Worksheet / Manual S · #BS-2026-MS-0001 · Example project
Design conditions
Manual J output - load from prior step
ACCA Manual S - Equipment selection (Zone 2A · 115% cap)
Equipment · ACCA Manual S
The latent check fails ✗, since the unit removes 7,920 BTU/h of moisture against a 10,500 BTU/h latent load, 2,580 short. No other size fits the window, so the calculator keeps this unit and points to a dedicated dehumidifier or a different evaporator coil for the gap.
+ Show your work− Hide work
Cooling bin set (95 °F rating), which also sizes a heat pump: 18 · 24 · 30 · 36 · 42 · 48 · 60 kBTU/h
Cooling derate @ 95 °F (AHRI A-test rating point) = 1.000 total · 1.000 sensible · equipment SHR = 0.78 (default with no AHRI sensible rating entered)
Heating derate @ 34 °F (interp between 35 °F / 0.90 and 17 °F / 0.72) = 0.890
3-ton total = 36,000 × 1.000 = 36,000 ≥ 35,500 ✓ · ≤ 35,500 × 1.15 = 40,825 ✓
3-ton sensible = 36,000 × 0.78 × 1.000 = 28,080 ≥ 25,000 ✓
3-ton latent = 36,000 - 28,080 = 7,920 < 10,500 ✗ (2,580 short)
3-ton heating @ 34 °F = 36,000 × 0.890 = 32,040 ≥ 24,000 ✓ · balance point 27 °F, below the design day, so no backup heat at design
Next size down (2.5-ton / 30,000): total 30,000 < 35,500 ✗ - undersized on total.
Next size up (3.5-ton / 42,000): 42,000 > 40,825 (115% cap) ✗ - oversized total for cooling-dominated zone 2A.
With the matched coil's own sensible rating entered, this unit clears both the sensible and the latent line only if its sensible capacity at design lands between 25,000 and 25,500 BTU/h.