Maintained by BuildSolver · Updated
Calculator · HVAC circuits
AC wire size calculator
The wire for an air conditioner is sized from the minimum circuit ampacity (MCA) on its nameplate, not from the breaker. What trips people up is the terminal rating. A 22.5 A MCA needs 10 AWG copper on terminals that are not marked for 75°C (167°F), and 12 AWG when they are. This page picks the conductor from NEC Table 310.16, applies heat and crowding corrections if you enter them, and works the voltage drop for your run. Pair it with the AC breaker size calculator for the MCA and the largest breaker.
- Find the minimum circuit ampacity on the unit's nameplate, and check whether its terminals are marked for 75°C (167°F) conductors.
- Pick the conductor, the terminal and insulation ratings, the ambient temperature and the number of current-carrying conductors. Add the one-way length for the voltage drop.
- The result shows the smallest conductor, the ampacity left after corrections and the voltage drop at the MCA.
Example result for the default inputs
MCA 22.5 A, copper, 90°C (194°F) insulation, 60°C (140°F) terminals, single phase at 240 V.
Smallest conductor
10 AWG copper
Ampacity available
30 A
Voltage drop at the MCA
1.86 %
| Column of Table 310.16 | 60°C (140°F). Terminals count as 60°C (140°F) unless the equipment is listed and identified for higher (110.14(C)(1)(a)). |
|---|---|
| 10 AWG against the MCA | 30 A in the 60°C (140°F) column, MCA 22.5 A |
| Ambient correction, Table 310.15(B)(1)(1) | 1.00 (30°C (86°F) or lower, no correction) |
| More than three conductors, Table 310.15(C)(1) | 1.00 (3 or fewer current-carrying conductors) |
| Ampacity after the corrections | 40 A in the 90°C (194°F) column x 1.00 x 1.00 = 40 A |
| Why not 12 AWG | 20 A in the 60°C (140°F) column, under the 22.5 A MCA |
| Voltage drop | 2 x 12.9 x 22.5 A x 80 ft / 10,380 cmil = 4.47 V, 1.86 percent of 240 V |
| 3 percent guideline | Within it. The 3 percent figure is an Informational Note, not a requirement. |
| Breaker | The wire does not set the breaker. Table 240.4(G) sends air-conditioning circuit conductors to Article 440 for their overcurrent protection, so the nameplate MOCP is the limit, even where it is higher than this conductor's ampacity. |
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the conductor is chosen
The conductor has to carry the minimum circuit ampacity at the temperature its terminals allow, after any corrections for a hot location or a crowded raceway. The voltage drop is worked separately, because a conductor that carries the current can still be too thin for a long run.
- Which column of Table 310.16
ampacity column = the lower of the terminal rating and the insulation ratingNEC 110.14(C) holds the ampacity to the lowest temperature rating among the terminals, the conductor and any device it connects to. For circuits of 100 A or less, terminals count as 60°C (140°F) unless the equipment is listed and identified for higher. A 22.5 A MCA on 60°C (140°F) terminals needs 10 AWG copper (30 A). On 75°C (167°F) terminals 12 AWG copper (25 A) carries it.- Corrections for heat and crowding
ampacity = table value at the insulation column x ambient factor x conductor-count factor, and not above the terminal columnTable 310.15(B)(1)(1) for the ambient and Table 310.15(C)(1) for four or more current-carrying conductors. In the attic example a 33 A MCA at 120°F needs 8 AWG instead of 10 AWG.- Voltage drop
VD = 2 x K x I x L / CM, K = 12.9 (copper) or 21.2 (aluminum)K is the resistance constant at 75°C (167°F), I the current, L the one-way length and CM the circular mils from Chapter 9 Table 8. With 12 AWG at 22.5 A and 80 ft the drop is 7.11 V, 2.96 percent of 240 V.- The 3 percent figure
guideline, not a requirementAn Informational Note under NEC 210.19 suggests keeping the drop near 3 percent on a branch circuit, and near 5 percent for feeder and branch circuit together, for reasonable operation. An Informational Note is guidance. It is not a requirement of the code.
