Maintained by BuildSolver · Updated
Calculator · Electrical
Wire size calculator
The NEC sizes a conductor for the noncontinuous load plus 125 percent of the continuous load, read at the ampacity the terminals allow, and it must also carry the load itself after the heat and conductor-count corrections. On 75°C (167°F) terminals, a 45 A continuous load needs 56.25 A, so 6 AWG copper and a 60 A breaker. A 100 A continuous plus 100 A noncontinuous feeder needs 225 A and 4/0 AWG. This page covers 14 to 4/0 AWG for any load that is not a motor or an air conditioner; for an air conditioner use the AC wire size calculator, and for the ampacity of a wire you already have, the wire ampacity derating calculator.
- Put the load that runs three hours or more in the continuous field, and everything else in the noncontinuous field, in amps. Use 0 for either one that does not apply.
- Pick copper or aluminum, the insulation or NM-B cable, and the terminal rating marked on the breaker and the equipment. Enter the ambient temperature and the number of current-carrying conductors.
- Leave the breaker blank to use the smallest standard size. Enter the one-way length, phase and voltage to see the voltage drop.
- The result shows the smallest size, which of the three checks set it, why the next smaller size fails, the breaker and the voltage drop.
Example result for the default inputs
Continuous 45 A, copper, 90°C (194°F) insulation, 75°C (167°F) terminals, 86°F, 4 current-carrying conductors.
Smallest conductor
6 AWG copper
Smallest breaker
60 A
Voltage drop
not worked
| Load for the table value, before corrections | 0 A + 1.25 x 45 A = 56.25 A. A continuous load runs three hours or more (Article 100) and counts at 125 percent, the noncontinuous load at 100 percent (210.19(A)(1)(a), 215.2(A)(1)(a)). |
|---|---|
| Load for the corrected ampacity | 45 A, the load itself without the 125 percent (210.19(A)(1)(b)). |
| Column of Table 310.16 | 75°C (167°F). Terminals marked and listed for 75°C (167°F) conductors (110.14(C)(1)(a)(3)). |
| 6 AWG before corrections | 65 A in the 75°C (167°F) column, 56.25 A needed |
| Ambient correction, Table 310.15(B)(1)(1) | 1.00 (30°C (86°F) or lower, no correction) |
| More than three conductors, Table 310.15(C)(1) | 0.80 (4 to 6 current-carrying conductors) |
| Ampacity after the corrections | 75 A in the 90°C (194°F) column x 1.00 x 0.80 = 60 A, 45 A load |
| Why not 8 AWG | 50 A in the 75°C (167°F) column, under the 56.25 A needed before corrections; and 44 A after the corrections, under the 45 A load; and a 60 A breaker is above the next standard rating (45 A) over its 44 A ampacity (NEC 240.4(B)) |
| What set the size | 6 AWG is the smallest size that passes all three checks. These stop the next size down: the table value before corrections (210.19(A)(1)(a)); the ampacity after the corrections (210.19(A)(1)(b)); the breaker (240.4(D) and 240.4(B)). |
| Breaker assumed | 60 A, the smallest standard size at or above 56.25 A (210.20(A), Table 240.6(A)). Enter the real breaker if it is larger. The conductor's ampacity for the breaker check is 60 A, and the next standard rating over it is 60 A (240.4(B)). 240.4(D) puts no limit on 6 AWG copper; it limits only 14, 12 and 10 AWG. A 60 A breaker needs at least 8 AWG on that rule alone. |
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the size, the breaker and the drop are worked
A conductor has to pass three checks, and the smallest size in Table 310.16 that passes all of them is the answer. Check one reads the table before any correction, at the noncontinuous load plus 125 percent of the continuous load. Heat and conductor-count corrections come in check two, which compares with the load itself. Check three is the breaker. Voltage drop is separate and uses the load current.
