Preliminary numbers for estimating and for checking a plan. The adopted NEC edition and the local authority having jurisdiction come first. A licensed electrician sizes and installs the grounding system.

Maintained by BuildSolver · Updated

Calculator · Electrical

Grounding electrode conductor size calculator

A 3/0 AWG copper service, the size that carries 200 A in the 75°C (167°F) column of Table 310.16, takes a grounding electrode conductor of 4 AWG copper or 2 AWG aluminum to a metal water pipe, from NEC Table 250.66. The table goes by the size of the service conductors, not by the breaker. A ground rod needs no more than 6 AWG copper and a concrete-encased (Ufer) electrode no more than 4 AWG copper. This page reads the table, adds up parallel conductors and applies those limits. The wire that grounds the equipment on a circuit is a different conductor, sized from the breaker. For that one, use the equipment grounding conductor size calculator.

  1. Pick the material and the size of one service-entrance conductor per phase, and the number of parallel conductors if the service is paralleled. For a separately derived system use its largest ungrounded conductor.
  2. Pick the electrode the conductor runs to, which is a metal water pipe or building steel, a ground rod, pipe or plate, a concrete-encased electrode, or a ground ring. For a ring, add the ring conductor.
  3. The result shows the Table 250.66 size in copper and in aluminum, the limit for the electrode you picked, and the conductor for your material, with the area and the row it was read from.

The grounding electrode conductor of an AC service, of a building fed by a feeder or of a separately derived system, from the service conductor size. Not the equipment grounding conductor. A licensed electrician installs it under the local AHJ.

The material of the phase conductors of the service. For a separately derived system, use its largest ungrounded conductor. Table 250.66 has one column for each.

The largest ungrounded conductor, one per phase. The table goes by this size, not by the breaker or the amps on the service.

1 for a service with one conductor per phase. For paralleled conductors enter how many, and the areas are added.

Aluminum is not used for a concrete-encased electrode, and 250.64(A) limits it near concrete, corrosion and the earth.

A water pipe or building steel takes the full table. The other three have a smaller limit, for the run to that electrode only.

Example result for the default inputs

3/0 AWG copper service-entrance or derived conductors per phase, GEC to a water pipe or building steel. NEC 250.66.

Table 250.66, copper

4 AWG

Table 250.66, aluminum

2 AWG

GEC to this electrode

4 AWG copper

Calculation details
Service conductors3/0 AWG copper per phase, 167,800 circular mils (Chapter 9, Table 8).
Table 250.66 row"2/0 or 3/0" in the copper column.
Table 250.66 gives4 AWG copper, or 2 AWG aluminum if aluminum or copper-clad aluminum.
Electrode limitNone. A metal underground water pipe or building steel electrode is sized from the table.
Grounding electrode conductor4 AWG copper, to a water pipe or building steel. This is the smallest the code requires; a larger conductor is allowed.
Range of the tableThe smallest is 8 AWG copper or 6 AWG aluminum. The largest is 3/0 AWG copper or 250 kcmil aluminum, however large the service conductors are.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the conductor size is worked

The grounding electrode conductor connects the grounded conductor and the grounding electrode system to earth. NEC Table 250.66 sizes it from the largest ungrounded service-entrance conductor, or from the added area of parallel conductors, and not from the breaker. Four electrode types follow the table in different ways: a metal water pipe or building steel takes the table size, and a ground rod, a concrete-encased electrode and a ground ring each cap the size for the run to that electrode.

