For estimation and planning use. The heater manufacturer's data, a licensed contractor and the authority having jurisdiction decide the heater, the gas or electric supply and the installation. Gas heaters are sized from the maker's rated input. Not a substitute for a contractor's pool heater calculation.

Maintained by BuildSolver · Updated

Calculator · Pool heater

Pool heater size calculator

A pool heater is chosen by its input in BTU/h and checked by how long it takes to warm the water. Raypak's rule gives the input from the surface area and the rise from the coldest month's mean air temperature to the pool temperature, and Pentair's formula gives the hours from the gallons, the rise, the heater input and its efficiency. Pentair's own example pool of 40 by 20 ft at 5.5 ft holds 33,000 gal. Held at 82°F against a 57°F mean, a 25°F rise, the rule gives 300,000 BTU/h, and a 300,000 BTU/h heater at 84 percent takes 21.8 hours to heat the water 20°F before any loss. The page does not calculate evaporation or wind losses, and it sizes gas, propane and electric resistance heaters. For the gas line, use the gas pipe sizing calculator. For the air the heater burns, use the combustion air calculator.

  1. Enter the surface area and the average depth of the pool, the pool temperature you want, and the mean air temperature of the coldest month the pool is used. The difference is the rise, 25°F in the default case.
  2. Multiply the area by the rise and by 15 for the input in BTU/h. Choose a faster heating rate or a commercial pool where it applies, and step up one model size in high wind.
  3. Enter the water temperature the heat-up starts from, the heater efficiency, and the input of a heater you are weighing. The result gives the hours it takes and the input that would do it in the target time.

Gas, propane and electric resistance pool heaters, 100 to 20,000 sq ft of surface, outdoor or indoor. The form opens on Pentair's 40 by 20 ft pool at 5.5 ft, 33,000 gal, with no heater input entered.

Length times width for a rectangle, and radius squared times 3.14 for a round pool. The page opens on Pentair's 40 by 20 ft example.

For a pool with a shallow and a deep end, average the two depths. A 3 ft shallow end and an 8 ft deep end average 5.5 ft.

Raypak's rule rests on a 3-1/2 MPH average wind. High wind adds a note to step up one model size. An indoor pool is outside the rule, so enter the room air temperature below, and a rise above 10°F is refused.

Raypak's table assumes a 24-hour recovery. For a commercial pool on a 30-hour recovery it multiplies the listed pool size by 1.25, so this page divides the input by 1.25.

The Department of Energy's fact sheet gives 78 to 82°F as the typical range for pools.

Raypak sizes on the pool temperature less this mean. Use the mean for the coldest month of the swimming season, not the coldest night. For an indoor pool enter the temperature the pool room is held at.

Raypak's formula is based on 1 to 1-1/4°F per hour. A faster heat-up adds 50 percent to the input for 1-1/2°F per hour and 100 percent for 2°F per hour.

The water temperature a cold start begins from, such as the pool in spring. The heat-up runs from here to the desired pool temperature.

Thermal efficiency from the heater's label. Jandy's Energy Guide labels show 83 and 84 percent for its gas models, and an electric resistance heater is 100 percent. A heat pump is not sized on this page.

The page gives the heater input that would raise the water in this many hours. Pentair's tables use 24 hours.

The rated input of a heater you are weighing. A spec sheet that prints MBH is 1,000 BTU/h per MBH. Leave it blank to time the heater that the surface-area rule gives.

Example result for the default inputs

800 sq ft pool, 33,000 gal, held at 82°F with a 25°F rise over the air temperature entered.