- Load before corrections
I(a) = noncontinuous + 1.25 x continuousNEC 210.19(A)(1)(a) for a branch circuit and 215.2(A)(1)(a) for a feeder. Mike Holt's 2017 example is a 45 A continuous load: 56.25 A. His feeder example adds 100 A continuous and 100 A noncontinuous for 225.00 A. A continuous load runs three hours or more (Article 100).- Table value, first check
table ampacity in the lower of the insulation and terminal columns >= I(a)The correction factors are not applied here. With 75°C (167°F) terminals, 6 AWG copper is 65 A against 56.25 A, and 8 AWG is 50 A. NM-B cable stays in the 60°C (140°F) column (334.80). On 60°C (140°F) terminals the 60°C (140°F) column is used.- Corrected ampacity, second check
table ampacity in the insulation column x ambient factor x conductor-count factor >= noncontinuous + continuousTable 310.15(B)(1)(1) for the ambient and Table 310.15(C)(1) for more than three current-carrying conductors. The 90°C (194°F) value may be used here (110.14(C)(1)(a)(2)). 6 AWG THHN is 75 A x 0.80 = 60.00 A against the 45 A load. The 125 percent is not carried into this check.- Breaker, third check
breaker <= 240.4(D) limit of the size, and breaker <= next standard rating above the conductor's ampacityThe breaker is the smallest standard size at or above the first-check load (Table 240.6(A)), unless you enter one. 240.4(D) caps a breaker at 15 A on 14 AWG copper, 20 A on 12 AWG and 30 A on 10 AWG, and 15 A on 12 AWG aluminum and 25 A on 10 AWG. A 25 A breaker on a 4,500 W heater is over the 20 A limit of 12 AWG, so the answer is 10 AWG even on 75°C (167°F) terminals.- Voltage drop
VD = 2 x K x I x L / CM single phase, 1.732 x K x I x L / CM three phaseK is 12.9 for copper and 21.2 for aluminum, L is the one-way length and CM the circular mils of the size. I is the load, continuous plus noncontinuous. 10 AWG copper carrying 30 A for 200 ft at 240 V drops 14.91 V, 6.2 percent.
Continuous loads through the same formula
Each row is a continuous load with nothing else on the circuit, THHN in a dry location at 86°F with two current-carrying conductors. The breaker is the smallest standard size at or above 125 percent of the load. Copper on 60°C (140°F) terminals reads the 60°C (140°F) column, copper and aluminum on terminals listed for 75°C (167°F) the 75°C (167°F) column. At 15 A, copper is 12 AWG in both copper columns. On 60°C (140°F) terminals 14 AWG fails: 15 A in the 60°C (140°F) column, under the 18.75 A needed before corrections; and a 20 A breaker is over the 15 A limit of NEC 240.4(D) for 14 AWG copper. On 75°C (167°F) terminals it fails because a 20 A breaker is over the 15 A limit of NEC 240.4(D) for 14 AWG copper. A load the table cannot carry up to 4/0 AWG shows as over 4/0. Above a 100 A breaker the terminals count as 75°C (167°F) (110.14(C)(1)(b)), so the 60°C (140°F) column shows n/a.
| Continuous load, A | 125 percent, A | Smallest breaker, A | Copper, 60°C (140°F), AWG | Copper, 75°C (167°F), AWG | Aluminum, 75°C (167°F), AWG |
|---|---|---|---|---|---|
| 15 | 18.75 | 20 | 12 | 12 | 10 |
| 20 | 25.00 | 25 | 10 | 10 | 10 |
| 24 | 30.00 | 30 | 10 | 10 | 8 |
| 30 | 37.50 | 40 | 8 | 8 | 8 |
| 40 | 50.00 | 50 | 6 | 8 | 6 |
| 48 | 60.00 | 60 | 4 | 6 | 4 |
| 60 | 75.00 | 80 | 3 | 4 | 3 |
| 80 | 100.00 | 100 | 1 | 3 | 1 |
| 100 | 125.00 | 125 | n/a | 1 | 2/0 |
| 120 | 150.00 | 150 | n/a | 1/0 | 3/0 |
| 160 | 200.00 | 200 | n/a | 3/0 | over 4/0 |
| 200 | 250.00 | 250 | n/a | over 4/0 | over 4/0 |
Mike Holt's three published examples are checked against this code: 45 A continuous with four conductors gives 6 AWG (8 AWG fails both checks), 100 A continuous plus 100 A noncontinuous gives 4/0 AWG, and 200 A continuous needs 250 kcmil, which the page refuses. His 4,500 W appliance gives 10 AWG.
