Calculator · Mixed air
Mixed air temperature calculator
Outdoor air and return air meet ahead of the coil, and the mixed air lands on a line between them. ASHRAE places it by the mass of dry air in each stream, and the CFM figures alone do not say where. For 4,238 CFM of outdoor air at 39.2 °F and 35.6 °F wet-bulb with 13,243 CFM of return air at 77 °F and 50 percent RH, the mix is 67.3 °F dry-bulb and 58.2 °F wet-bulb, 24.2 percent outdoor air by CFM. The plain CFM average of the two dry-bulbs says 67.8 °F, which is 0.5 °F high. The second form of this page works backward from OAT, RAT and MAT readings to the percent outdoor air, and it refuses readings that cannot give a sound answer. For the state of a single stream, use the psychrometric calculator. To compare a measured outdoor air percent with a ventilation requirement, use the ASHRAE 62.2 ventilation calculator.
- Pick the mix to get the mixed-air temperature of two streams, or the percent form to get the outdoor air share from three thermometer readings.
- For the mix, type the airflow and dry-bulb of the outdoor air and the return air, and add a relative humidity or wet-bulb for each to include moisture. For the percent form, type OAT, RAT and MAT.
- The result shows the mixed dry-bulb beside the plain CFM average, or the outdoor air percent with its possible error. A fog alert or a refusal means the readings or the streams need another look.
Example result for the default inputs
4,238 CFM outdoor air with 13,243 CFM return air, humidity included.
Mixed air dry-bulb
67.3 °F
Mixed air wet-bulb
58.2 °F
Outdoor air by CFM
24.2 %
| Outdoor air | 4,238 CFM at 39.2 °F dry-bulb, 35.6 °F wet-bulb, 70.8% RH |
|---|---|
| Return air | 13,243 CFM at 77 °F dry-bulb, 50% RH, 64.2 °F wet-bulb |
| Total of the two airflows | 17,481 CFM |
| Outdoor air by CFM | 24.2% |
| Outdoor air by mass of dry air | 25.8% |
| Dry air, outdoor stream | 20,109 lb/h |
| Dry air, return stream | 57,827 lb/h |
| Mixed dry-bulb from the mass and energy balance | 67.3 °F |
| Plain CFM average of the two dry-bulbs | 67.8 °F |
| Plain average minus the mixed dry-bulb | +0.5 °F |
| Mixed humidity ratio | 0.00823 lb water / lb dry air |
| Mixed enthalpy | 25.13 BTU/lb dry air |
| Mixed relative humidity | 58.0% |
| Mixed wet-bulb | 58.2 °F |
| Mixed dew point | 52.1 °F |
| Mixed airflow at the mixed conditions | 17,481 CFM |
- Each CFM figure is for its own stream, measured in that stream's air. The airflow of the mix comes out close to the sum of the two: at constant pressure, mixing changes the temperature of the air but hardly its volume.
- Humidity ratio and enthalpy follow the ASHRAE moist-air equations with the Magnus-Tetens saturation curve, which sits within about 0.5 °F of Hyland-Wexler in the HVAC range.
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the mixed air is calculated
Outdoor air and return air that meet in a mixing box leave as one stream, and the dry air, the water vapor and the energy all carry over. ASHRAE writes the balance by mass of dry air, so each CFM is first turned into pounds of dry air with the specific volume of its own stream. The mixed humidity ratio and enthalpy are the mass-weighted values, and the dry-bulb comes back out of the enthalpy equation. With no humidity readings the page weights each dry-bulb by the dry air from absolute temperature, and it shows the plain CFM average beside that. The second form works backward from three thermometer readings to the outdoor air percent.
