For estimation and planning use. The page works out a heating load, not a unit model, and it does not size the exhaust. The equipment manufacturer's data, a licensed contractor or engineer and the authority having jurisdiction decide the design. Local amendments to the model code differ.

Maintained by BuildSolver · Updated

Calculator · Makeup air

Makeup air unit size calculator

A hood throws air out of the building, and the makeup air unit puts the same air back in. IMC 508.1 asks for makeup air from all sources approximately equal to the exhaust, and in winter that air has to be heated. For 3,000 CFM from 0 °F outdoors to a 65 °F supply, the heat is 1.08 times 3,000 times 65.0, which is 210,600 BTU/h or 61.7 kW. With gas at 1,000 BTU per cubic foot and 100 percent efficiency that is 210.6 cubic feet per hour. The page also checks the supply against the room, because 2015 IMC 508.1.1, as the Washington State Building Code Council quotes it, limits the difference to 10 °F unless the HVAC system can carry the added load. For the exhaust side of the job, see the commercial kitchen hood CFM calculator. For a home range hood and the question of whether makeup air is required, use the range hood CFM calculator. Look up the outdoor temperature on the HVAC design temperatures page.

  1. Type the total exhaust airflow of the hoods and any other exhaust the unit replaces, and the share of it the unit covers.
  2. Type the winter design outdoor temperature, the supply temperature from the unit and the room temperature.
  3. The result shows the makeup airflow, the heat to the air, the burner input at the efficiency you entered, the gas flow, and whether the supply is within 10 °F of the room.

Winter heating of makeup air, US units. The form opens on 3,000 CFM from 0 °F to 65 °F in a 70 °F room at sea level, which is 210,600 BTU/h by hand. The efficiency opens on 100 percent, so the input equals the heat. Enter the data sheet figure for the real input.

The total of the hoods and any other exhaust the unit has to replace, in CFM. The page opens on 3,000 CFM.

100 when the unit replaces all of it. Use less where transfer air or conditioned supply air from the space makes up the rest.

Look up the design temperature for the job site with the HVAC design temperatures page. The page opens on 0 °F.

The temperature the unit delivers to the space. The page opens on 65 °F.

The air temperature of the conditioned space, for the check against the 10 °F limit of 2015 IMC 508.1.1.

Enter 0 for sea level. Thinner air carries less heat per CFM, so the heat falls with elevation.

Take it from the unit's data sheet. At the default of 100 percent the burner input equals the heat to the air.

1,000 for natural gas unless the utility gives another figure. It turns the input into cubic feet per hour. The range is that of natural gas, 700 to 1,200, so propane, which has a far higher value per cubic foot, is not covered by this page.

Example result for the default inputs

3,000 CFM of makeup air from 0 °F to 65 °F.

Makeup air

3,000 CFM

Heat to the air

210,600 BTU/h

Burner input

210,600 BTU/h

Calculation details
Exhaust airflow3,000 CFM
Share the unit covers100%
Makeup airflow3,000 CFM
Exhaust left to transfer air or another supply0 CFM
Outdoor temperature0 °F
Supply temperature65 °F
Temperature rise, supply minus outdoor+65.0 °F
Air density ratio at the elevation1.000
Heat to the air210,600 BTU/h
Heat to the air, in kW61.7 kW
Burner input at 100% efficiency210,600 BTU/h
Gas flow at 1,000 BTU per cubic foot210.6 cubic feet per hour
Room temperature70 °F
Supply minus room-5.0 °F
10 °F limit, 2015 IMC 508.1.1Within the limit
  • The heat uses the sensible factor 1.08 corrected by the air density ratio, 1.000 at 0 ft, with the CFM read at about 70 °F at this elevation. Humidity and the heat of the hood are not in it.
  • The efficiency is 100 percent, so the burner input equals the heat to the air. Enter the efficiency from the unit's data sheet for the real input.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the makeup air load is calculated

A makeup air unit replaces the air a hood throws out, so the airflow follows the exhaust and the heat follows the winter temperature rise. The page takes the exhaust CFM, the share the unit covers, and the rise from the design outdoor temperature to the supply temperature. It returns the heat the unit puts into the air, the burner input at the efficiency from the data sheet, the gas flow, and a check of the supply temperature against the room. For 3,000 CFM from 0 °F to 65 °F the heat is 210,600 BTU/h.

