A preliminary number for a certified technician. The nameplate, the installation instructions and the local code come first, and the final charge is set by the manufacturer's charging method.

Maintained by BuildSolver · Updated

Calculator · Refrigerant charge

Line set charge calculator

An outdoor unit ships charged for a set length of line, and every foot beyond it needs more refrigerant at the rate the manufacturer prints. Goodman's long-line guide, for one, covers 15 ft and adds 0.6 oz per foot of 3/8 in. liquid line on its R-410A units, so a 50 ft run takes 21.0 oz. Your unit may differ. Enter the numbers from your unit's instructions. To check the charge afterward, use the superheat and subcooling calculator.

  1. Choose the refrigerant, then enter the actual line set length and the length the factory charge covers.
  2. Type the ounces per foot the outdoor unit's installation instructions give for your liquid line size.
  3. The result shows ounces and pounds to add, with a reference for the liquid the extra line holds.

Preliminary. Use the rate and factory length from the installation instructions. The installation instructions, the nameplate and the local code come first. No line sizing and no A2L charge limit.

Switching away from the R-410A example clears the rate and the factory length, because each refrigerant and unit has its own.

Actual length of the run, end to end. Equivalent length, which adds allowances for fittings, is for checking long-line limits.

From the outdoor unit's installation instructions or nameplate.

Ounces per foot beyond the factory length, for this unit and liquid line size. Required, the page has no default for it.

Used for the reference estimate of the liquid in the line. If you change it, check that the rate is for this size.

Measured at the liquid service valve, or condensing temperature minus subcooling. Only the reference estimate uses it.

Past this length the manufacturer's long-line guide takes over.

Adds the result to the nameplate charge for a system total. For A2L units that total is what the charge limit applies to.

Example result for the default inputs

R-410A, 50 ft line set, 3/8 in. OD liquid line, factory charge covers 15 ft.

Charge to add

21.0 oz

Same amount in pounds

1.31 lb

Line beyond the factory length

35 ft

Calculation details
How it was worked(50 - 15) ft x 0.6 oz per ft
Reference, liquid one foot of this line holds0.52 oz per ft (R-410A, 3/8 in. OD, 100°F liquid)
Reference, liquid in the extra liquid line18.2 oz. Physics only, it leaves out the suction line and never replaces the manufacturer's rate.
Final chargeSet by the manufacturer's charging method after the addition, usually subcooling or superheat.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the charge addition is calculated

The outdoor unit ships with enough refrigerant for the coil, the condenser and a set length of line. Every foot past that length needs more, at a rate the manufacturer prints in the installation instructions. The calculator does that arithmetic and, next to it, shows how much liquid the extra liquid line physically holds.

Charge to add
(total length - factory length) x oz per ftThis is the manufacturer's method. Goodman TP-107M writes it for its residential R-410A units as (L - 15) ft x 0.6 oz per ft, which gives 21.0 oz for a 50 ft line.
Pounds
oz / 16Scales read in pounds and ounces, so the result is shown both ways.
Liquid in one foot of line (reference)
pi / 4 x ID² / 144 x liquid density x 16ID is the inside diameter of annealed ACR tube from the Copper Development Association handbook, 0.311 in. for 3/8 in. OD. Density is saturated liquid at the temperature you enter, from CoolProp. For R-410A in 3/8 in. line at 100°F that is 0.52 oz per foot.
Rate against physics
manufacturer rate vs liquid in the lineGoodman lists its 0.6 oz per foot for the 3/8 in. liquid line alone, above the 0.52 the physics gives at 100°F, and the guide does not state the basis. Its table then steps the rate up to 0.78 oz per foot once a suction line as large as 1-1/8 in. is counted. Either way, the rate is what goes on the scale.

Line lengths and what the line holds

Goodman's published R-410A numbers, 15 ft and 0.6 oz per foot of 3/8 in. liquid line, at five run lengths, next to the liquid the extra line holds at 100°F.

Refrigerant to add by line set length with Goodman TP-107M numbers
RunExtra ftAdd, ozAdd, lbLiquid in extra line, oz
Worked example, 50 ft3521.01.3118.2
40 ft run2515.00.9413.0
65 ft run5030.01.8826.1
90 ft run7545.02.8139.1
Exactly 15 ft00.00.000.0

On the 50 ft run the rate asks for 21.0 oz while the extra liquid line holds about 18.2 oz. Goodman labels its rate for the liquid line alone and does not give the basis for the 2.8 oz gap. The rate is the number that goes on the scale.

Liquid one foot of annealed ACR tube holds at 100°F liquid, in ounces. Physics only, for checking that a rate is in the right range.

