Preliminary sizing from published tables. The NEC text is paid; the tables here were read in a free-view copy of the 2014 edition and in open commentary, and the adopted edition and the authority having jurisdiction govern. The rating plate and the installation instructions of the appliance come first. A licensed electrician designs and installs the circuit.

Maintained by BuildSolver · Updated

Calculator · Electrical

Electric range and dryer circuit calculator

A range is not sized from its nameplate. Table 220.55 counts one range of 12 kW or less as 8 kW, and adds 5 percent for each kW over 12, so a 14 kW range is 8.8 kW, 36.7 A at 240 V. A range of 8.75 kW or more still gets a branch circuit of at least 40 A, so the breaker is 40 A. A dryer is 5,000 VA or its nameplate. Several ranges or dryers on one feeder use the demand tables. This page works those steps and sizes the wire for the breaker. For a general conductor, see the wire size calculator; for a water heater circuit, the water heater breaker size calculator.

  1. Choose a range, one wall oven or cooktop on its own circuit, or a clothes dryer. A cooktop with up to two wall ovens on one circuit is entered as one range, with the ratings added.
  2. Read the rating plate in kW, or watts divided by 1,000. A range is worked from Table 220.55, a dryer plate under 5 kW counts as 5,000 VA. For several identical units on a feeder, enter how many.
  3. The result shows the calculated load, the current at 240 V, the breaker with the 40 A minimum for ranges of 8.75 kW or more, the wire for it, and the feeder demand for more than one unit.

One 240 V single-phase range, wall oven, cooktop or dryer, and the feeder demand of several identical ones. Preliminary sizing. No unequal ranges, no neutral or grounding conductor size, no voltage drop.

A range is Table 220.55, Column C. A cooktop with up to two wall ovens on one circuit in the same room is added up and treated as one range. A lone oven or cooktop is its nameplate.

From the rating plate, in kW or in watts divided by 1,000. A dryer plate under 5 kW is counted as 5,000 VA.

Leave at 1 for a single circuit. More than one gives the feeder demand, as in an apartment building.

Example result for the default inputs

One 14 kW electric range, 240 V single phase.

Calculated load

8.8 kW

Current

36.7 A

Breaker

40 A

Calculation details
Table 220.55, Column COne range of 12 kW or less: 8 kW of demand, whatever the nameplate (Note 4 lets one range use the table).
Note 1, over 12 kW14 kW is 2 kW over 12, which is 2 steps of 5 percent (a major fraction counts as a whole kW): 8 kW x 1.10 = 8.8 kW.
Current8.8 kW x 1,000 / 240 V = 36.7 A
Breaker40 A, the least standard size at or above 36.7 A (Table 240.6(A)).
Wire on 40 Acopper 8 AWG, aluminum 6 AWG on 60°C (140°F) terminals or 8 AWG on 75°C (167°F). At 86°F, two current-carrying conductors and 90°C (194°F) insulation. NM cable (Romex) is held to the 60°C column. The conductors must carry at least the breaker rating. The neutral and the equipment grounding conductor are not sized here.
  • Check the appliance's installation instructions and rating plate first. They name the breaker, the cord or cable and the receptacle, and they govern over a calculated minimum.
  • The tables here are the 2014 text, with Column C and Table 220.54 as other sources print them for the 2017 to 2023 editions. A newer edition, one commentary says, moves these rules to Article 120 and changes the dryer table. Use the edition your jurisdiction adopted.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the circuit is worked

A household range is not sized from its nameplate. Table 220.55 gives a maximum demand for the range in kW: 8 kW for one range up to 12 kW, and 5 percent more for each kW the rating is over 12 kW. That load divided by 240 V is the current, and the breaker is the least standard size at or above it, never under 40 A for a range of 8.75 kW or more. A lone wall oven or cooktop is its nameplate. A dryer is 5,000 VA or its nameplate, whichever is larger. Several identical ranges or dryers on one feeder use the Column C row for the count, or the dryer percentages of Table 220.54.