- Dry air in each stream
m = 60 x CFM / v (lb of dry air per hour, v in ft3 per lb of dry air)The specific volume comes from the psychrometric engine, for that stream's own dry-bulb and humidity at the elevation entered. In the default case the 4,238 CFM of outdoor air has v = 12.65 and carries 20,109 lb/h of dry air. The 13,243 CFM of return air has v = 13.74 and carries 57,827 lb/h.- Mass and energy balance
W3 = (m1 W1 + m2 W2) / (m1 + m2) and h3 = (m1 h1 + m2 h2) / (m1 + m2)ASHRAE's three mixing equations are the enthalpy, dry air and moisture balances, and eliminating the mass of the mix gives its Eq. 45. On the psychrometric chart the mix sits on the straight line between the two streams, dividing it in the ratio of their dry air masses. The default case gives a humidity ratio of 0.00823 lb/lb and an enthalpy of 25.13 BTU/lb.- Mixed dry-bulb with humidity
t3 = (h3 - 1061 W3) / (0.240 + 0.444 W3)This is the enthalpy equation, h = 0.240 t + W (1061 + 0.444 t), solved for t. The result is 67.3 °F. Example 4 in the 2001 ASHRAE chapter reads 67.1 °F off the chart with a ruler, so the book value is good to a few tenths of a degree.- Mixed dry-bulb with no humidity
t3 = (m1' t1 + m2' t2) / (m1' + m2'), m' = CFM / (t + 459.67)Dry air at one pressure has a mass proportional to CFM over absolute temperature, which is why cold air counts for more than its CFM. For the default temperatures that gives 67.3 °F, within 0.01 °F of the full balance. The plain CFM average, (CFM1 t1 + CFM2 t2) / (CFM1 + CFM2), gives 67.8 °F.- Mixed RH, wet-bulb and dew point
RH from W3 and the saturated W at t3, then the full state from the engineThe balance gives the humidity ratio, and the ratio of vapor pressures turns it into RH, 58.0 percent here. From there the engine returns the wet-bulb, 58.2 °F, and the dew point, 52.1 °F. Averaging the two RH figures directly would give 55.0 percent, which is not the mix.- Past saturation
RH from the balance above 100 percent means fog, so find saturated air at the same enthalpyA mix that lands above the saturation curve forms fog. The page then finds the saturated air at the enthalpy of the mix, which is warmer than the dry-bulb before the fog because condensing water gives up heat, and reports the water that drops out. Liquid water's own enthalpy is left out. 5,000 CFM of saturated 10 °F outdoor air with the same flow of 80 °F, 70 percent RH return air gives 134.7 percent RH by the balance.- Percent outdoor air from three temperatures
OA % = (RAT - MAT) / (RAT - OAT) x 100This follows from the dry-bulb balance with equal specific heats. It is the same ratio as (MAT - RAT) / (OAT - RAT) with both signs flipped. The Example 4 temperatures, 39.2 °F, 77 °F and 67.1 °F, give 26.2 percent. Next to the 25.8 percent that the book's dry air masses give, the thermometer method lands within half a point when the readings are clean.- How much a reading error can move it
error in points = 200 x reading error / |RAT - OAT|Differentiating the formula with respect to the three temperatures gives partial derivatives whose absolute values add up to 2 / |RAT - OAT|. A 1 °F error on each reading therefore moves the answer by up to 5.3 points at 37.8 °F of difference and 33.3 points at 6.0 °F. PNNL calls the method meaningful only above 5 °F of difference and Falke says it works best at 10 °F or more, which is why the page refuses under the first and warns under the second.
Worked examples from the ASHRAE Handbook
The default case is Example 4 in the 2001 ASHRAE Fundamentals chapter on psychrometrics, converted from SI. Read off the chart with a ruler, the book gives 67.1 °F dry-bulb and 58.3 °F wet-bulb, and it puts 25.8 percent of the dry air outdoors. This page gives 67.3 °F, 58.2 °F and 25.8 percent, and the mixed air is at 58.0 percent RH with a dew point of 52.1 °F. The outdoor air is 24.2 percent of the CFM and 25.8 percent of the dry air, because the cold outdoor air is the denser of the two.