Heater input, surface-area method

300,000 BTU/h

Heat to raise the water

5,504,400 BTU

Heat-up time at the heater input

21.8 hours

Input to heat in 24 hours

273,036 BTU/h

Calculation details
Pool800 sq ft, 5.5 ft average depth, 33,000 gal
Rise for sizing82°F pool less 57°F air is 25°F
Input by pool area800 x 25 x 15 = 300,000 BTU/h
Heat-up from62°F to 82°F, a 20°F rise
Heater input checked300,000 BTU/h, the surface-area result
Heater output252,000 BTU/h at 84 percent efficiency
Net heating rate0.92°F per hour before losses
Run time to win back 2°F2.2 hours, 550,440 BTU
Run time to win back 4°F4.4 hours, 1,100,880 BTU
  • The heat-up time counts only the heat that raises the water. Pentair's time formula has no loss term, so a real heat-up is longer, most of all on a cool, windy or uncovered pool.
  • Gas heater input is the maker's rated figure for the model, and any derate for elevation or venting comes from the installation manual. This page applies none, so size a gas heater from the manufacturer's data.
  • Before any loss this heater raises the water about 0.92°F per hour. Raypak's formula rests on 1 to 1.25°F per hour, so a deep pool or a small heater heats more slowly than the formula assumes. Jandy's chart assumes 4.5 ft of average depth.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the pool heater input and heat-up time are calculated

This page uses two published methods. One sizes the heater input from the surface area of the pool and the temperature rise, which is Raypak's rule and rests on a 3.5 MPH average wind and a heat-up of 1 to 1.25°F per hour. The other counts the heat that the water itself needs from the volume, which is Pentair's time formula, and gives the hours a given heater takes and the input that would do it in a target time. Losses to evaporation, wind and the night sit inside the first method as an allowance and are left out of the second, and the page does not calculate them. Gas heaters need the maker's rated input and its derates, and heat pumps are not sized here.

Temperature rise
rise = desired pool temperature - mean air temperature of the coldest month usedRaypak sizes on the rise from the coldest month's mean to the pool temperature you want. 82°F against 57°F is a 25°F rise. The maker's table has columns for 20, 25, 30 and 35°F.
Input by pool area
BTU/h input = pool area x rise x 15The factor is 15 BTU/h of input per square foot per °F of rise. 800 sq ft at a 25°F rise is 300,000 BTU/h. The same rule reproduces the maker's own table, since each printed row works out to within 1 percent of its model's input.
Faster heating and commercial pools
input x 1.5 for 1-1/2°F per hour, x 2 for 2°F per hour; input / 1.25 for a commercial pool on a 30-hour recoveryFor 1-1/2°F per hour Raypak adds 50 percent to the input, which makes 450,000 BTU/h here, and for 2°F per hour it adds 100 percent, which makes 600,000 BTU/h. Raypak's table rests on a 24-hour recovery, and for a 30-hour recovery it multiplies the listed pool size by 1.25. A heater therefore serves a larger pool, and the input for this pool is the area rule divided by 1.25, which gives 240,000 BTU/h.
Volume
gallons = area x average depth x 7.5Pentair estimates gallons as length times width times average depth times 7.5 for a rectangle, which is the area times the depth times 7.5. 800 sq ft at 5.5 ft is 33,000 gal, the 40 by 20 ft pool in Pentair's own example.
Heat for the water
BTU = gallons x 8.34 x riseA gallon of water weighs 8.34 lb in Pentair's formula and takes 1 BTU per pound for each °F, so 33,000 gal raised 20°F needs 5,504,400 BTU before any loss.
Heat-up time
hours = gallons x 8.34 x rise / (heater BTU/h input x efficiency)Dividing the heat by what the heater puts into the water gives the hours. A heater of 300,000 BTU/h at 84 percent puts 252,000 BTU/h into the water, so 5,504,400 BTU takes 21.8 hours, a rise of 0.92°F per hour before losses.
Input for a target time
BTU/h input = gallons x 8.34 x rise / (hours x efficiency)Solving the same formula for the input gives 273,036 BTU/h to heat 20°F in 24 hours at 84 percent. The two methods need not agree, because the first is a rule for the whole pool and the second counts only the water.
Run time to hold the temperature
run hours a day = gallons x 8.34 x daily loss / (input x efficiency)Pentair says a pool will usually lose 2 to 4°F per day in cooler periods. Winning back 2°F is 550,440 BTU and takes 2.2 hours of run time at 300,000 BTU/h, and 4°F takes 4.4 hours, against the 4 to 6 hour daily filter cycle that Pentair names.

Worked examples from published pool heater data

The default case is the 40 by 20 ft pool of Pentair's gallons example, 800 sq ft at 5.5 ft average depth, which holds 33,000 gal. At 82°F against a 57°F coldest-month mean, Raypak's rule gives 300,000 BTU/h. Heating the water from 62°F to 82°F needs 5,504,400 BTU by Pentair's formula. At 84 percent, 300,000 BTU/h takes 21.8 hours and 273,036 BTU/h would take 24 hours. A 400,000 BTU/h heater takes 16.4 hours.