One range of 12 kW or less
load = Column C, 1 range = 8 kWTable 220.55 Note 4 lets one range use the table. A 9 kVA range: 8 kW x 1,000 / 240 V = 33.3 A, Holt's 33 A.
A range over 12 kW
load = 8 kW x (1 + 0.05 x steps)Note 1 adds 5 percent for each kW, or major fraction, over 12 kW. 14 kW is 2 kW over, so 8 x 1.10 = 8.8 kW and 36.7 A (Holt, 37 A). 15 kW is 3 steps: 9.2 kW. 18 kW is 6 steps: 10.4 kW.
Current
I = load kW x 1,000 / 240 VAt 240 V single phase. A 14 kW range is 36.7 A.
Breaker
least standard size at or above I, minimum 40 A for a range of 8.75 kW or moreTable 240.6(A) and 210.19(A)(3). A 12 kW range needs 33.3 A, which is a 35 A size, and the 40 A floor makes it 40 A. A 18 kW range needs 43.3 A, so 45 A.
One wall oven or cooktop
load = nameplate kWNote 4. 7.2 kW is 30.0 A, a 30 A breaker. A cooktop with not more than two wall ovens on one circuit in the same room is added together and treated as one range.
A clothes dryer
load = max(5,000 VA, nameplate)220.54. A 5 kW dryer is 5 kW, 20.8 A, a 25 A minimum breaker. A 5.6 kW nameplate is used as it stands: 23.3 A.
Several ranges on a feeder
demand = Column C for N ranges x (1 + 0.05 x steps)Column C reads 8, 11, 14, 17, 20 kW for 1 to 5 ranges, then 21 kW for 6, one kW more for each, and 15 kW + 1 kW per range for 26 to 30. Three 12 kW ranges: 14 kW, not 36 kW.
Several dryers on a feeder
demand = N x load x Table 220.54 percent1 to 4 dryers 100 percent, 5 dryers 85, 6 dryers 75, 11 dryers 47, then 47 minus 1 per dryer over 11. 15 dryers at 5 kW: 75 kW x 43 percent = 32.25 kW (ExpertCE).
Feeder neutral
neutral = 70 percent of the demand220.61(B)(1). The 15 dryers: 32.25 kW x 0.70 = 22.58 kW.

Eight appliances through the same formulas

The first two rows are Holt's examples, a 14 kW range at 8.8 kW and a 9 kW range at 8 kW. The next three show how the range load grows over 12 kW. One row is a wall oven at its nameplate, and two are dryers, one on the 5,000 VA floor and one on its own nameplate.

Calculated load, current and breaker for eight appliances at 240 V
ApplianceWorked asLoad, kWCurrent, ABreaker, A
14 kW range (Holt)8 kW x 1.108.836.740
9 kW range (Holt)Column C, 8 kW833.340
12 kW rangeColumn C, 8 kW833.340
15 kW range8 kW x 1.159.238.340
18 kW range8 kW x 1.3010.443.345
7.2 kW wall ovennameplate7.230.030
5 kW dryer5,000 VA520.825
5.6 kW dryernameplate5.623.325

The breaker is the least standard size at or above the current, and not under 40 A for a range of 8.75 kW or more. The 12 kW range shows the floor at work: 8 kW is 33.3 A, a 35 A size, and the breaker is 40 A.

Standards and data sources

Limitations of this calculator

  • Section numbers move between editions. The 40 A rule for ranges is quoted as 210.19(A)(3) in the 2014 to 2020 editions, and secondary sources place it at 210.19(C) in 2023. The NEC text is paid. The tables and notes here were read in a free-view copy of the 2014 edition and in Holt, ExpertCE and VoltageLab articles. Column C and the dryer percentages are the same in the 2017 to 2023 editions as those sources print them. One commentary says the 2026 edition moves the dryer and range rules to Article 120 and changes the dryer table. Use the edition your jurisdiction has adopted.
  • The rating plate and the installation instructions come first. They name the breaker, the cable or cord and the receptacle for the appliance, and they govern over a minimum from a calculation.
  • The 40 A floor is for a range of 8.75 kW or more, 210.19(A)(3), as Holt restates it; the section text is paid. A range under 8.75 kW takes the breaker its 8 kW load gives.
  • Only a range, a lone wall oven or cooktop, or a dryer at 240 V single phase. Not worked: Columns A and B (Note 3, appliances from 1.75 to 8.75 kW), ranges of unequal rating (Note 2), more than 30 ranges, three-phase feeders, 208 V and 120 V appliances, commercial kitchens and gas appliances.
  • The wire is the copper or aluminum conductor that carries the breaker rating, from Table 310.16 at 86°F with two current-carrying conductors and 90°C insulation, held to the 60°C column for NM cable. The neutral, the equipment grounding conductor and the voltage drop over a long run are separate checks.
  • A range's calculated load is Column C, not its nameplate, so a 12 kW range is 8 kW, 33.3 A. The breaker is still not under 40 A. The conductor must carry the breaker, not only the calculated load.
  • The feeder demand applies to a dwelling feeder or service calculation, such as an apartment building. The branch circuit of each appliance is sized on its own and does not use the feeder demand.
  • A licensed electrician designs and installs circuits under the local authority having jurisdiction.