Standards and data sources
- NEC 2023, 210.19(A)(1), 215.2(A)(1), 210.20(A), 110.14(C), 240.4(B), 240.4(D), 334.80, Table 310.16, Table 310.15(B)(1)(1), Table 310.15(C)(1) and Table 240.6(A) - the branch-circuit and feeder conductor rules, the temperature columns, the breaker limits and the standard ratings. The NEC text was not read in NFPA's viewer. It was read as Mike Holt prints it in EC&M (2017 edition, with the table renumbered to 2023) and as third-party copies print it.
- Mike Holt, EC&M Code Q&A, Sizing Branch-Circuit Conductors (Feb 2, 2017) - the two conductor checks, 125 percent of the continuous load at the terminal ampacity and the maximum load after corrections, and the worked example this page opens on: 45 A continuous, four conductors, 75°C (167°F) terminals, 6 AWG.
- Mike Holt, EC&M, Conductor Sizing, Part 2 of 2 (Jun 18, 2019), and Code Q&A, Sizing Circuit Conductors for Individual Appliances (Oct 15, 2020) - the feeder rule in 215.2(A)(1)(a), the 100 A continuous plus 100 A noncontinuous example that gives 4/0 AWG, the 200 A continuous example that gives 250 kcmil, the 90°C (194°F) ampacity for corrections, and the 4,500 W, 240 V appliance at 18.75 A, 125 percent, 23.44 A and 10 AWG. The appliance article is at https://www.ecmweb.com/national-electrical-code/qa/article/21144798/code-qa-sizing-circuit-conductors-for-individual-appliances
- Ascent / IEWC, Product Specification No. 10521 rev 01 (May 16, 2025), THHN / THWN-2 building wire - where each marking may be used: THHN is a dry-location wire to 90°C (194°F), THWN-2 is wet or dry to 90°C (194°F), and THWN is wet to 75°C (167°F) or dry to 90°C (194°F). One wire is marked THHN in all sizes, also THWN-2 from 8 AWG up and THWN in 14, 12 and 10 AWG.
- HELUKABEL, Allowable Ampacity Tables, NFPA 70: NEC - 2023, and the Cerrowire ampacity chart - the ampacities of copper and aluminum conductors in the 60°C (140°F), 75°C (167°F) and 90°C (194°F) columns, the ambient correction and the conductor-count adjustment. Copper columns were cross-checked against Cerrowire.
- Thomas A. Domitrovich, IAEI Magazine, 100% vs 80%: Choosing the right OCPD solution (2016, 2014 NEC) - the text of 210.20(A) as printed there: the breaker is not less than the noncontinuous load plus 125 percent of the continuous load, unless the assembly is listed for operation at 100 percent of its rating. The voltage drop rows use Mike Holt's K method, as on the voltage drop calculator.
Limitations of this calculator
- This page gives preliminary numbers for estimating and for checking a quote. A licensed electrician sizes and installs the circuit under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
- Sizes run from 14 to 4/0 AWG. A load that needs more is refused, with the reason. Kcmil sizes, parallel conductors and busway are not on this page.
- Not for service conductors. The 83 percent allowance for a dwelling service or feeder in 310.12 is not applied, and the load calculation of Article 220 is a separate step.
- Not for motors or air-conditioning equipment. A motor circuit is sized from the full-load current in the tables of Article 430 (430.22 and Tables 430.248 and 430.250), not from a measured load. An air conditioner, heat pump or mini split is sized from its minimum circuit ampacity under Article 440; use the AC wire size calculator.
- The conductor count is yours to enter. Which conductors count, including a neutral on a nonlinear load, is in 310.15(E) and is not worked here. The rooftop temperature adder of 310.15(B)(2) is not worked; the wire ampacity derating calculator covers the corrections in more detail.
- The insulation choice follows the location. The Ascent specification sheet rates THHN to 90°C (194°F) in dry locations only and THWN to 75°C (167°F) in wet ones, so conduit outdoors, which counts as a wet location, takes the 75°C (167°F) choice unless the wire is marked THWN-2 or XHHW-2. Check the marking printed on the wire.