Equivalent area
A = n x (circular mils of one conductor)One conductor's area comes from NEC Chapter 9, Table 8: 3/0 AWG is 167,800 circular mils and 4/0 AWG is 211,600. A kcmil size is 1,000 circular mils per kcmil. Parallel conductors are added and treated as one: four 250 kcmil aluminum conductors are 1,000 kcmil, and three 600 kcmil copper conductors are 1,800 kcmil.
Table 250.66 row
the first row whose upper limit is at or above A, in the column of the service conductor materialCopper column, with the copper and aluminum GEC for each row, 2 or smaller: 8 AWG copper or 6 AWG aluminum; 1 or 1/0: 6 AWG copper or 4 AWG aluminum; 2/0 or 3/0: 4 AWG copper or 2 AWG aluminum; Over 3/0 through 350: 2 AWG copper or 1/0 AWG aluminum; Over 350 through 600: 1/0 AWG copper or 3/0 AWG aluminum; Over 600 through 1100: 2/0 AWG copper or 4/0 AWG aluminum; Over 1100: 3/0 AWG copper or 250 kcmil aluminum. The aluminum or copper-clad aluminum column uses the same GEC sizes against these service sizes: 1/0 or smaller; 2/0 or 3/0; 4/0 or 250; Over 250 through 500; Over 500 through 900; Over 900 through 1750; Over 1750. "Through" includes the upper size, so a 600 kcmil copper service is in the row for 1/0 AWG and a 700 kcmil service is in the next row, 2/0 AWG.
Rod, pipe or plate
GEC = lesser of the table size and 6 AWG copper (4 AWG aluminum)NEC 250.66(A): where the conductor goes to rods, pipes or plates and no further to an electrode that needs more, it need not be larger than 6 AWG copper or 4 AWG aluminum. A 3/0 AWG copper service has a table size of 4 AWG copper, and the limit makes it 6 AWG copper. A 2 AWG copper service has a table size of 8 AWG, and the limit does not raise it.
Concrete-encased electrode
GEC = lesser of the table size and 4 AWG copperNEC 250.66(B): no larger than 4 AWG copper, with the same condition on other electrodes. IAEI adds that aluminum conductors are not permitted for this connection. A 1,800 kcmil copper service (3/0 AWG to a water pipe) takes 4 AWG copper to the concrete-encased electrode.
Ground ring
GEC = lesser of the table size and the ground ring conductorNEC 250.66(C): no larger than the ground ring conductor, which is bare copper of 2 AWG at the smallest (250.52(A)(4)). A ring of 2 AWG copper limits the 1,800 kcmil example to 2 AWG. A 500 kcmil copper service on a 4/0 AWG ring keeps the table size, 1/0 AWG copper, because a limit never raises a size.
Not the equipment grounding conductor
GEC: service conductor size, Table 250.66. EGC: breaker rating, Table 250.122The equipment grounding conductor of a circuit or feeder is sized from the rating of the overcurrent device ahead of it. IAEI's example is a 200 A device, which takes 6 AWG copper from Table 250.122. The grounding electrode conductor for a 3/0 AWG copper service is 4 AWG copper. The two tables answer different questions.

Eight services through the same table

The first five rows are the worked examples of an IAEI Magazine article by the chair of NEC code-making panel 7, the sixth is the 1,200 A service of a Mike Holt column and the seventh is the example of an NFPA fact sheet. This page gives the same sizes. Those sizes apply to a metal water pipe or building steel, where the full table applies.

Equivalent area and Table 250.66 conductor size in copper and aluminum for eight services
Service conductors per phaseEquivalent area, kcmilCopper GECAluminum GEC
3/0 AWG copper (IAEI example)167.84 AWG2 AWG
750 kcmil aluminum (IAEI example)7501/0 AWG3/0 AWG
4 x 250 kcmil aluminum in parallel (IAEI example)1,0002/0 AWG4/0 AWG
500 kcmil copper (IAEI example)5001/0 AWG3/0 AWG
2 AWG copper (IAEI example)66.48 AWG6 AWG
3 x 600 kcmil copper in parallel (Holt example)1,8003/0 AWG250 kcmil
2 x 500 kcmil copper in parallel (NFPA example)1,0002/0 AWG4/0 AWG
4/0 AWG aluminum211.64 AWG2 AWG

The same 1,800 kcmil copper service as the sixth row, on a daisy chain of electrodes: 3/0 AWG copper to the water pipe, 2 AWG copper to a 2 AWG ground ring, 4 AWG copper to the concrete-encased electrode and 6 AWG copper to the ground rods. IAEI notes that if that sequence is changed, the step-down is not available.

