For estimation and sales-phase use. Not a substitute for an ACCA-approved permit package or a licensed engineer's seal.

Maintained by BuildSolver · Updated

Calculator · Use case

Replacement AC sizing from your site-visit notes, no blueprint needed.

On a change-out, Manual J gives you the load for the house as it stands today, with its current windows, insulation and air sealing. Get a quick load estimate below, then describe the job in BuildSolver chat for a free whole-house Manual J in a couple of minutes. Room-by-room loads and Manual S selection are on the Pro and Team plans.

  1. Type the 5-digit ZIP code and the conditioned floor area in square feet.
  2. Pick the stories, air tightness, foundation and windows, add the year built if you know it, set the occupants, and tick the box if ducts run through an unconditioned attic.
  3. Optionally pick the tonnage of the unit being replaced. It is not used in the calculation.
  4. Press Calculate load. The cooling card shows the load in BTU/h and the size to the nearest half ton, and the difference from the existing unit if you picked one. The heating load is shown next to it.

Simplified whole-house estimate: ten inputs, instant result. The room-by-room Manual J with orientation, shading and measured R-values is part of the Pro plan.

Blank uses the ZIP's USGS elevation. Enter it when the house sits well above or below the town, or when the ZIP's elevation is not determined. Changing the ZIP clears it.

Example result for the default inputs

ZIP 85003 · Maricopa County, AZ · IECC zone 2B · elevation 1,085 ft · design 110°F DB / 71°F WB cooling, 32°F heating

Cooling load

22,224BTU/h

≈ 2 ton (nearest 0.5) · SHR 0.97

Heating load

16,814BTU/h

  • Furnace input bin 40,000 BTU/h at 90% AFUE
  • Heat pump 24,000 BTU/h at 47°F (20,880 at design temp)
Load breakdown by component
Cooling and heating load components, BTU/h
ComponentCoolingHeating
Transmission (walls, ceiling, floor, glass, doors)10,03813,342
Solar through glass8,649-
Infiltration1,0473,472
Internal gains (people, appliances)2,490-
Ducts in unconditioned attic00
  • These design temperatures are an approximate estimate for the IECC climate zone, not location-specific. For permit work use the design conditions for your exact location.
  • These are preliminary design conditions. For a permit load, take the design temperatures from ASHRAE Handbook - Fundamentals 2021, Chapter 14.
  • Recommended 2.0 tons rounds to 108% of computed load. Per ACCA Manual S, oversize >115% may impair dehumidification. Consider a 2-stage or variable-capacity unit.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF with a free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. Calculate once more and download the PDF. No card.

Or continue in the chat as a guest

Room-by-room Manual J and branded PDFs · Pro plan

How the replacement load is calculated.

The on-page calculator runs the whole-house Speed Sheet simplification of ACCA Manual J 8th Edition, the same deterministic code BuildSolver's assistant uses for a first sizing pass. Every component is computed separately and summed; the tonnage is the total rounded to the nearest half ton.

Cooling total
Q_cool = transmission + solar + infiltration + internal + ductIndoor design 75°F dry-bulb, 50% RH. Sensible and latent parts are reported separately; SHR = sensible ÷ total.
Transmission
Q = U × A × (CLTD multiplier × ΔT)Walls, ceiling, floor, glass and doors. U = 1/R from year-built × climate-zone defaults; wall area from a square footprint at 8 ft per story.
Solar through glass
Q = SHGC × A_glass × zone solar factor × 0.775Glass is 15% of floor area, split evenly across N/E/S/W. The 0.775 factor is the average of the four orientation factors in ACCA Manual J 8th Edition Table 3A. The page gives no shading credit.
Infiltration
Q_s = 1.08 × CFM × ΔT; Q_l = 4840 × CFM × ΔWCFM = ACH × house volume ÷ 60 with ACH by air-tightness class. Both terms are scaled by the ASHRAE standard-atmosphere air-density ratio at the elevation you enter, or, left blank, where Census and USGS data pin down the ZIP's elevation. Otherwise the result states that no altitude correction was applied.
Internal gains
Q = 230 × occupants + 1,200 (sensible) + 200 × occupants (latent)Per-person sensible and latent gains plus a baseline for lighting, refrigerator and plug loads.
Ducts in attic
cooling × 1.12 of sensible; heating × 1.20Applied only when ducts run through an unconditioned attic.
Heating total
Q_heat = Σ(U × A × ΔT) + slab edge + 1.08 × CFM × ΔT + ductΔT = 70°F indoor − 99% heating design dry-bulb. A slab's loss is figured at the edge as F2 × exposed perimeter × ΔT (Manual J Table 5C). Infiltration uses winter ACH by tightness class with the same elevation correction. The furnace input bin, the heat pump size at 47°F and its capacity at design temperature come from the same heating tool.