The table below runs every printed row of Raypak's P-514, P-624 and P-824 sizing table through the area rule. Each model number is read as its input in thousands of BTU/h. The pool area times the rise times 15 lands within 1 percent of that input in every row, for example 1,360 sq ft at 25°F for the P-514, which is 510,000 BTU/h against 514,000.

Raypak printed pool areas against the surface-area rule
ModelRise, °FPrinted area, sq ftArea x rise x 15, BTU/hModel input, BTU/hDifference, %
P-514201,700510,000514,0000.8
P-514251,360510,000514,0000.8
P-514301,135510,750514,0000.6
P-51435970509,250514,0000.9
P-624202,090627,000624,0000.5
P-624251,670626,250624,0000.4
P-624301,390625,500624,0000.2
P-624351,190624,750624,0000.1
P-824202,750825,000824,0000.1
P-824252,200825,000824,0000.1
P-824301,830823,500824,0000.1
P-824351,570824,250824,0000.0

Eight cases below run through the same functions the form uses. Five of them use the Pentair pool and change one input at a time. A 15°F rise from a 67°F month cuts the area rule to 180,000 BTU/h and stretches that heater to 36.4 hours. The faster rates raise the input to 450,000 and 600,000 BTU/h, and a commercial pool on a 30-hour recovery divides the input by 1.25, which makes 240,000 BTU/h for the Pentair pool.

Pool heater input and heat-up time for eight example pools
CaseSetupResult
Pentair example pool800 sq ft, 5.5 ft deep, 33,000 gal, 82°F against 57°F300,000 BTU/h by area, 21.8 hours to heat 20°F at 300,000 BTU/h, 273,036 BTU/h for 24 hours
Same pool, 400,000 BTU/h heater800 sq ft, 5.5 ft deep, 33,000 gal, 82°F against 57°F300,000 BTU/h by area, 16.4 hours to heat 20°F at 400,000 BTU/h, 273,036 BTU/h for 24 hours
Same pool, mild climate, 15°F rise800 sq ft, 5.5 ft deep, 33,000 gal, 82°F against 67°F180,000 BTU/h by area, 36.4 hours to heat 20°F at 180,000 BTU/h, 273,036 BTU/h for 24 hours
Same pool, 1-1/2°F per hour800 sq ft, 5.5 ft deep, 33,000 gal, 82°F against 57°F450,000 BTU/h by area, 14.6 hours to heat 20°F at 450,000 BTU/h, 273,036 BTU/h for 24 hours
Same pool, 2°F per hour800 sq ft, 5.5 ft deep, 33,000 gal, 82°F against 57°F600,000 BTU/h by area, 10.9 hours to heat 20°F at 600,000 BTU/h, 273,036 BTU/h for 24 hours
Backyard pool, 16 by 32 ft512 sq ft, 4.5 ft deep, 17,280 gal, 82°F against 55°F207,360 BTU/h by area, 18.2 hours to heat 22°F at 207,360 BTU/h, 157,269 BTU/h for 24 hours
Small pool, 14 by 28 ft392 sq ft, 4 ft deep, 11,760 gal, 80°F against 58°F129,360 BTU/h by area, 18.1 hours to heat 20°F at 129,360 BTU/h, 97,300 BTU/h for 24 hours
Commercial pool, 2,000 sq ft2,000 sq ft, 4.5 ft deep, 67,500 gal, 82°F against 57°F, commercial600,000 BTU/h by area, 22.3 hours to heat 20°F at 600,000 BTU/h, 558,482 BTU/h for 24 hours