Standards and data sources

Limitations of this calculator

  • This page gives preliminary numbers for estimating, for checking a plan and for studying the table. A licensed electrician sizes and installs the grounding system under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
  • The NEC text was read as an NFPA fact sheet, IAEI Magazine, EC&M columns and two utility sheets print it, not in NFPA's own viewer. They cover the 2005, 2017 and 2020 editions and agree on the table. The 2023 text was not read directly, and this page names no change in it. Check the edition your AHJ adopted.
  • The page works the grounding electrode conductor of a service, of a building supplied by a feeder, or of a separately derived system, from the ungrounded conductor size. It does not size the equipment grounding conductor (Table 250.122), the grounded conductor, the main or system bonding jumper (Table 250.102(C)(1)), or a supply-side bonding jumper.
  • Table 250.66 has notes. Note 1 sizes from the largest sum of the areas when several sets of service-entrance conductors connect to one service drop or lateral, and the page does that only if you enter the largest sum as parallel conductors. Note 2 applies where there are no service-entrance conductors: the size is the equivalent of the largest service-entrance conductor the load requires, which you have to work out and enter.
  • The smaller sizes of 250.66(A), (B) and (C) are for the conductor that ends at that electrode. From the 2017 NEC on, they apply where no other electrode that needs a larger conductor is connected on beyond it. Earlier editions allowed them only for the part of the conductor that is the sole connection to the electrode. A run that goes to a ground rod first and then to a water pipe is sized from Table 250.66 all the way. The page sizes one run to one electrode type.
  • Under 250.64(A) of the 2020 NEC, as Mike Holt printed it in EC&M in 2021, bare or covered aluminum or copper-clad aluminum without an extruded polymeric covering is not installed where subject to corrosive conditions or in direct contact with concrete, and outside a building or enclosure it is not terminated within 18 in. of the earth. Older editions also kept it off masonry and the earth. IAEI (Lofland) adds that aluminum is not permitted for the connection to a concrete-encased electrode, so the page returns copper there. Whether a given aluminum conductor can be used on a ground ring is for the inspector.
  • Installation rules are not checked. For the 2020 NEC, Holt prints that a GEC of 6 AWG or larger may run exposed along the building surface if securely fastened and not exposed to physical damage, one exposed to physical damage goes in RMC, IMC, Schedule 80 PVC, RTRC-XW, EMT or cable armor, and one smaller than 6 AWG always does (250.64(B)). The rules for splices, taps, termination and bonding the raceway are in 250.64 and 250.70.
  • Electrode requirements are not checked. A ground ring is at least 20 ft of bare 2 AWG copper in contact with the earth, and a metal water pipe electrode needs a supplemental electrode (250.53(D)(2), as Holt printed it for 2005). The page does not size the electrodes, the soil resistance or the number of rods.
  • Multiple-enclosure services (250.64(D)), services over 1000 V and DC systems are not covered. The sizes are minimums. A larger grounding electrode conductor is allowed.

Common mistakes with grounding electrode conductors

  1. Sizing the grounding electrode conductor from the breaker. Table 250.66 goes by the size of the service conductors, not the breaker or the amps. A 3/0 AWG copper service carries 200 A in the 75°C (167°F) column of Table 310.16, and its grounding electrode conductor is 4 AWG copper. The equipment grounding conductor for a 200 A device is another table, 250.122, and gives 6 AWG copper (IAEI). Using one answer for the other undersizes or oversizes the wire.
  2. Using the 6 AWG ground rod allowance for a run that goes on to a water pipe. The 6 AWG copper limit of 250.66(A) holds for the conductor that ends at the rod. If the same conductor is run to the rod first and on to a metal water pipe, it is sized from Table 250.66 as if it went to the pipe. For the 600 kcmil x 3 copper service that is 3/0 AWG copper, not 6 AWG.
  3. Putting 6 AWG or 4 AWG on a water pipe or building steel. The step-down is only for rods, pipes, plates, concrete-encased electrodes and ground rings. A metal water pipe or building steel electrode takes the full table. A 500 kcmil copper service needs 1/0 AWG copper to a water pipe, and the 6 AWG copper that is enough for a rod is not.
  4. Using aluminum on a concrete-encased electrode or in the ground. Aluminum is not permitted for the connection to a concrete-encased electrode, so a 3/0 AWG copper service with an Ufer ground takes 4 AWG copper, never 2 AWG aluminum. Aluminum also has installation limits near concrete, corrosion and the earth under 250.64(A).
  5. Sizing from one conductor when the service is paralleled. Parallel conductors are added. A single 250 kcmil aluminum conductor is 250,000 circular mils and gives 4 AWG copper or 2 AWG aluminum. Four of them are 1,000 kcmil and give 2/0 AWG copper or 4/0 AWG aluminum. Three 600 kcmil copper conductors are 1,800 kcmil and give 3/0 AWG copper, not the 1/0 AWG of one.
  6. Reading the top of a row as the start of the next one. "Over 350 through 600" includes 600 kcmil. A 600 kcmil copper service takes 1/0 AWG copper, and a 700 kcmil copper service takes 2/0 AWG. An aluminum service of 250 kcmil is in the "4/0 or 250" row, 4 AWG copper, and 300 kcmil is already in the next row.