The same MCA under different conditions
Eight cases run through the same function the form uses, each over an 80 ft one-way run at 240 V unless the row says otherwise. The MCA values are illustrations, not typical values for any unit.
| Case | Conductor | Ampacity, A | Drop, % |
|---|---|---|---|
| 22.5 A MCA, 60°C (140°F) terminals (the default) | 10 AWG | 30 | 1.86 |
| 22.5 A MCA, 75°C (167°F) terminals | 12 AWG | 25 | 2.96 |
| 22.5 A MCA, 75°C (167°F) terminals, 81 ft | 12 AWG | 25 | 3.0003 |
| 27.5 A MCA, 75°C (167°F) terminals | 10 AWG | 35 | 2.28 |
| 33 A MCA, 75°C (167°F) terminals, attic at 120°F | 8 AWG | 45.1 | 1.72 |
| 22.5 A MCA, aluminum, 75°C (167°F) terminals | 10 AWG | 30 | 3.06 |
| 20.8 A MCA, compressor unit, 75°C (167°F) terminals | 12 AWG | 25 | 2.74 |
| 20.8 A, 4 kW heat strip on a 25 A breaker, 75°C (167°F) terminals | 10 AWG | 35 | 1.73 |
The 75°C (167°F) row at 80 ft sits at 2.96 percent, and one more foot makes it 3.0003 percent, just over the 3 percent figure in the Informational Note under NEC 210.19. That note is a recommendation and not a requirement, and the page shows the next size that brings the drop under it. The last two rows have the same 20.8 A. The compressor unit takes 12 AWG, while the heat strip takes 10 AWG, because a heater circuit is held to the small-conductor limits of NEC 240.4(D) and its 25 A breaker is over the 20 A limit for 12 AWG copper. In the attic row, heat takes the conductor from 10 AWG to 8 AWG even though the terminals are the same.
Standards and data sources
- NEC 2023, Table 310.16 and 310.15 - the ampacities of copper and aluminum conductors in the 60°C (140°F), 75°C (167°F) and 90°C (194°F) columns, the ambient temperature correction of Table 310.15(B)(1)(1) and the adjustment for more than three current-carrying conductors in Table 310.15(C)(1).
- NEC 2023, 110.14(C) and 240.4(G) - 110.14(C) for the terminal temperature limit and 240.4(G) with Article 440 for why an air-conditioning circuit's breaker is not limited by the conductor's ampacity.
- NEC 2023, Informational Note under 210.19, and Chapter 9 Table 8 - the 3 percent and 5 percent voltage drop recommendation, and the circular mils of each conductor size used in the drop formula.
Limitations of this calculator
- The nameplate comes first. The MCA and the MOCP on the unit govern the installation, and the installation instructions may set a minimum wire size on top. NEC 110.3(B) has listed equipment installed according to its listing and labeling.
- This page gives preliminary numbers for estimating and for checking a quote. A licensed electrician sizes, pulls and terminates the conductors under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
- No typical MCA is given for any tonnage or model, and none is looked up. You type in the number from the nameplate. The default example is a hand example, not a typical unit.
- The tables are the 2023 edition of the NEC. Your state or city may enforce another edition or amend it. Check the edition your AHJ uses.
- The 100 A test in 110.14(C)(1) looks at the circuit rating, which is the breaker. With a breaker above 100 A, or terminals marked for conductors larger than 1 AWG, the 75°C (167°F) rule of 110.14(C)(1)(b) applies, so check the terminal marking.
- Cable types carry their own temperature limit in their own article of the NEC. For nonmetallic-sheathed cable (NM-B) the page follows NEC 334.80: corrections start from the 90°C (194°F) value, and the result may not exceed the 60°C (140°F) value. That rule was read in the text of an earlier edition. NM cable is also not permitted in wet or damp locations (NEC 334.12, read in the 2017 text), so not outdoors and not in conduit outdoors. Other cable types, such as armored or metal-clad cable, have their own articles that this page does not apply.
- The heater circuit type applies the small-conductor breaker limits of NEC 240.4(D) and the next-higher-rating rule of 240.4(B). A heater with a single supply circuit or a kit with its own nameplate MCA and MOCP follows those numbers.
- The conductor count is yours to enter. The rules for which conductors count in a raceway, including neutrals and spares, are in 310.15(E) and (F) and are not worked here.
- Below 78°F the table allows a correction factor above 1.00 for cool air. This calculator holds the factor at 1.00 and takes no credit. Rooftop and sunlight conditions are not modeled, and an ambient above 185°F is outside the table.
- The voltage drop uses the MCA as the current, which is a little higher than the running current, and one-way length times two for the round trip. The constant K is for AC conductors up to 1/0, so at 2/0 and larger the reactance is left out and the real drop is somewhat higher.
- Single phase only. Three-phase circuits use a different drop formula, which the voltage drop calculator works. Sizes go up to 4/0, and a larger need is outside this page.
- The equipment grounding conductor, the disconnect, conduit fill and the breaker are not sized here. The breaker comes from the nameplate or the breaker calculator.
Common mistakes sizing AC wire
- Using the 75°C (167°F) column on unmarked terminals. Where the terminals are not listed and identified for 75°C (167°F), the 60°C (140°F) column applies, even with 90°C (194°F) wire. For a 22.5 A MCA that is the difference between 10 AWG and 12 AWG copper.