The table below shows how far the plain CFM average sits from the dry-air weights when the return air is at 75 °F and 30 percent of the CFM comes from outdoors. That gap is small on a mild day and reaches a degree or more when it is cold. With humidity entered the page uses the full mass and energy balance, and the table is the case with no humidity.
| Outdoor dry-bulb | Plain CFM average | Dry-air weights | Plain minus weighted |
|---|---|---|---|
| -10 °F | 49.5 °F | 46.3 °F | 3.2 °F |
| 20 °F | 58.5 °F | 57.2 °F | 1.3 °F |
| 40 °F | 64.5 °F | 64.0 °F | 0.5 °F |
| 60 °F | 70.5 °F | 70.4 °F | 0.1 °F |
| 95 °F | 81.0 °F | 80.8 °F | 0.2 °F |
Eight cases below run through the same functions the form uses. First comes the ASHRAE example, and the second takes the humidity away to show what the dry-bulb alone gives, 67.3 °F against 67.3 °F. In the sixth row, cold saturated outdoor air meets humid return air and passes the saturation line, so it fogs. The last two rows are the percent form, one on the Example 4 temperatures and one on an economizer check with temperatures chosen for the page and the airflow of the Contracting Business article, where 50.0 percent of 2,000 CFM is 1,000 CFM of outside air.
| Case | Setup | Result |
|---|---|---|
| ASHRAE Example 4 in IP units | Outdoor 4,238 CFM at 39.2 °F, 35.6 °F wet-bulb, return 13,243 CFM at 77 °F, 50% RH | 67.3 °F dry-bulb, 58.2 °F wet-bulb, 58.0% RH, 24.2% outdoor air by CFM |
| Same flows and dry-bulbs, no humidity | Outdoor 4,238 CFM at 39.2 °F, return 13,243 CFM at 77 °F | 67.3 °F by dry-air weights, plain CFM average 67.8 °F, 24.2% outdoor air by CFM |
| Winter, 20 percent outdoor air | Outdoor 1,000 CFM at 20 °F, 60% RH, return 4,000 CFM at 70 °F, 30% RH | 59.2 °F dry-bulb, 46.7 °F wet-bulb, 36.9% RH, 20.0% outdoor air by CFM |
| Summer, 15 percent outdoor air | Outdoor 1,500 CFM at 95 °F, 76 °F wet-bulb, return 8,500 CFM at 75 °F, 50% RH | 77.9 °F dry-bulb, 64.8 °F wet-bulb, 49.4% RH, 15.0% outdoor air by CFM |
| Minimum outdoor air at 5,280 ft | Outdoor 600 CFM at 30 °F, 50% RH, return 5,400 CFM at 72 °F, 40% RH, 5,280 ft | 67.5 °F dry-bulb, 53.6 °F wet-bulb, 43.0% RH, 10.0% outdoor air by CFM |
| Cold saturated air meets humid return air | Outdoor 5,000 CFM at 10 °F, 100% RH, return 5,000 CFM at 80 °F, 70% RH | past saturation at 134.7% RH, saturated at 47.0 °F after the fog, 45.7 lb/h of water, 50.0% outdoor air by CFM |
| Percent outdoor air, Example 4 temperatures | OAT 39.2 °F, RAT 77 °F, MAT 67.1 °F | 26.2 percent outdoor air, up to 5.3 points of error per 1 °F |
| Economizer check, 2,000 CFM unit (temperatures chosen for the page) | OAT 40 °F, RAT 80 °F, MAT 60 °F | 50.0 percent outdoor air, about 1,000 CFM of outdoor air, up to 5.0 points of error per 1 °F |
Standards and data sources
- 2001 ASHRAE Fundamentals Handbook (SI), Chapter 6 Psychrometrics, Adiabatic Mixing of Two Moist Airstreams - mixing equations by mass of dry air, the straight-line result on the chart, and Example 4. The page opens on that example converted to IP units, 4,238 CFM at 39.2 °F and 35.6 °F wet-bulb with 13,243 CFM at 77 °F and 50 percent RH. Its chart readings are 67.1 °F dry-bulb and 58.3 °F wet-bulb, and this page gives 67.3 °F and 58.2 °F. Tests allow half a degree against the book. Later editions carry the same section in Chapter 1.
- ASHRAE Handbook - Fundamentals (2021), Ch. 1 Psychrometrics - the humidity ratio, specific volume, enthalpy and wet-bulb equations (Eq. 22, 26, 32, 35 and 37) and the standard atmosphere that the psychrometric engine behind this page uses for the state of each stream and of the mix.