Ounces of saturated liquid per foot of liquid line by refrigerant and tube size
Refrigerant1/4 in. OD, ID 0.1905/16 in. OD, ID 0.2483/8 in. OD, ID 0.3111/2 in. OD, ID 0.436
R-410A0.190.330.521.02
R-220.220.380.601.18
R-320.180.300.480.94
R-454B0.180.310.490.96

R-32 liquid is lighter than R-410A, so 3/8 in. line holds about 9 percent less of it. That is one reason an R-410A rate cannot be carried to an A2L unit. The other is that the A2L system's total charge has a ceiling, which the installation manual states.

Standards and data sources

Limitations of this calculator

  • The result is only as right as the rate and factory length you enter, so take both from the installation instructions that shipped with the outdoor unit you are setting today.
  • The addition is a starting amount. Manufacturers call for a final charge check after it, by subcooling, superheat or weight, and that procedure governs.
  • The reference estimate assumes the liquid line runs full of liquid at the temperature you enter and treats subcooled liquid as saturated liquid at that temperature, which reads about half a percent light for every 10°F of subcooling. It ignores the suction line, the oil dissolved in the refrigerant and anything held in an accumulator or receiver.
  • Line set sizing, oil return, traps and long-line accessories are not calculated. Past the length the standard instructions cover, the manufacturer's long-line guide applies.
  • For A2L refrigerants (R-454B, R-32) the total charge limit under UL 60335-2-40, the room area it implies and any leak detection requirement are not calculated. Read them from the installation manual.
  • When the line is shorter than the factory length, the page prints no number. The short-line instructions in the manual govern that case.
  • The work is for a certified technician under EPA Section 608. The calculator gives a preliminary number, and the nameplate, the installation instructions and the local code come first.

Common line set charge mistakes

  1. Using equivalent length for the charge. Equivalent length adds allowances for elbows and is how manufacturers judge whether a long line is acceptable. Goodman's guide bases the charge addition on actual linear length. Measure the tubing, not the fitting count.
  2. Carrying an R-410A rate to an A2L unit. R-454B and R-32 have different liquid densities and different factory charges. A rate from an R-410A manual does not transfer. The form clears the rate when you change refrigerant for this reason.
  3. Treating the physical estimate as the rate. The liquid in 3/8 in. R-410A line at 100°F is about 0.52 oz per foot, below Goodman's 0.6. Charging by the physics alone would leave the system short of what the manufacturer expects.
  4. Skipping the final charge check. The addition gets the system close. Close is not finished. Indoor airflow, the actual liquid line temperature and the coil all move the right charge, so finish with the manufacturer's charging method.
  5. Forgetting the line already in the factory length. The first part of the run is already paid for. Subtract it before multiplying, or a 50 ft line gets charged as if all 50 ft were extra.

Common questions about line set charge

How much refrigerant do I add per foot of line set?

Whatever the outdoor unit's installation instructions say for that liquid line size. Goodman's TP-107M guide, for example, gives 0.6 oz per foot of 3/8 in. liquid line for its residential R-410A units, beyond the first 15 ft. Other manufacturers and other refrigerants use their own numbers.

How much refrigerant do I add for a 50 ft line set?

Subtract the length the factory charge covers and multiply by the rate. With Goodman's R-410A numbers, 15 ft and 0.6 oz per foot, that is (50 - 15) x 0.6 = 21.0 oz, about 1.31 lb, before the final charge check.

How do I calculate the line set charge for R-454B or R-32?

The same way. Take the rate and the factory length from that unit's own instructions. Rates differ by manufacturer and model, so no published rate serves as a default for either refrigerant, and the field stays empty until you enter one. A2L systems also have a total charge limit under UL 60335-2-40 that the manual states for each unit.

How many ounces of refrigerant does a foot of 3/8 line hold?

With R-410A liquid at 100°F, about 0.52 oz, from the tube's inside diameter and the liquid density. At 120°F it drops to about 0.48 oz, because hot liquid is lighter. Goodman's published rate for the same line is 0.6 oz, and the rate in your manual is the one to charge by.

Do I remove refrigerant for a short line set?

Not by this page. The answer belongs to the manufacturer, so the calculator prints no number for that case. Check the short-line instructions in the installation manual and finish with the charging method it gives.

Does the line set charge use actual or equivalent length?

Goodman's long-line guide uses actual linear length for the charge addition and equivalent length to decide whether a long line is acceptable at all. Check which length your unit's instructions call for at each step.

What size line set do I need?

Not from this page. Liquid and suction sizes, maximum lengths and the lift allowed between the units all come from the manufacturer's tables for the specific outdoor and indoor match you are installing.

Used on the same job

Get the load in chat

A perfect charge on a unit that is the wrong size for the house still leaves rooms warm on the hottest afternoons and damp in the shoulder months. Describe the house in chat and the assistant runs the free whole-house Manual J cooling and heating load. The chat does not work out refrigerant charge, so keep this page for that.