEC count per circuit; they are counted in the general lighting load, not one by one. Telling a homeowner that a 20 A kitchen or bedroom circuit may have "no more than 13" is a rule of thumb. Use the count to plan, and let the circuit design and the AHJ decide.
- Counting a duplex as two receptacles. 220.14(I) counts the yoke: a single, a duplex and a triplex are each 180 VA. A duplex counted as 360 VA halves the answer to 6 on a 20 A circuit instead of 13. Count yokes.
- Mixing up the 100 percent count and the 80 percent count. 2,400 VA / 180 VA is 13, and 1,920 VA / 180 VA is 10. The first is the nondwelling load calculation with receptacles as a noncontinuous load; the second is the conservative rule. Quoting 13 and wiring a bank that runs all day is how a breaker ends up at its limit.
- Forgetting the 125 percent on lighting. A 100 VA fixture counts as 125 VA on the breaker. On 20 A that is 19 fixtures, not 24. A 15 A circuit takes 14. Count at 100 percent and the circuit sits at its full rating for hours.
- Ignoring a load that is already there. A 20 A circuit with 960 VA of continuous lighting has 1,200 VA taken off the top, leaving 1,200 VA, which is 6 receptacles at 180 VA, not 13. The EEPower example fills the circuit alone: 16 A of continuous load is 2,400 VA at 125 percent, all of the 2,400 VA, leaving 0 outlets.
- Counting an appliance outlet at 180 VA. The 180 VA figure stands for ordinary plug-in use. A 1,500 W space heater plugged into one of the 13 receptacles draws 1,500 VA at 120 V, which is 8.3 receptacles' worth. Dedicated loads get a dedicated circuit and their own size.
Common questions about outlets per circuit
How many outlets can you put on a 20 amp circuit?
In a nondwelling load calculation, 13: 120 V x 20 A is 2,400 VA, and at 180 VA per receptacle that is 13.3, rounded down. With the conservative 80 percent rule it is 10. In a house the NEC sets no number, so this is an estimate and not a limit.
How many outlets can you put on a 15 amp circuit?
10 at 100 percent of the circuit (1,800 VA / 180 VA) and 8 on the 80 percent basis (1,440 VA / 180 VA). The same caveat holds: there is no NEC count per circuit in a dwelling.
Is there a limit on outlets per circuit in a house?
Not in the NEC. In a dwelling unit the Code does not limit the number of receptacle and lighting outlets on a general-purpose branch circuit. It requires a minimum number of circuits and an even spread of the load, and the receptacles are counted in the general lighting load. Many installers still hold to about 10 on 15 A and 13 on 20 A as a working rule.
Where does 180 VA per receptacle come from?
NEC 220.14(I) counts a receptacle outlet in a nondwelling at not less than 180 VA per single or multiple receptacle on one yoke. A duplex is 180 VA, not 360. At 120 V that is 1.5 A each. It is an allowance for a load calculation, not a measured draw.
Do receptacles count as a continuous load at 80 percent?
The NEC Handbook note quoted by Holt says general-purpose receptacles are not considered a continuous load, so the first count is 13 on 20 A. A continuous load, one that runs three hours or more, is counted at 125 percent under 210.20(A), which is 80 percent of the circuit. Applying that to receptacles gives 10 on 20 A and 8 on 15 A. It is a cautious choice, not a requirement.
How many light fixtures can go on a 15 or 20 amp circuit?
Count each fixture at 125 percent of its VA. At 100 VA each, a 15 A, 120 V circuit takes 14 fixtures and a 20 A circuit 19. A 277 V, 20 A circuit takes 44. Use the nameplate VA of the fixture and its driver.
Does 240 V change the number of outlets?
The circuit carries more VA at a higher voltage, so more outlets fit by this arithmetic: amps times volts, divided by the VA of one outlet. A 20 A circuit at 240 V is 4,800 VA. The 180 VA figure is the same at any voltage. Check that the receptacles are rated for the circuit voltage.
Can I use this to size a wire or a breaker?
No. This counts outlets against a breaker rating you already chose. The wire size depends on the load current, the insulation temperature rating, the run length and the conditions of use, and the breaker comes from the load. Use the wire size calculator and the standard breaker size calculator for those.