Makeup airflow
makeup CFM = exhaust CFM x share / 100IMC 508.1 asks for makeup air from all sources approximately equal to the exhaust of all exhaust systems in the building. At 100 percent the unit carries all 3,000 CFM. With 50 percent it carries 1,500 CFM and transfer air or another supply makes up the other 1,500 CFM.
Temperature rise
delta T = supply temperature - outdoor temperatureThe default rise is 65.0 °F, from 0 °F outdoors to 65 °F supply. A supply at or below the outdoor temperature needs no heat, and the page reads zero.
Heat to the air
Q = 1.08 x density ratio x CFM x delta T (BTU/h)This is the sensible heat equation with the textbook factor of 1.08, corrected for elevation. 3,000 CFM times 65.0 °F times 1.08 gives 210,600 BTU/h, which you can check with a calculator. The unit's heating capacity has to cover this at the design day.
Elevation
density ratio = (1 - 6.8754e-6 x elevation)^5.2559Air at 5,280 ft has a density ratio of 0.823, so the same airflow needs 173,402 BTU/h in place of 210,600 BTU/h. The ratio comes from the standard atmosphere in the ASHRAE Handbook, the one the other pages of this site use.
Heat in kW
kW = BTU/h / 3,412One kilowatt-hour is 3,412 BTU, so 210,600 BTU/h is 61.7 kW. The figure is the heat to the air. An electric coil would draw that power, and a gas unit gets there through the burner input below.
Burner input and gas flow
input = Q / (efficiency / 100) and cubic feet per hour = input / heating valueEfficiency comes from the unit's data sheet. At 100 percent the input equals the heat, 210,600 BTU/h, and at 85 percent it is 247,765 BTU/h. With gas at 1,000 BTU per cubic foot the default case burns 210.6 cubic feet per hour, and 247.8 at 85 percent.
Supply against the room
|supply - room| compared with 10 FAs the Washington State Building Code Council quotes it, 2015 IMC 508.1.1 limits the difference between makeup air and the air in the conditioned space to 10 °F, except where the added heating and cooling loads of the makeup air do not exceed the capacity of the HVAC system. A 65 °F supply in a 70 °F room is 5.0 °F off and passes. At a 55 °F supply the difference is 15.0 °F, which is over by 5.0 °F.

Worked examples

The default case is 3,000 CFM of makeup air from 0 °F to 65 °F at sea level, and you can reproduce it with a calculator. The rise is 65.0 °F, and 1.08 times 3,000 times 65.0 is 210,600 BTU/h. That is 61.7 kW of heat in the air. The room is at 70 °F, so the supply is 5.0 °F off, inside the 10 °F limit.

The table below gives the heat for 1,000 CFM at a 65 °F supply and sea level as the design temperature falls. Scale it by the airflow. 3,000 CFM at 0 °F is three times the 1,000 CFM figure of 70,200 BTU/h.

Heat for 1,000 CFM of makeup air at five outdoor temperatures
Outdoor temperatureRise to 65 °FHeat, BTU/hHeat, kW
-20 °F85.0 °F91,80026.9
0 °F65.0 °F70,20020.6
20 °F45.0 °F48,60014.2
40 °F25.0 °F27,0007.9
55 °F10.0 °F10,8003.2

Seven cases below run through the same function the form uses. Row two shows the input when the burner is 85 percent efficient, 247,765 BTU/h. In the third, the unit covers half the exhaust. A cold climate comes fourth, with 8,000 CFM at -20 °F and 734,400 BTU/h. At 5,280 ft the sixth case repeats the default, and thinner air takes 173,402 BTU/h. Last comes a 55 °F supply, over the room limit by 5.0 °F.