- Sizing the wire to the breaker. For an air conditioner the wire is sized from the MCA, not from the breaker. The nameplate MOCP is a ceiling for the breaker, and Article 440 lets it sit above the conductor's ampacity.
- Ignoring a hot attic or a crowded raceway. Heat and bundling lower the ampacity. A 33 A MCA on 75°C (167°F) terminals needs 10 AWG in a cool run and 8 AWG at 120°F.
- Checking ampacity and skipping the length. A conductor that carries the current can still drop too much voltage on a long run. At 22.5 A, 12 AWG copper drops 2.96 percent at 80 ft and 3.0003 percent at 81 ft, on either side of the 3 percent guideline.
- Calling 3 percent a code limit. The 3 percent and 5 percent figures are in an Informational Note. They are a recommendation for reasonable operation, not a requirement, and the equipment's own voltage tolerance is what protects the unit.
- Pulling aluminum to terminals that are not marked for it. NEC 110.14 requires terminals used to connect aluminum to be identified for it. Look for AL or CU/AL on the lugs before you land aluminum. Check first.
Common questions about AC wire sizing
What size wire do I need for an AC unit?
Size it from the minimum circuit ampacity (MCA) on the unit's nameplate. Take the smallest conductor whose ampacity in the right column of NEC Table 310.16 is not below the MCA. For a 22.5 A MCA on terminals that are not marked for 75°C (167°F), that is 10 AWG copper at 30 A. On 75°C (167°F) terminals 12 AWG copper at 25 A carries it. The nameplate and the installation instructions come first, and a licensed electrician makes the final choice.
What size wire for a mini split?
The same way as any air conditioner. Read the MCA on the outdoor unit's nameplate. Pick the conductor from Table 310.16 for your terminal rating. Then check the installation manual for any minimum wire size it sets. The length of the run to the outdoor unit can matter as much as the ampacity.
Why does the terminal temperature matter?
NEC 110.14(C) holds the ampacity to the lowest temperature rating among the terminals, the conductor and any device it connects to. For circuits of 100 A or less, terminals count as 60°C (140°F) unless the equipment is listed and identified for higher. Using 90°C (194°F) wire does not change that. It only helps when you derate for heat or crowding.
Can I use 12 AWG on a 30 A breaker for an AC unit?
It can be allowed for a compressor unit. NEC 240.4(G) sends air-conditioning circuit conductors to Article 440, so the breaker is limited by the nameplate MOCP and not by the usual small-conductor limits. The wire still has to carry the MCA. At a 22.5 A MCA, 12 AWG copper works only on 75°C (167°F) terminals (25 A), and this calculator shows 10 AWG on 60°C (140°F) terminals. Electric heat strips are different. They are not an Article 440 circuit, so 240.4(D) holds a breaker on 12 AWG copper to 20 A and on 10 AWG copper to 30 A. Confirm with the nameplate and your AHJ.
What wire size for electric heat strips?
Use the circuit type for heaters. The conductor ampacity is 125 percent of the heater load, and the breaker limits small conductors under NEC 240.4(D). A 4 kW heater at 240 V draws 16.7 A, so the circuit needs 20.8 A and a 25 A breaker. On 75°C (167°F) terminals, 12 AWG copper would carry that ampacity, but a 25 A breaker is over the 20 A limit for 12 AWG copper, so it takes 10 AWG copper, or 10 AWG aluminum. A 3 kW heater needs 15.6 A and a 20 A breaker, which 12 AWG copper or 10 AWG aluminum can carry. The heater's nameplate and instructions still come first.
How much voltage drop is acceptable?
The NEC does not set a limit here. An Informational Note under 210.19 suggests about 3 percent on a branch circuit and about 5 percent for feeder and branch circuit together. That note is a recommendation, not a requirement. With 12 AWG copper at 22.5 A and 240 V, 80 ft is 2.96 percent and 81 ft is 3.0003 percent.
Does distance change the wire size?
Not the ampacity. A conductor carries the same current at any length, so Table 310.16 gives the same answer. Distance changes the voltage drop, and a long run may call for a larger conductor to hold the drop to a level you are comfortable with.
Can I use aluminum wire for an air conditioner?
Where the terminals are marked for it. NEC 110.14 requires terminals used to connect aluminum to be identified for it, and aluminum needs a larger size for the same current. At a 22.5 A MCA on 75°C (167°F) terminals this calculator gives 10 AWG aluminum (30 A) against 12 AWG copper.
Does this replace an electrician?
No. This page is for estimating and for checking numbers on a quote. A licensed electrician sizes and installs the circuit under a permit, and the local authority having jurisdiction inspects it.
Used on the same job
Get the house load in chat
The chat does not size wire or circuits. It runs the free whole-house Manual J load, which tells you the heating and cooling the equipment has to cover before anyone looks at its nameplate. For the conductor, use this page and the nameplate.