Standards and data sources

  • Raypak, P-514 Manual, pool heater sizing page - The rule BTUH input required = pool area x desired temperature rise x 15, based on 1 to 1.25°F per hour and a 3.5 MPH average wind. It adds 50 percent to the input for 1-1/2°F per hour and 100 percent for 2°F per hour, says to select a heater one size larger where high wind exists, and, for a commercial pool on a 30-hour recovery against the 24 hours of its table, multiplies the listed pool size by 1.25. Its table of pool area by rise at 20, 25, 30 and 35°F is reproduced in the worked examples.
  • Pentair, Product Catalog 2025-2026, Engineering Data, Heater Sizing Information - The time formula in hours with the 8.34 lb per gallon, the estimate of gallons in a pool with 7.5 gallons per cubic foot for a rectangle and its 40 by 20 ft example, the 2 to 4°F daily loss in cooler periods, the 4 to 6 hour filter cycle for maintenance heating, and a time formula that counts only the heat that raises the water. It sends commercial heaters of 500,000 BTU/h and over to the factory.
  • Fluidra, Jandy Gas Heaters (JXiQ and JXi), 2024 Product Catalog Addendum - A pool sizing chart that assumes 4.5 ft of average depth and 1°F per hour, and Energy Guide labels with a thermal efficiency of 83 and 84 percent for its gas models. The 84 percent default comes from these labels.
  • U.S. Department of Energy, Energy Savers, Heat Pump Swimming Pool Heaters (archived 2004 fact sheet) - The statements that evaporation turns out to be 70 percent of the heat loss from a pool, that a cover can reduce a pool's energy consumption by 50 to 75 percent, and that the typical range for pools is 78 to 82°F. These are used as text only, and no number from the sheet enters a formula.

Limitations of this calculator

  • Evaporation, wind and night losses are not calculated. The Department of Energy's archived fact sheet puts evaporation at 70 percent of a pool's heat loss, but the sources quoted here give no coefficients for it, so Raypak's area rule stands in for all of it and the time formula leaves it out.
  • Raypak's rule rests on a 3.5 MPH average wind and a heat-up of 1 to 1.25°F per hour, and it has no depth term. A windier site, a deeper pool or an uncovered pool in a cold month can need more than it gives, which is why Raypak says to select one size larger where high wind exists.
  • The heat-up time counts only the heat that raises the water. Pentair's time formula has no loss term, so a real heat-up is longer, and a pool that loses heat as fast as the heater adds it never reaches temperature. Results beyond 168 hours are refused.
  • Heater models come in fixed sizes, and a maker's model number is not the input this page prints. Take the figure to the manufacturer's data for the model, its rated input, its efficiency and any derate for elevation, venting or gas type. This page applies none of them.
  • Gas, propane and electric resistance heaters only. A heat pump is rated by a COP above 1, not by an efficiency under 100 percent, and solar collectors depend on sun and roof area, so neither is sized here. The efficiency field takes 50 to 100 percent.
  • An indoor pool is outside Raypak's outdoor basis. Its evaporation goes into the room air and has to be removed by the building's dehumidification and ventilation, which is a separate design with its own load. Enter the room air temperature for an indoor pool, since the outdoor mean would give a rise the room never has. A rise above 10°F is refused.
  • A cover is not credited. The Department of Energy's fact sheet says a cover can reduce a pool's energy consumption by 50 to 75 percent, which would shorten real heat-ups and lower the heater needed, and the page gives no figure for it.
  • Volume is the area times the average depth times 7.5, so an irregular pool needs a fair average depth. Spas and hot tubs heat on other tables and are not sized here, and a pool above 500,000 BTU/h of input goes to the manufacturer.
  • This is a planning estimate, not a design drawing. A licensed contractor, the manufacturer's data and the authority having jurisdiction decide the heater, the gas or electric supply and the installation.

Common pool heater sizing mistakes

  1. Using the pool temperature as the rise. Raypak's rule takes the rise from the coldest month's mean air temperature to the pool temperature, and not the pool temperature alone. 82°F against 57°F is 25°F and gives 300,000 BTU/h, while a milder 67°F month gives a 15°F rise and 180,000 BTU/h.
  2. Leaving the efficiency out of the heat-up time. Pentair divides by the input times the efficiency of the heater. At 84 percent a 300,000 BTU/h heater puts 252,000 BTU/h into the water, and the heat-up takes 21.8 hours. A heater taken as 100 percent efficient would show 18.3 hours.
  3. Treating the heat-up time as a promise. The formula gives 21.8 hours for 20°F with no loss at all. Pentair's formula has no loss term, so a cool night, wind or an uncovered pool lengthens it. Plan on more than the figure, and keep the pool covered while it heats to hold what the heater adds.
  4. Ignoring wind. Raypak's formula assumes a 3.5 MPH average wind and says to go one size larger where high wind conditions exist. A pool in an exposed yard sized at 300,000 BTU/h should be checked against the next model up.
  5. Sizing a deep pool on its area alone. The area rule has no depth in it. Jandy's chart assumes 4.5 ft of average depth. The default pool is 5.5 ft deep, holds 33,000 gal, and at 300,000 BTU/h heats about 0.92°F per hour before losses, which is under the 1°F per hour that the rule is based on. A deeper pool should be checked with the time formula.
  6. Forgetting the gas line, the air and the vent. A heater of 300,000 BTU/h burns gas at a rate set by its input, so the gas line, the combustion air and the venting are sized from the maker's input for the model chosen. The gas pipe sizing calculator and the combustion air calculator take that input.