Makeup air results for seven example cases
CaseSetupResult
Default, 3,000 CFM at 0 °F3,000 CFM exhaust, 0 °F to 65 °F, 70 °F room, 100 percent efficiency3,000 CFM, 210,600 BTU/h to the air (61.7 kW), 210,600 BTU/h input, 210.6 cubic feet per hour of gas, within 10 °F of the room
Same case, 85 percent efficiency (chosen for the page)3,000 CFM exhaust, 0 °F to 65 °F, 70 °F room, 85 percent efficiency3,000 CFM, 210,600 BTU/h to the air (61.7 kW), 247,765 BTU/h input, 247.8 cubic feet per hour of gas, within 10 °F of the room
Unit covers half of the exhaust3,000 CFM exhaust, 50 percent covered, 0 °F to 65 °F, 70 °F room, 100 percent efficiency1,500 CFM, 105,300 BTU/h to the air (30.9 kW), 105,300 BTU/h input, 105.3 cubic feet per hour of gas, within 10 °F of the room
Cold climate, 8,000 CFM at -20 °F8,000 CFM exhaust, -20 °F to 65 °F, 70 °F room, 100 percent efficiency8,000 CFM, 734,400 BTU/h to the air (215.2 kW), 734,400 BTU/h input, 734.4 cubic feet per hour of gas, within 10 °F of the room
Mild design day, 30 °F outdoors3,000 CFM exhaust, 30 °F to 65 °F, 70 °F room, 100 percent efficiency3,000 CFM, 113,400 BTU/h to the air (33.2 kW), 113,400 BTU/h input, 113.4 cubic feet per hour of gas, within 10 °F of the room
Default case at 5,280 ft3,000 CFM exhaust, 0 °F to 65 °F, 70 °F room, 5,280 ft, 100 percent efficiency3,000 CFM, 173,402 BTU/h to the air (50.8 kW), 173,402 BTU/h input, 173.4 cubic feet per hour of gas, within 10 °F of the room
55 °F supply into a 70 °F room3,000 CFM exhaust, 0 °F to 55 °F, 70 °F room, 100 percent efficiency3,000 CFM, 178,200 BTU/h to the air (52.2 kW), 178,200 BTU/h input, 178.2 cubic feet per hour of gas, 5.0 °F past the 10 °F room limit

Standards and data sources

Limitations of this calculator

  • Winter heating only. Cooling or dehumidifying the makeup air in summer is outside this page, and so is the humidity of the outdoor air. A unit that also cools needs its own load work.
  • The 1.08 factor is for standard air at 70 °F. Air at 0 °F is denser, so a unit rated by CFM at the outdoor temperature moves about 15.2 percent more mass than standard air does. The page reads the CFM at about 70 °F at the site elevation and leaves that difference out.
  • This is not a model selection. The page returns a load, and the capacity, the temperature rise range and the turndown come from the manufacturer's data for the unit you pick. It does not tell a direct-fired unit from an indirect-fired one, and the efficiency is whatever the data sheet says.
  • No source for a typical burner efficiency was read for this page, so none is built in. The field takes 50 to 100 percent and opens on 100, which makes the input equal the heat to the air. Enter the data sheet figure for the real input.
  • The 10 °F limit is the text of 2015 IMC 508.1.1 as quoted by the Washington State Building Code Council. Other editions and local amendments differ, and Minnesota uses 50 °F at the diffuser. Check the code the job is permitted under.
  • The page does not size the hood exhaust. That figure comes from the hood type, the appliances and the listing of the hood, and the commercial kitchen hood CFM calculator covers that side.
  • A gas burner is rated for sea level, and manufacturers reduce the rated input above 2,000 ft. The page does not derate the input. Compare the burner input with the unit's derated rating at the site, as in the furnace altitude derate calculator.
  • Building pressure is not calculated. The code asks for makeup air approximately equal to the exhaust, and the balance of the space with doors, other exhaust fans and transfer paths is a field and design matter.
  • This is a planning estimate. A licensed contractor or engineer, the equipment manufacturer's instructions and the authority having jurisdiction decide the design, and the page makes no claim of code compliance.

