Maintained by BuildSolver · Updated
Calculator · Electrical
Baseboard heater breaker size calculator
A 1,500 W baseboard heater on 120 V draws 12.5 A, which looks fine on a 15 A breaker. The conductors are sized at 125 percent of the load, 15.6 A, so the breaker is 20 A. The same heater on 240 V takes 15 A. This page gives the breaker, the wire and the number of circuits for the heaters you have, or how many heaters fit on a breaker. A 20 A circuit at 240 V carries 3,840 W, which is 5 heaters of 750 W. For the wire in more detail, the AC wire size calculator adds terminal ratings and derating.
- Pick the supply voltage and the rated voltage on the nameplate, then the number of heaters and the watts of each.
- Get the breaker and the number of circuits for the heaters you have, or the number of heaters that fit on a breaker of a size you pick.
- The result shows the current, the conductor ampacity at 125 percent, the breaker, the circuits by breaker size and the wire for a circuit at its limit.
Example result for the default inputs
5 x 750 W = 3,750 W at 240 V. Single phase, heater rated 240 V. NEC Article 424.
Total heater load
3,750 W
Current
15.6 A
Breaker
20 A
| Load | 5 x 750 W = 3,750 W at 240 V |
|---|---|
| Current | 3,750 W / 240 V = 15.63 A |
| Conductor ampacity, 424.4(B) | 1.25 x 15.63 A = 19.53 A |
| Breaker | The smallest standard size at or above 19.53 A is 20 A (Table 240.6(A)). A heater runs for hours, a continuous load, so NEC 210.20(A) rates the breaker at no less than 125 percent of it. Check the heater's instructions too: a thermostat rating can hold the load lower. |
| Circuit rule, 424.4(A) | All 5 heaters on one 20 A circuit is within the 30 A limit for a circuit that feeds more than one heater (NEC 2017 424.3(A), 2020 424.4(A)). Check the text of your edition. |
| Circuits by breaker size | 15 A (up to 2,880 W): 2 circuits; 20 A (up to 3,840 W): 1 circuit; 25 A (up to 4,800 W): 1 circuit; 30 A (up to 5,760 W): 1 circuit. |
| Wire for this breaker | copper 12 AWG, aluminum 10 AWG. At 86°F with two current-carrying conductors and 90°C (194°F) insulation. Article 424 is not in Table 240.4(G), so 240.4(D) caps a breaker on small conductors: 15 A on 14 AWG copper, 20 A on 12 AWG and 30 A on 10 AWG. |
| Thermostat and relays | A line-voltage thermostat or relay carries the same current. Cadet's owner's guide limits the load to 80 percent of the breaker or the thermostat's amp rating, whichever is lower. Marley/Qmark lists line-voltage thermostats rated 22 A. |
| Heat output | 3,750 W x 3.412 = 12,795 BTU/h at 240 V |
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the breaker and the circuits are worked
A baseboard heater is a resistor, so its current follows from its watts and the voltage across it. The conductors are sized at 125 percent of that current, which is the same as loading the breaker to 80 percent, and the breaker is the next standard size up. Everything else on the page, from watts per circuit to heaters per circuit, comes from those two steps.
- Current
I = W x V / Vr^2For a heater on its rated voltage this is W / V. A 750 W heater at 240 V draws 3.13 A, and the five of the default example draw 15.63 A. Vr is the voltage on the nameplate and V the supply.- 240 V heater on 208 V
W208 = W240 x (208 / 240)^2 = 0.751 x W240The resistance of the element stays the same, so watts fall with the square of the voltage. A 1,500 W heater makes 1,126.7 W on 208 V, and the Marley/Qmark catalog prints 1,128 W. On 120 V it would make 25 percent, 375 W.- Conductor ampacity
A = 1.25 x INEC 424.4(B) sizes the branch-circuit conductors for fixed electric space heating at no less than 125 percent of the load. The default example needs 19.53 A of conductor.- Breaker
smallest standard size at or above 1.25 x I, not below 15 AA heater runs three hours or more, a continuous load by the NEC Article 100 definition, and NEC 2017 424.3(B) says so by name. NEC 210.20(A) rates the breaker on a continuous load at no less than 125 percent of it. Standard sizes are from NEC Table 240.6(A). The default example needs a 20 A breaker.- Watts per circuit
W max = breaker x V / 1.25At 240 V a 15, 20, 25 and 30 A circuit carries 2,880, 3,840, 4,800 and 5,760 W. At 120 V it carries half as much, and at 208 V 3,328 W on 20 A.- Heaters per circuit
n = whole number of (0.8 x breaker / I)Heaters cannot be split, so the count rounds down. 5 heaters of 750 W fit on 20 A at 240 V, 3 of 1,000 W and 2 of 1,500 W.- Circuits
circuit rating of 30 A or less when it feeds two or more heatersNEC 2017 424.3(A) and 2020 424.4(A) limit a circuit that feeds more than one heater to 30 A. Eight 1,000 W heaters at 240 V need 2 circuits of 30 A, or 3 of 20 A.