Common questions about pool heater size

How do you size a pool heater?

Multiply the pool surface area in square feet by the temperature rise in °F and by 15, which is Raypak's rule for the BTU/h of input. The rise is the pool temperature you want less the mean air temperature of the coldest month you swim. 800 sq ft at 82°F against 57°F is a 25°F rise and 300,000 BTU/h. The rule rests on a 3.5 MPH wind and 1 to 1.25°F per hour.

How long does it take to heat a pool?

Multiply the gallons by 8.34 and by the rise in °F, then divide by the heater's BTU/h input times its efficiency. That is Pentair's formula. For 33,000 gal raised 20°F by a 300,000 BTU/h heater at 84 percent it gives 21.8 hours, and a 400,000 BTU/h heater gives 16.4 hours. Real heat-ups run longer because the formula leaves out losses.

Which temperature rise do I use?

Use the pool temperature you want less the mean air temperature of the coldest month the pool is used. Raypak's table has columns for 20, 25, 30 and 35°F. This page accepts a rise up to 60°F and adds a note outside 20 to 35°F, since the maker's table does not confirm the rule there.

Do I need a bigger heater for wind or a faster heat-up?

Raypak says to select a heater one size larger than the formula gives where high wind conditions exist. It also adds 50 percent to the input for a heat-up of 1-1/2°F per hour and 100 percent for 2°F per hour, which takes the default pool from 300,000 BTU/h to 450,000 BTU/h and 600,000 BTU/h.

How does heater efficiency change the size?

Pentair's time formula divides by the input times the efficiency, so a lower efficiency means less heat reaches the water. Jandy's Energy Guide labels show 83 and 84 percent for its gas models, and this page opens on 84 percent. Raypak's input rule is already an input figure, so the efficiency enters the time and the input for a target time and not the area rule.

Should the heater heat the pool in one day?

Pentair separates maintenance heating from spot heating. A smaller heater run through the daily 4 to 6 hour filter cycle can hold a pool that loses 2 to 4°F a day, and a larger one heats a pool quickly for a weekend. Heating 20°F in 24 hours takes 273,036 BTU/h at 84 percent for the default pool.

Why do the area rule and the time formula give different numbers?

They answer different questions. Raypak's rule scales with the rise and has no depth term, while the time formula counts the water. For a pool 4.5 ft deep heated 1°F per hour at 84 percent, the volume method needs about 335 BTU/h per square foot. Raypak's rule gives 300 at a 20°F rise and 375 at a 25°F rise, so it falls below the volume figure in a mild climate and goes above it in a cold one. Deeper water raises the volume figure and leaves the rule where it is.

How much does a pool cover help?

The Department of Energy's archived fact sheet says evaporation turns out to be 70 percent of the heat loss from a pool and that a cover can reduce a pool's energy consumption by 50 to 75 percent. This page does not credit a cover, so a covered pool heats faster than the page shows.

Can I use it for a heat pump, a spa or solar heating?

No. A heat pump is rated by COP, a spa heats on other tables, and solar collectors depend on sun and roof area. This page sizes a heater with an efficiency of 100 percent or less, such as a gas, propane or electric resistance unit.

Is there a limit on how many times I can run this?

No. This calculator runs in your browser with no daily limit and no signup.

Used on the same job

Size the input, then check the heat-up

The input from the area rule is a figure to compare with a maker's model, and the heat-up time shows what that model does to the water before losses. Take the rated input, the efficiency and any derate from the manufacturer's data. The gas line comes from the gas pipe sizing calculator, and the air for burning it from the combustion air calculator. You can also ask the assistant to go over a heater selection.