Common mistakes sizing range and dryer circuits

  1. Sizing a range circuit from the nameplate. A 12 kW range at 240 V is 50.0 A on the nameplate, but Table 220.55 gives 8 kW, 33.3 A. The current alone is a 35 A size, and the 40 A floor makes the breaker 40 A. Neither the nameplate current nor 125 percent of it is the rule.
  2. Missing the increase over 12 kW. Column C stays at 8 kW up to 12 kW. A 14 kW range is 8.8 kW, 36.7 A; a 18 kW range is 10.4 kW, 43.3 A, so 45 A, not 40 A.
  3. Putting a 35 A breaker on a 9 kW range. 8 kW is 33.3 A, and the next standard size is 35 A. A range of 8.75 kW or more has a branch circuit of at least 40 A, 210.19(A)(3), so 40 A is the answer.
  4. Splitting a cooktop and ovens that share a circuit. A counter-mounted cooktop and not more than two wall ovens on one circuit in the same room are added up and treated as one range: a 12 kW cooktop and two 3 kW ovens are 18 kW, so 10.4 kW and 45 A. On separate circuits, each is its nameplate.
  5. Taking the connected load for several ranges. Three 12 kW ranges are 36 kW connected, but Column C for three is 14 kW. The feeder follows the table, not the sum. Each range's own branch circuit is still 40 A.
  6. Using the 5,000 VA floor when the dryer plate says more. A dryer is 5,000 VA or its nameplate, whichever is larger. A 5.6 kW plate is 5.6 kW and 23.3 A, not 5 kW. Read the plate before the table.

Common questions about range and dryer circuits

What size breaker does an electric range need?

For a 12 kW range, 40 A: Table 220.55 gives 8 kW, 33.3 A, and a range of 8.75 kW or more has a branch circuit of at least 40 A. A 14 kW range is 36.7 A, still 40 A, and 18 kW is 43.3 A, so 45 A. Follow the plate and the installation instructions, which govern.

How do you calculate the load of an electric range under NEC 220.55?

Use Column C of Table 220.55: 8 kW for one range up to 12 kW. For a range over 12 kW, add 5 percent for each kW, or major fraction of a kW, over 12. A 14 kW range is 8 x 1.10 = 8.8 kW, and at 240 V that is 36.7 A.

Why is a 12 kW range calculated at 8 kW?

Table 220.55 applies a demand to household cooking. One range of 12 kW or less is 8 kW in Column C, which is 33.3 A at 240 V. Note 4 lets the branch-circuit load for one range use the table. The breaker is still 40 A because of the 40 A minimum for ranges of 8.75 kW and up.

What is the wire size for a 40 amp or 50 amp range circuit?

It depends on the breaker and the insulation: the conductors must carry at least the breaker rating. The result shows copper and aluminum sizes at 60°C (140°F) and 75°C (167°F) terminals for the breaker it finds. NM cable uses the 60°C (140°F) column. The neutral and the grounding conductor are not sized here.

What size breaker does an electric dryer need?

The load is 5,000 VA or the nameplate, whichever is larger. At 240 V a 5 kW dryer is 20.8 A, so 25 A is the least standard breaker by the arithmetic. A cord-connected dryer plugs into a 30 A receptacle (NEMA 14-30, or the older 10-30), and dryer installation instructions commonly call for a 30 A circuit. The instructions name the breaker and the cord, and they govern.

What percentage is used for several dryers in an apartment building?

Table 220.54: 100 percent for 1 to 4 dryers, 85 for 5, 75 for 6, 65 for 7, 60 for 8, 55 for 9, 50 for 10, 47 for 11, then 47 percent minus 1 percent for each dryer over 11. Fifteen dryers at 5,000 VA are 75 kW x 43 percent = 32.25 kW.

Is a wall oven and cooktop one circuit or two?

Either. A counter-mounted cooktop and not more than two wall ovens on one circuit in the same room are added and treated as one range. One wall oven or one cooktop on its own circuit is its nameplate: a 7.2 kW oven is 30.0 A, a 30 A breaker.

Does the 125 percent continuous load rule apply to a range?

Cooking appliances are not treated as a continuous load in the calculation here. The range follows Table 220.55 and the 40 A minimum, and the dryer follows 220.54. The appliance instructions and the authority having jurisdiction decide any other reading.