- Rob Falke, Measuring Fresh Air With a Thermometer, Contracting Business, 2008 - a field check from outside air, return air and mixed air temperatures. The article says the formula does not give good results when indoor and outdoor conditions are nearly the same, that it works best with 10 degrees or more of difference, and that smaller differences call for readings to a tenth of a degree. Its example puts 1,000 CFM of outside air in a 2,000 CFM system at 50.0 percent, which the tests reproduce.
- PNNL, Building Re-tuning, AHU Minimum Outdoor-Air Operation (PNNL-SA-88958) - the outdoor air fraction as (MAT - RAT) / (OAT - RAT) and the caution that it is only meaningful when the outdoor air temperature differs from the return air temperature by a margin of about 5 °F either way. This page refuses under that margin.
Limitations of this calculator
- Steady state and well mixed. The page treats the two streams as blended completely, and a real mixing box can leave layers. A reading taken in a layer is one stream's temperature, not the mix.
- Each CFM is for its own stream. The page treats each figure as measured in the air of that stream. A CFM read at the coil, after mixing, is a third figure, and with humidity entered the page shows the mixed airflow at the conditions of the mix.
- Without humidity the answer is an estimate. Dry-air weights from absolute temperature land within 0.01 °F of the full balance for the default case, and moisture moves it a little more in wet air. The plain CFM average sits 0.5 °F from the full balance there, and 3.6 °F away with outdoor air at -10 °F and return air at 75 °F.
- Nothing between the readings is modeled. A fan, a heater, a coil or a long duct run between the mixing point and the sensor changes the temperature, and the page cannot see it. The percent form in particular fails when the mixed-air sensor sits after a fan.
- The temperature method needs room between OAT and RAT. This page refuses a difference under 5 °F, following PNNL, and warns under 10 °F, following Falke. Those two figures are rules of thumb from the trade literature, not limits from a code.
- A fogged mix is an estimate. The page finds saturated air at the enthalpy of the mix and leaves out the enthalpy of the liquid water, so the temperature after the fog is close but not exact. Real fog also depends on how the streams meet.
- Humidity comes from the project's psychrometric engine, which uses the Magnus-Tetens saturation curve, within about 0.5 °F of Hyland-Wexler in the HVAC range. Dry-bulb range is -40 to 150 °F, relative humidity from 1 percent, and elevation from -500 to 12,000 ft.
- Outdoor air percent does not say whether a space is ventilated enough. The ventilation rate comes from a standard such as ASHRAE 62.2 or 62.1, and a measured airflow is the proof.
- This is a planning and field-check estimate. A licensed contractor, the equipment manufacturer's instructions and the authority having jurisdiction decide the installation, and the page makes no claim of code compliance.
Common mixed air mistakes
- Averaging the dry-bulbs by CFM on a cold day. The plain CFM average ignores that cold air is denser. With 4,000 CFM at -10 °F and 6,000 CFM at 75 °F it gives 41.0 °F, while the dry-air weights give 37.4 °F, 3.6 °F lower. The gap shrinks on mild days and grows with the spread.
- Averaging relative humidity or wet-bulb. Humidity mixes in humidity ratio and enthalpy, not in RH. Weighting the two RH figures of the default case by CFM gives 55.0 percent, and the mix is at 58.0 percent. RH depends on temperature, so a straight average of it carries no meaning.
- Reading the mixed air after the fan. A sensor behind the supply fan reads the mix plus the heat of the motor and the fan. With OAT at 40 °F and RAT at 75 °F, a true mix of 55 °F is 57.1 percent outdoor air, and a sensor that reads 58 °F makes it 48.6. That is 8.6 points of outdoor air lost to heat that is not in the mix.
- Trusting a reading with OAT close to RAT. With OAT and RAT only 6.0 °F apart, a 1 °F error in each reading can move the answer by 33.3 points, against 5.3 points when they are 37.8 °F apart. A result of 50.0 percent from such a day tells almost nothing. Wait for a day with 10 °F or more of difference, or measure the airflows.
- Taking a damper position for the outdoor air percent. A damper at 20 percent open is not 20 percent outdoor air. Linkage slop, leakage past the blades, fan speed and the pressure in the mixing box all move the real fraction. The temperature check or an airflow measurement shows what the unit is doing.
