An approximation. There is no direct conversion between SEER, EER, SEER2 and HSPF, and the AHRI certificate of the matched system decides. Use these numbers for a first comparison, not for a submittal or a rebate form.

Maintained by BuildSolver · Updated

Calculator · HVAC

SEER, EER and COP conversion calculator

SEER, SEER2, EER, EER2, HSPF, HSPF2 and COP rate the same equipment on different tests, so they do not convert exactly. The published approximations are close enough to compare. A 13 SEER split system comes to an EER of about 11.18, a SEER2 of 12.35 and a cooling COP of 3.28. A 7.7 HSPF heat pump is 6.55 HSPF2 and a seasonal COP of 2.26. To price what a rating means in running cost, use the SEER2 energy cost calculator.

  1. Choose SEER, SEER2, EER, EER2, HSPF, HSPF2 or a COP, and enter the number from the label, the spec sheet or the AHRI certificate.
  2. Ducted split, ducted packaged or ductless. It sets the SEER2, EER2 and HSPF2 factors. If you do not know, keep ducted split.
  3. The page shows the matching ratings and the COP. They are approximations. Use the AHRI certificate figure whenever one exists.

Approximate conversions between cooling ratings and between heating ratings. Cooling does not convert to heating. The AHRI certificate decides. No energy cost and no sizing.

The rating on the label or the AHRI certificate. Cooling ratings convert among themselves, and heating ratings among themselves.

Seasonal cooling rating on the pre-2023 test. 13 is the Building America benchmark.

Sets the SEER2, EER2 and HSPF2 factors. If you do not know, ducted split is the default RESNET uses.

Example result for the default inputs

13 SEER, ducted split system.

SEER

13.00

SEER2

12.35

EER

11.18

EER2

10.62

Calculation details
SEER and SEER2SEER2 = SEER x 0.95: 13.00 x 0.95 = 12.35. A SEER2 is read against a SEER2, not a SEER.
SEER and EEREER = -0.02 x SEER^2 + 1.12 x SEER = -0.02 x 13.00^2 + 1.12 x 13.00 = 11.18. A fit, not a measurement.
EER and EER2EER2 = EER x 0.95: 11.18 x 0.95 = 10.62.
Cooling COPCOP = EER / 3.412 = 11.18 / 3.412 = 3.28. On the EER2 basis 10.62 / 3.412 = 3.11.
Heating ratingsNot from a cooling rating. HSPF and HSPF2 come from a heating test; enter them with the HSPF, HSPF2 or heating COP choice.
FactorsThe ducted split system factors are SEER2/SEER 0.95, EER2/EER 0.95, HSPF2/HSPF 0.85, from AHRI through RESNET Addendum 71f.
  • An approximation. There is no direct conversion between these ratings: SEER is seasonal and EER is a single full-load point, and units with the same SEER differ in EER. The AHRI certificate of the matched outdoor and indoor units gives the real figures.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the ratings relate

These ratings measure efficiency on different tests, so there is no exact conversion; the page gives the published approximations. SEER and EER are cooling ratings, SEER2 and EER2 are the same ratings on the 2023 Appendix M1 test, and HSPF and HSPF2 are heating ratings. COP is the plain ratio of useful heat or cooling to the electricity used, and 1 W is 3.412 BTU/h. Whenever you have the AHRI certificate of the matched system, use that figure. Nothing here replaces it.