- The terminal column is your choice. For circuits of 100 A or less, or equipment marked for 14 to 1 AWG, the terminals count as 60°C (140°F) unless the equipment is listed and marked for 75°C (167°F) (110.14(C)). Above that, read the marking on the breaker, the panel and the load.
- The breaker rule is the 240.4(D) limit on small conductors and the next-standard-rating rule of 240.4(B). Where 240.4(E) or 240.4(G) says otherwise, the rule differs. Where the result leans on 240.4(B), the page shows the breaker and the size without it, for a multioutlet circuit to cord-and-plug loads, which 240.4(B) does not cover. Equipment listed for continuous operation at 100 percent of its rating and fuses are not modeled; the listing and the AHJ decide.
- The NEC text was read as Mike Holt prints it in EC&M (2017 edition), with the table renumbered to Table 310.16 of the 2023 edition, and as third-party copies print it, not in NFPA's own viewer. Section numbers moved between editions, and a later edition may number them again. Check the edition and the local amendments your AHJ uses.
- The voltage drop uses the load current and one-way length times two (single phase) for the round trip. The constant K is for AC conductors up to 1/0, so at 2/0 and larger the reactance is left out and the real drop is somewhat higher. The 3 percent figure is an Informational Note, not a requirement.
Common mistakes when sizing wire
- Stopping after the 125 percent figure. A 45 A continuous load on 75°C (167°F) terminals needs 56.25 A before corrections, and 8 AWG gives only 50 A. It also has to carry the load after the corrections: 8 AWG THHN is 55 A x 0.80 = 44.00 A, under 45 A, with four conductors. Both checks send it to 6 AWG.
- Running the 125 percent through the correction factors. The corrected ampacity is compared with the load, not with the 125 percent figure. A 24 A continuous load in a raceway with 7 conductors needs 30.00 A before corrections, and 10 AWG THHN is 40 A x 0.70 = 28.00 A after, which is above the 24 A load. The AC wire size calculator applies the corrections to a minimum circuit ampacity and gives 8 AWG for the same 30.00 A.
- Calling a load continuous, or not. A continuous load runs three hours or more. A 40 A noncontinuous load on 60°C (140°F) terminals takes 8 AWG copper. The same 40 A as a continuous load is 50.00 A and takes 6 AWG. Check how long the load really runs.
- Using the 75°C column on terminals that count as 60°C. A 50 A noncontinuous load takes 8 AWG copper in the 75°C (167°F) column and 6 AWG in the 60°C (140°F) column. The smaller size is only right where the breaker and the equipment are listed and marked for 75°C (167°F). Circuits of 100 A or less default to 60°C (140°F).
- Sizing for ampacity and forgetting the breaker. A 4,500 W heater at 240 V is 18.75 A, 23.44 A at 125 percent, and a 25 A breaker. 12 AWG copper carries 25 A in the 75°C (167°F) column, but 240.4(D) holds a breaker on 12 AWG to 20 A, so the answer is 10 AWG. On 60°C (140°F) terminals it is 10 AWG anyway, as in Mike Holt's answer.
- Ignoring the length of the run. Ampacity does not change with length, the voltage drop does. A 30 A load on 10 AWG copper for 200 ft at 240 V drops 14.91 V, 6.2 percent, over the 3 percent in the Informational Note under 210.19. 6 AWG brings it to 2.5 percent. Enter the length to see it.
Common questions about wire size
What size wire for a 30 amp, 40 amp, 50 amp or 60 amp circuit?
For a noncontinuous load equal to the breaker, copper wire with THHN at 86°F and two conductors: 30 A takes 10 AWG, 40 A takes 8 AWG, 50 A takes 6 AWG and 60 A takes 4 AWG on 60°C (140°F) terminals. On terminals listed for 75°C (167°F), 30 A takes 10 AWG, 40 A 8 AWG, 50 A 8 AWG and 60 A 6 AWG. For a continuous load the breaker rating is 125 percent of the load, so a 40 A breaker carries 32 A of continuous load.