Common questions about grounding electrode conductors

What size grounding electrode conductor do I need for a 200 amp service?

It depends on the service conductors, not on the 200 A. A 3/0 AWG copper conductor carries 200 A in the 75°C (167°F) column of Table 310.16, and Table 250.66 gives 4 AWG copper or 2 AWG aluminum for it. If the conductor goes only to ground rods, 6 AWG copper is the most required, and for a concrete-encased electrode 4 AWG copper.

What size wire goes to a ground rod?

250.66(A) says no larger than 6 AWG copper or 4 AWG aluminum, where the conductor ends at rods, pipes or plates. The table can ask for less: a 2 AWG copper service needs only 8 AWG copper. A 3/0 AWG copper service needs 4 AWG at the water pipe, and 6 AWG copper to the rod. If the same run goes on to a water pipe, the table size applies all the way.

What size ground wire for a Ufer ground?

For a concrete-encased electrode, 250.66(B) allows no more than 4 AWG copper. Aluminum is not permitted for this connection. A 600 kcmil x 3 copper service has a 3/0 AWG copper conductor to the water pipe and 4 AWG copper to the concrete-encased electrode. Where a water pipe is the only electrode, a supplemental electrode is also required.

What size GEC for a 4/0 aluminum service?

4/0 AWG is 211,600 circular mils, which is in the "4/0 or 250" row of the aluminum column. Table 250.66 gives 4 AWG copper or 2 AWG aluminum. A 4/0 copper service is a larger row, "Over 3/0 through 350", and gives 2 AWG copper or 1/0 AWG aluminum.

Is the grounding electrode conductor the same as the equipment grounding conductor?

No. The grounding electrode conductor runs from the service to the grounding electrodes and is sized from the service conductors in Table 250.66. The equipment grounding conductor runs with the circuit and is sized from the breaker in Table 250.122. A 3/0 AWG copper service has a 4 AWG copper grounding electrode conductor, while a 200 A circuit takes a 6 AWG copper equipment grounding conductor.

What is the largest and the smallest grounding electrode conductor?

The smallest is 8 AWG copper or 6 AWG aluminum. The largest is 3/0 AWG copper or 250 kcmil aluminum, for service conductors over 1100 kcmil copper or over 1750 kcmil aluminum, however large they are. Rods, concrete-encased electrodes and ground rings can limit the size below that.

How do I size the GEC for parallel service conductors?

Add the areas of the parallel conductors and treat them as one. Four 250 kcmil aluminum conductors are 1,000 kcmil and take 2/0 AWG copper or 4/0 AWG aluminum. Three 600 kcmil copper conductors are 1,800 kcmil and take 3/0 AWG copper. Two 500 kcmil copper conductors are 1,000 kcmil and take 2/0 AWG copper.

Can I use an aluminum grounding electrode conductor?

Yes, with the aluminum column of Table 250.66, for example 2 AWG aluminum for a 3/0 AWG copper service. Under 250.64(A) of the 2020 NEC, bare or covered aluminum without an extruded polymeric covering cannot be in direct contact with concrete or where subject to corrosion, and outside a building it cannot be terminated within 18 in. of the earth. IAEI adds that it is not permitted for the connection to a concrete-encased electrode.

What if there are no service-entrance conductors?

Note 2 to Table 250.66 says the size is the equivalent size of the largest service-entrance conductor required for the load to be served. Work out the conductor the load needs, then enter that size in the calculator.

Does this replace an electrician?

No. This page is for estimating and for checking numbers on a plan or a quote. A licensed electrician installs the grounding system under a permit, and the local authority having jurisdiction inspects it.

Used on the same job