- Ignoring fog when cold and humid air meets warm return air. 5,000 CFM of saturated 10 °F outdoor air with the same flow of 80 °F, 70 percent RH return air gives 134.7 percent RH by the balance. Water drops out, about 45.7 lb/h, and the air after the fog is at 47.0 °F, not the 42.6 °F the dry-bulb balance alone gives.
Common questions about mixed air
How do you calculate mixed air temperature?
Turn each CFM into pounds of dry air with the specific volume of its stream, weight the humidity ratios and the enthalpies by those masses, and solve the enthalpy equation for the dry-bulb. For 4,238 CFM at 39.2 °F and 35.6 °F wet-bulb with 13,243 CFM at 77 °F and 50 percent RH, the mix is 67.3 °F dry-bulb and 58.2 °F wet-bulb. With dry-bulbs alone, weight each by CFM divided by absolute temperature.
Can I just average the temperatures by CFM?
For a quick estimate, yes. The plain average gives 67.8 °F for the default case and the mass balance gives 67.3 °F, 0.5 °F apart. That gap grows with the spread, to 3.6 °F at -10 °F outdoors and 75 °F indoors, because cold air is denser and counts for more than its CFM. ASHRAE states the mixing law by mass of dry air.
How do I find percent outdoor air with a thermometer?
Read the outdoor air, return air and mixed air temperatures, then divide the return minus the mixed by the return minus the outdoor, and multiply by 100. With 39.2 °F outdoors, 77 °F return and 67.1 °F mixed that is 26.2 percent. Multiply by the total airflow to get outdoor CFM, as in Falke's example of 1,000 CFM of outside air in a 2,000 CFM system at 50.0 percent.
How far apart do the outdoor and return temperatures need to be?
PNNL calls the method meaningful only when the outdoor air differs from the return air by a margin of about 5 °F, and Falke says it works best at 10 °F or more. This page refuses under 5 °F and warns under 10 °F. The reason is arithmetic. With each reading off by 1 °F, the answer can move by 200 divided by the difference in points, which is 5.3 points at 37.8 °F and 33.3 points at 6.0 °F.
Why does my percent outdoor air come out below 0 or above 100?
Two streams that mix give an air temperature between theirs, so the mixed-air temperature must fall between OAT and RAT. A MAT of 85 °F with 40 °F outdoors and 80 °F return would be negative 12.5 percent. The usual causes are a mixed-air sensor after a fan, a heater or a coil, a sensor in unmixed air, a swapped reading and a thermometer that is off. This page refuses the result and shows the raw figure.
What happens when cold outdoor air mixes with humid return air?
If the balance lands above the saturation curve, fog or condensation forms. For 5,000 CFM of saturated 10 °F air with the same flow of 80 °F, 70 percent RH return air, the balance gives 134.7 percent RH. The page shows the dry-bulb before the fog, 42.6 °F, the saturated air after it, 47.0 °F, and about 45.7 lb/h of water.
Does elevation change the mixed air?
With humidity entered, yes. Pressure sets the humidity ratio and the specific volume. The default readings at 5,280 ft give a mixed humidity ratio of 0.01007 against 0.00823 at sea level, and a mixed dry-bulb of 67.3 °F against 67.3 °F. A dry-bulb-only mix does not use elevation.
How close is this to the ASHRAE example?
ASHRAE Example 4 reads the mix at 67.1 °F dry-bulb and 58.3 °F wet-bulb off the chart with a ruler, and its dry air masses put 25.8 percent of the dry air outdoors. This page, run on the same example in IP units, gives 67.3 °F, 58.2 °F and 25.8 percent. The tests allow half a degree against the book.
Is there a limit on how many times I can run this?
No. This calculator runs in your browser with no daily limit and no signup.
Used on the same job
Read the mixed air where the streams have blended
The number is only as good as the readings behind it. A probe in the wrong spot reads one stream. Take the return air at the return, the outdoor air away from exhaust and the mixed air where the two have blended, ahead of any fan, heater or coil. When the outdoor and return air are within 10 °F of each other, the percent form loses most of its accuracy, so wait for a day with more spread or measure the airflows. You can also ask the assistant to talk through a set of readings from a unit.