Do I size the wire at 125 percent?
Only the continuous part of the load. NEC 210.19(A)(1)(a) and 215.2(A)(1)(a) size the conductor at 125 percent of the continuous load plus 100 percent of the noncontinuous load, read at the terminal ampacity before any correction. After the heat and conductor-count corrections the conductor must also carry the load itself. Take a 45 A continuous load: it is 56.25 A for the first check and 45 A for the second.
What counts as a continuous load?
Under NEC Article 100, a load is continuous when its maximum current is expected to last three hours or more (paraphrased, not quoted). Heaters, EV chargers and store lighting are typical. Anything that cycles off sooner is noncontinuous. The page asks for the two separately and adds them as the NEC does.
Why 6 AWG and not 8 AWG for a 45 amp continuous load?
Mike Holt's 2017 example is a 45 A continuous load with four current-carrying conductors on 75°C (167°F) terminals. Before corrections the load calls for 56.25 A: 8 AWG is 50 A in the 75°C (167°F) column and fails, 6 AWG is 65 A. After corrections, 6 AWG THHN is 75 A x 0.80 = 60.00 A, above 45 A, and 8 AWG is 55 A x 0.80 = 44.00 A, under 45 A. That load takes a 60 A breaker.
What size wire for a feeder with 100 amps continuous and 100 amps noncontinuous?
4/0 AWG copper. 1.25 x 100 A + 100 A = 225.00 A, and 4/0 AWG is 230 A at 75°C (167°F); 3/0 AWG is only 200 A. That is Mike Holt's feeder example. A feeder of 200 A continuous is 250.00 A and needs 250 kcmil, so this page refuses it: This load needs a larger conductor than 4/0 (kcmil sizes are not on this page). 4/0 AWG copper gives 230 A in the 75°C (167°F) column against the 250 A the load calls for. Use a larger conductor, parallel conductors or an engineered design.
Can I use Romex (NM-B) for this?
Yes, indoors in a dry location, sized from the 60°C (140°F) column even though the conductors are rated 90°C (194°F) (334.80). A 24 A continuous load takes 10 AWG. The 90°C (194°F) rating can be used for the heat and conductor-count corrections, but the result cannot exceed the 60°C (140°F) value. A 48 A continuous load takes 4 AWG NM-B against 6 AWG THHN on 75°C (167°F) terminals. NM cable is not allowed in wet or damp locations (334.12, read in the 2017 text).
What size aluminum wire do I need?
Aluminum is lower in ampacity than copper, so it runs about one size up. A 40 A continuous load is 50.00 A and takes 6 AWG aluminum against 8 AWG copper on 75°C (167°F) terminals. Table 310.16 lists aluminum from 12 AWG, so there is no 14 AWG aluminum, and the terminals must be identified for aluminum (110.14).
How does the length of the run change the wire size?
Length does not change the ampacity check, it changes the voltage drop. A 40 A load on 8 AWG copper at 240 V drops 2.6 percent over 100 ft and 3.9 percent over 150 ft. The 3 percent in the Informational Note under 210.19 is a recommendation, not a requirement. At 150 ft 6 AWG brings it to 2.5 percent.
Can the breaker make the wire bigger?
Yes. A 24 A continuous load needs 30.00 A and a 30 A breaker, which 10 AWG copper can take. A 40 A breaker on the same load is over the 30 A limit of 240.4(D) for 10 AWG, and over the next standard rating above its ampacity, so the wire becomes 8 AWG. The breaker may not be larger than the next standard size above the conductor's ampacity (240.4(B)).
What about 12 AWG on a 25 amp breaker?
It is not allowed. 4,500 W at 240 V is 18.75 A, 23.44 A at 125 percent, and a 25 A breaker. 12 AWG copper has 25 A in the 75°C (167°F) column but 240.4(D) limits the breaker on 12 AWG copper to 20 A, so the answer is 10 AWG copper, the same as Mike Holt's answer for this appliance.
Does this replace an electrician?
No. This page is for estimating and for checking numbers on a quote. A licensed electrician sizes and installs the circuit under a permit, and the local authority having jurisdiction inspects it.