Eight jobs through the same formula
The first three rows are the heater lists in a Mike Holt forum thread, and the page gives the same circuits. The others show what 120 V, a 208 V supply or a bigger load does to the breaker.
| Heaters | Load, W | Current, A | Result |
|---|---|---|---|
| 5 x 750 W, 240 V (Holt forum example) | 3,750 | 15.63 | 20 A breaker |
| 2,000 W + 1,500 W, 240 V (Holt forum example) | 3,500 | 14.58 | 20 A breaker |
| 1,500 W + 500 W, 240 V (Holt forum example) | 2,000 | 8.33 | 15 A breaker |
| One 1,500 W heater, 120 V | 1,500 | 12.50 | 20 A breaker |
| 4 x 1,000 W, 240 V | 4,000 | 16.67 | 25 A breaker |
| 2 x 1,500 W, 240 V heaters on 208 V | 2,253.3 | 10.83 | 15 A breaker |
| 3 x 2,000 W, 240 V | 6,000 | 25.00 | 2 circuits, 30 A or less |
| 8 x 1,000 W, 240 V | 8,000 | 33.33 | 2 circuits, 30 A or less |
Watts set the circuit, not the number of heaters. On 20 A at 240 V, 5 heaters of 750 W fit, 3 of 1,000 W, 2 of 1,500 W and 1 of 2,000 W. Three 2,000 W heaters need 2 circuits, because one circuit would need 35 A and a circuit with more than one heater is held to 30 A.
Standards and data sources
- NEC 2023, Article 424 (424.4), Table 240.6(A), Table 310.16 and 240.4(D) - the 125 percent conductor rule of 424.4(B), the 125 percent breaker rule of 210.20(A) for a continuous load, the rule that one circuit may feed a heater of any rating it is rated for, the 30 A limit for a circuit that feeds two or more heaters in the 2017 and 2020 editions, the standard breaker sizes and the small-conductor limits. The 2023 wording of the 30 A sentence was not confirmed.
- Mike Holt forum threads on baseboard circuits, 2013 and 2016 - the 3,840 W limit of a 20 A circuit and 2,880 W of a 15 A circuit at 240 V, and the five 750 W heater example this page opens on. The same forum shows the 424.3(A) and 424.4(A) text as members pasted it.
- Cadet Electric Baseboard Heater Owner's Guide and King Electric, Sizing the Heater Circuit - the heater makers' limit of 80 percent of the breaker or the thermostat rating, whichever is lower, and King's table of heater current and breaker, for example 4,000 W at 240 V on a 25 A breaker.
- Marley/Qmark baseboard heater catalog, 2500 series - watts printed at 240 and 208 V, which the 208 V derating matches to within 0.2 percent, and the 22 A line-voltage thermostats.
Limitations of this calculator
- This page gives preliminary numbers for estimating and for checking a quote. A licensed electrician sizes and installs the circuit under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here is an approval of an installation.
- The heater's nameplate and installation instructions come first. They can set a smaller circuit, a particular wire, or a thermostat rating that is lower than the breaker allows, and listed equipment is installed according to its listing.
- The breaker is sized at 125 percent of the heater load because NEC 210.20(A) requires it for a continuous load. A heater is one by the Article 100 definition of three hours or more, and the 2017 edition (424.3(B)) says so by name; the later wording of that sentence was not confirmed. The exception is a breaker and panel listed for 100 percent operation, which residential panel breakers are not, so this page does not use it.
- A circuit that feeds two or more heaters is held to 30 A, as in the 2017 edition (424.3(A), a list of 15, 20, 25 or 30 A) and the 2020 edition (424.4(A), not over 30 A). The 2023 text of 424.4(A), as a member pasted it into a forum, shows only the sentence that lets an individual circuit feed any rating, so whether the 30 A sentence moved or was dropped was not confirmed. This page keeps 30 A, the more cautious reading. Check the edition your AHJ adopted.
- A 240 V heater on a 208 V supply is derated by the square of the voltage ratio. Real elements change resistance a little with temperature, so a maker's printed 208 V watts can differ by a fraction of a percent. A heater made for 208 V is better entered at 208 V with the nameplate watts.
- Wire sizes are for copper and aluminum at 86°F with two current-carrying conductors and 90°C (194°F) insulation, for a circuit loaded to its limit. Cable type, a hot attic, more conductors in the conduit and the length of the run change them. Use the AC wire size calculator for terminal ratings and corrections, and the voltage drop calculator for a long run.
- The page works single phase at 120, 208 and 240 V, up to two heater sizes, and heaters from 100 to 4,000 W each. Three phase, 277 V and 480 V commercial heaters, hydronic baseboard and cord-and-plug heaters are not covered.
- The page does not say how many watts a room needs, and it does not apply the demand factors that a service or feeder calculation may use. Size the heat from the room's load, and have the service checked by an electrician.
- A line-voltage thermostat or relay in the circuit has its own amp rating, and the lower of that and the breaker limit governs. Low-voltage controls and smart thermostats that switch a heater through a relay are not worked here.
- The tables are from the 2023 edition of the NEC where it was read. Your state or city may enforce another edition or amend it.