SEER to EER
EER = -0.02 x SEER^2 + 1.12 x SEERBuilding America's protocol gives this approximate conversion (Wassmer 2003). The benchmark 13 SEER gives an EER of 11.18, and 16 SEER gives 12.80. It rises to 15.68 at SEER 28 and turns down after that, so it is not used above 28.
EER to SEER
SEER = (1.12 - sqrt(1.2544 - 0.08 x EER)) / 0.04Solved the other way, the same fit gives SEER, on the branch where EER rises with SEER. An EER of 12 gives a SEER of 14.44. Two units with the same EER can have different SEERs.
SEER2 and EER2
SEER2 = SEER x 0.95, EER2 = EER x 0.95 (ducted); x 1.00 (ductless)RESNET's table, factors developed by AHRI. A 14 SEER2 split system is a 14.74 SEER; a 14 SEER one is 13.30 SEER2.
HSPF2
HSPF2 = HSPF x 0.85 (ducted split), x 0.84 (packaged), x 0.90 (ductless)The benchmark 7.7 HSPF on the split factor is 6.55 HSPF2. An HSPF of 9 is 7.65 HSPF2 on a split system and 7.56 on a packaged one.
Cooling COP
COP = EER / 3.4121 W = 3.412 BTU/h, and EER is BTU/h per watt. An EER of 11.18 is a COP of 3.28.
Seasonal heating COP
COP = HSPF / 3.412HSPF is BTU of heat per watt-hour. An HSPF of 8.5 is a seasonal COP of 2.49, and the benchmark 7.7 HSPF is 2.26.

Eight split systems from 13 to 24 SEER

Each row starts from a SEER and applies the Building America fit and the ducted split factors. The first row is the protocol's benchmark. The EER climbs more slowly than the SEER and flattens near 15.68 at SEER 28. These are estimates; a unit's own certificate can differ.

SEER converted to SEER2, EER, EER2 and cooling COP for a ducted split system
SystemSEERSEER2EEREER2COP
Building America benchmark13.0012.3511.1810.623.28
Mid-efficiency split system14.0013.3011.7611.173.45
15 SEER split system15.0014.2512.3011.693.60
16 SEER split system16.0015.2012.8012.163.75
18 SEER split system18.0017.1013.6813.004.01
20 SEER split system20.0019.0014.4013.684.22
22 SEER split system22.0020.9014.9614.214.38
24 SEER split system24.0022.8015.3614.594.50

COP is the EER divided by 3.412, so it is exact once the EER is known. The SEER2 and EER2 columns use 0.95; a ductless system uses 1.00, and a 20 SEER ductless unit is 20.00 SEER2 against 19.00 for a split system.

Standards and data sources

Limitations of this calculator

  • This page converts ratings as an approximation. There is no direct conversion between SEER, EER, SEER2 and HSPF: they are measured at different conditions, and two units with the same SEER can differ in EER. The AHRI certificate for the matched outdoor and indoor units gives the real figures, and it decides.
  • The SEER to EER relation is a fit from the Building America protocol, written for estimating EER when it is missing. It covers SEER 5 to 28; above 28 the curve turns down and the page gives no EER. It is not a rating and not a basis for a quote or a submittal.
  • The SEER2, EER2 and HSPF2 factors are AHRI's, adopted by RESNET for software conversion. DOE gives no conversion of its own. They are averages for a type of equipment, and a particular model can sit above or below them.
  • EER2 from a SEER stacks two approximations, the SEER to EER fit and the 0.95 factor. Treat it as a rough figure.
  • The cooling COP here is EER divided by 3.412, a full-load figure. The heating COP is HSPF divided by 3.412, a seasonal figure. A COP quoted at one outdoor temperature, such as 47 F or 17 F, is a different quantity and does not convert to HSPF this way.
  • Cooling ratings do not convert into heating ratings, and the reverse. A SEER says nothing about the HSPF of the same heat pump.
  • Equipment with ratings other than SEER, EER and HSPF, such as large commercial units rated by IEER or gas furnaces rated by AFUE, is not covered. The RESNET table also has factors for small-duct high-velocity and space-constrained systems that the page does not include.
  • Ratings describe the equipment at test conditions, not a house. They do not size a system, and they give no running cost. Use the sizing and energy cost calculators for that.