Common makeup air sizing mistakes

  1. Heating to the room temperature. The heat follows the supply temperature, not the room temperature. Taking 70 °F as the target gives 226,800 BTU/h for the default case, 16,200 BTU/h more than the 210,600 BTU/h at a 65 °F supply. Pick the supply temperature on purpose, and check it against the room.
  2. Sizing on a mild day. A design temperature of 30 °F gives 113,400 BTU/h for 3,000 CFM, and the same hood at 0 °F needs 210,600 BTU/h. Choosing a unit for the mild day leaves it 97,200 BTU/h short on the cold one. Use the winter design temperature for the site.
  3. Reading the burner input as the heat to the air. The input is larger than the heat the air takes, by the losses of the burner. At 85 percent efficiency, 210,600 BTU/h of heat needs 247,765 BTU/h of input and 247.8 cubic feet per hour of gas. A gas line sized to the heat alone comes up short.
  4. Using the sea-level factor at a high site. At 5,280 ft the density ratio is 0.823. The sea-level 1.08 overstates the heat the air takes by 21.5 percent there, 210,600 BTU/h against 173,402 BTU/h. Burner input ratings fall with elevation as well, so look at the derated rating before the heat.
  5. Sizing the unit for all the exhaust when transfer air is available. The Washington interpretation recommends using transfer air and conditioned air from the kitchen before adding a dedicated unit. If the unit covers half the exhaust, 1,500 CFM, the heat drops from 210,600 BTU/h to 105,300 BTU/h. The code still asks for the total from all sources to be approximately equal to the exhaust.
  6. Counting a window or door as makeup air. A county plan-review worksheet on the 2012 IMC says windows and door openings shall not be used for the purpose of providing makeup air. Makeup air is mechanical or gravity means of sufficient capacity, interlocked with the exhaust so that it runs whenever the exhaust does.

Common questions about makeup air units

How do you size a makeup air unit?

Start from the exhaust CFM, take the share the unit covers, and work out the heat to lift the air from the winter design temperature to the supply temperature with 1.08 times CFM times the temperature rise. For 3,000 CFM from 0 °F to 65 °F that is 210,600 BTU/h, or 61.7 kW. Divide by the burner efficiency from the data sheet for the input.

How much heat does makeup air need per 1,000 CFM?

At a 65.0 °F rise, 1,000 CFM needs 1.08 times 1,000 times 65.0, which is 70,200 BTU/h or 20.6 kW. The figure scales with the rise. A colder design day or a warmer supply temperature raises it in proportion, and so does a larger airflow.

Does makeup air have to equal the exhaust?

IMC 508.1 says the makeup air supplied to the building from all sources shall be approximately equal to the exhaust air of all exhaust systems for the building. It does not require the unit alone to carry all of it. Transfer air and other conditioned supply count as sources, and the exhaust and makeup air systems are interlocked so that makeup air runs whenever the exhaust does.

What is the temperature limit on makeup air?

The 2015 IMC 508.1.1, as the Washington State Building Code Council quotes it, limits the temperature differential between makeup air and the air in the conditioned space to 10 °F. An exception applies where the added heating and cooling loads of the makeup air do not exceed the capacity of the HVAC system. Minnesota amends it to not less than 50 °F at the supply diffuser. The page checks the supply against the room and shows both warnings.

Can transfer air replace some of the makeup air unit?

Yes. The Washington interpretation recommends transfer air, and conditioned air serving the kitchen, before a dedicated unit is added, and calls for a dedicated unit where neither is available. Set the share the unit covers below 100 to see the heat for the part it carries. At 50 percent the default case is 1,500 CFM and 105,300 BTU/h.

How do I get kW for an electric makeup air heater?

Divide the heat to the air by 3,412, the BTU in one kilowatt-hour. The default case gives 210,600 BTU/h divided by 3,412, 61.7 kW. For an electric coil the kW is the heat to the air, and the supply voltage and phase come from the heater's data sheet.

Does elevation change the size of the heater?

It lowers the heat the air takes, because thin air carries less mass per CFM. At 5,280 ft the density ratio is 0.823 and the default case needs 173,402 BTU/h against 210,600 BTU/h at sea level. A gas burner is derated above about 2,000 ft by the manufacturer, so compare the input with the derated rating.

Which outdoor temperature should I use?

Use the winter design temperature for the job site, and the HVAC design temperatures page on this site looks it up by ZIP code. A milder figure undersizes the unit. At 30 °F the default case needs 113,400 BTU/h, and 210,600 BTU/h at 0 °F.

Is there a limit on how many times I can run this?

No. This calculator runs in your browser with no daily limit and no signup.

Used on the same job

Pick the supply temperature on purpose

The supply temperature sets both the heat and the room check. A lower supply saves heat and can fall outside the 10 °F limit of the 2015 IMC, and a warmer one costs more at the burner. Where a local code sets another figure, such as Minnesota's 50 °F at the diffuser, use that one. You can also ask the assistant to talk through a makeup air load for a kitchen.