Common mistakes with baseboard heater circuits
- Sizing the breaker at the running current. A 1,500 W heater at 120 V draws 12.50 A, which looks fine on a 15 A breaker. At 125 percent it is 15.63 A, so the breaker is 20 A. The same heater at 240 V draws 6.25 A and takes a 15 A double-pole breaker.
- Counting watts at the wrong voltage. A 20 A circuit carries 3,840 W at 240 V and only 1,920 W at 120 V. A plan that fits 5 heaters of 750 W on a 240 V circuit fits 2 on a 120 V circuit of the same size.
- Counting heaters instead of watts. Three heaters to a circuit works for 750 W heaters and fails for 2,000 W ones. Three 2,000 W heaters draw 25.00 A at 240 V and would need 35 A, over the 30 A limit for a circuit with more than one heater. They need 2 circuits.
- Expecting full heat from a 240 V heater on 208 V. A 2,000 W, 240 V heater makes 1,502.2 W on a 208 V supply, about 75 percent. The current is lower too, but the room gets less heat. Size the heater count for the 208 V watts, or buy 208 V heaters.
- Raising the breaker to stop nuisance trips. A breaker that trips under a steady heater load may be carrying too much, since the limit is 80 percent of its rating. A 25 A breaker on 12 AWG copper is not allowed, because NEC 240.4(D) caps 12 AWG at 20 A. A 25 A circuit needs 10 AWG copper, a 20 A circuit 12 AWG and a 15 A circuit 14 AWG. Move a heater to another circuit, or size the circuit up from the start.
- Wiring a 240 V heater to a 120 V circuit. A 240 V element on 120 V gets half the voltage and makes a quarter of its watts: a 1,500 W heater gives 375 W. The room stays cold and the load looks small. Read the voltage on the nameplate before sizing anything.
Common questions about baseboard heater breakers
What size breaker do I need for a baseboard heater?
Divide the heater watts by the voltage for the current, multiply by 1.25, and take the next standard breaker size. A 1,500 W heater at 240 V draws 6.25 A, so 7.81 A and a 15 A double-pole breaker. At 120 V the same heater draws 12.50 A and needs a 20 A breaker. Four 1,000 W heaters at 240 V draw 16.67 A and need 25 A. The heater's nameplate comes first.
How many baseboard heaters can you put on a 20 amp circuit?
It depends on watts and voltage. At 240 V a 20 A circuit carries 3,840 W, which is 5 heaters of 750 W, 3 of 1,000 W, 2 of 1,500 W or 1 of 2,000 W. At 120 V it carries 1,920 W, so 1 heater of 1,500 W. The limit is 80 percent of the breaker, as the heater makers state it.
How many watts can a 15, 20 or 30 amp baseboard circuit carry?
On a 240 V circuit the most is 2,880 W on 15 A, 3,840 W on 20 A, 4,800 W on 25 A and 5,760 W on 30 A. For 120 V the figures are 1,440, 1,920, 2,400 and 2,880 W, and for 208 V they are 2,496, 3,328, 4,160 and 4,992 W. Each is the breaker times the voltage divided by 1.25.
Why does the breaker have to be bigger than the heater's current?
A heater can run for hours, three hours or more being the NEC's definition of a continuous load. NEC 210.20(A) rates the breaker at no less than 125 percent of a continuous load, and 424.4(B) sizes the conductors the same way. Loading the breaker to at most 80 percent is the same ratio, and heater makers put the rule that way: Cadet's owner's guide gives the limit as 80 percent of the breaker or the thermostat rating, whichever is lower.
Can a 240 volt baseboard heater run on 208 volts?
Yes, if the nameplate allows it, but it makes less heat. The watts fall with the square of the voltage, to 75 percent. A 1,500 W heater makes 1,126.7 W on 208 V, and the Marley/Qmark catalog prints 1,128 W for its 240/208 V model. Two of them draw 10.83 A on 208 V and need a 15 A breaker.
What is the largest circuit for several baseboard heaters?
30 A in the 2017 and 2020 NEC: a circuit that feeds two or more heaters is limited to that, and a single heater may have a circuit of any rating it needs. The 2023 text of that sentence was not confirmed for this page, which keeps the 30 A limit. Check the edition your AHJ adopted.
What wire size does a baseboard heater circuit need?
For a circuit loaded to its limit, copper 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 25 A and 10 AWG on 30 A, at 86°F with two current-carrying conductors. Aluminum is 12, 10, 10 and 8 AWG. NEC 240.4(D) is why 12 AWG copper stops at 20 A. Cable type and long runs change these.
Does each baseboard heater need its own circuit?
Not under the NEC section read for this page. It lets one circuit feed more than one heater, up to 30 A in the 2017 and 2020 editions. A heater's instructions or the local code can ask for more. Heaters on one circuit also share the circuit's 80 percent limit, so add their watts, not their count.
Does this replace an electrician?
No. This page is for estimating and for checking numbers on a quote. A licensed electrician sizes and installs the circuit under a permit, and the local authority having jurisdiction inspects it.