Common mistakes converting efficiency ratings

  1. Treating the SEER to EER conversion as exact. The fit gives an EER of 11.76 for 14 SEER and 12.80 for 16 SEER, but the Building America protocol calls it an approximate conversion for when the actual EER is not available. Two 16 SEER units can have different EERs. Read the EER off the AHRI certificate when you have it.
  2. Comparing a SEER2 with a SEER. A 14 SEER2 split system is not a 14 SEER system. It is about 14.74 on the old scale, and a 14 SEER unit is 13.30 SEER2. Compare SEER2 with SEER2 and SEER with SEER, and convert only when one side has no other rating.
  3. Pushing the SEER to EER fit past its vertex. The curve peaks at SEER 28 with an EER of 15.68. Run it at SEER 30 and it returns 15.60, lower than at 28, which is wrong for a more efficient unit. The page stops the fit at SEER 28.
  4. Reading an HSPF as a COP. HSPF is in BTU per watt-hour, and COP is a plain ratio, so the 3.412 sits between them. An HSPF of 8.5 is a seasonal COP of 2.49, not 8.5. In the other direction, an HSPF of 10 is a COP of 2.93.
  5. Using the split-system factor for a ductless unit. Ductless systems use 1.00 for SEER2/SEER and 0.90 for HSPF2/HSPF. A 20 SEER ductless unit is 20.00 SEER2; the ducted split factor of 0.95 would give 19.00. An HSPF of 10 is 9.00 HSPF2 ductless and 8.50 on a split system.
  6. Using a COP from a catalog as the seasonal figure. Heat pump data sheets quote COP at set outdoor temperatures, 47 F and 17 F being common. HSPF is a seasonal figure over a heating season, so HSPF divided by 3.412 is a seasonal COP and not the COP at 47 F. Do not swap one for the other.

Common questions about SEER, EER and COP

How do you convert SEER to EER?

The Building America House Simulation Protocols give EER = -0.02 x SEER^2 + 1.12 x SEER as an approximation for when the actual EER is not available. 13 SEER gives an EER of 11.18, 16 SEER gives 12.80 and 20 SEER gives 14.40. It is an estimate. The AHRI certificate of the system has the real EER, and it should win over this page whenever the two disagree.

How do you convert SEER to SEER2?

Multiply the SEER by 0.95 for a ducted split or packaged system, and by 1.00 for a ductless system. 14 SEER is 13.30 SEER2 on a ducted system. To go back, divide SEER2 by the factor: 14 SEER2 is 14.74 SEER. The factors were developed by AHRI and adopted by RESNET; DOE publishes none.

How do you convert HSPF to HSPF2?

Multiply the HSPF by 0.85 for a ducted split system, 0.84 for a ducted packaged system and 0.90 for a ductless system. An HSPF of 9 is 7.65 HSPF2 on a split system and 7.56 on a packaged one. An HSPF2 of 8 on a split system is 9.41 HSPF.

How do you convert EER to COP?

Divide the EER by 3.412. One watt is 3.412 BTU/h. An EER of 11.18 is a COP of 3.28, and in the other direction a COP of 3.5 is an EER of 11.94.

How do you convert HSPF to COP?

Divide the HSPF by 3.412. That is all. It gives the seasonal COP, the heat delivered over the season per unit of electricity. An HSPF of 8.5 is 2.49 and 10 is 2.93. It is not the COP at one outdoor temperature such as 47 F.

How do you convert EER to SEER?

Solve the same fit for SEER: SEER = (1.12 - sqrt(1.2544 - 0.08 x EER)) / 0.04. An EER of 12 gives a SEER of 14.44. It is rough. The same EER can belong to units with different SEERs, and it works only up to an EER of 15.68.

Is there an exact conversion between SEER, EER and COP?

Not really. Only EER to COP is exact, and that is a change of units by 3.412. SEER to EER, SEER to SEER2 and HSPF to HSPF2 are approximations, because the ratings come from different tests. For a real figure, look up the AHRI certificate for the matched outdoor and indoor units.

Why is the EER lower than the SEER?

Different tests. EER is the efficiency at one full-load, hot-outdoor condition. SEER is an average over a cooling season, which spends most hours at part load and in milder weather where the equipment runs more efficiently. So above a SEER of about 6 the fit returns a lower EER than the SEER entered.

Which equipment type should I pick if I do not know?

Ducted split, in most cases. RESNET's conversion rule defaults to the ducted split factors when the equipment type is not determined, and most central air systems in houses are split systems. Pick ductless for a mini-split. Pick packaged for a rooftop unit or any other package that holds the compressor, coil and fan in a single cabinet outdoors. Through-the-wall and small-duct units have their own factors in the RESNET table, which this page does not carry.

Used on the same job