A worked example for a 1,200 sq ft Phoenix replacement.

1,200 sq ft single-story on slab · ZIP 85003, Phoenix, AZ · built 2008, average air tightness, three occupants, ducts inside conditioned space · replacing a 3-ton condensing unit. Existing ductwork stays.

ZIP 85003 · Maricopa County, AZ · IECC 2B · 110°F / 71°F design

22,224BTU/hr cooling · ≈ 2 ton load-based vs 3 ton installed

Heating 16,814 BTU/hr at 32°F design

For estimation only · ACCA MJ8 Speed Sheet · computed by the calculator above

Standards and data sources.

  • ACCA Manual J 8th Edition - residential load procedure. The page uses its whole-house Speed Sheet simplification, so expect the result to differ from a full room-by-room calculation.
  • IECC climate zone estimate - outdoor design conditions (1% cooling dry-bulb with a wet-bulb, 99% heating dry-bulb) as an approximate estimate for the ZIP's climate zone, not location-specific. Official city values are in ASHRAE Handbook - Fundamentals, Ch. 14.
  • IECC 2021 climate zones (PNNL county map) - ZIP → county → climate zone; the zone sets design temperatures, solar factor and envelope defaults.
  • ASHRAE Fundamentals Eq. 9.5 / 9.6 - sensible (1.08) and latent (4840) infiltration constants, with a standard-atmosphere density correction where Census and USGS data pin down the ZIP's elevation.
  • USGS 3D Elevation Program (3DEP) - ground elevation at the 2020 census centers of population of the tracts overlapping the ZIP (block groups for tracts larger than about 10 sq mi), averaged by population in the ZIP's land area, for the air-density correction.
  • ACCA Manual S - equipment sizing limits (cooling ≤115% of the Manual J load). The result warns once half-ton rounding lands above 107% of the load, before that limit is reached; equipment selection itself is a separate step.

Limitations of the quick estimate.

  • The load is a whole-house average, so it cannot size individual supply registers or find one hot bonus room.
  • Design temperatures are an approximate estimate for the IECC climate zone, not location-specific. For permit work use the design conditions for your exact location.
  • Insulation levels and, unless you pick one, window type come from year-built × climate-zone defaults. Real upgrades since construction change the answer a lot.
  • Glass is fixed at 15% of floor area, evenly split across orientations, with no shading credit. A west-facing wall of glass or deep overhangs are not modeled.
  • The residential scope is 100-20,000 sq ft and 1-3 stories. Light-commercial, multifamily and VAV systems need a different procedure.
  • Preliminary sales-phase estimate. Not ACCA-approved software output and not accepted for permit submission.
  • Elevation is the population-weighted average for the ZIP unless you enter the site's own. A house far up or down a slope in a hilly ZIP sits at a different elevation. BuildSolver treats the air-density correction as small below about 2,000 ft. Where the data cannot pin a ZIP's elevation down and you enter none, no altitude correction is applied and the result says so.

Common replacement sizing mistakes.

  1. Matching the old nameplate. The unit coming out was often picked with a square-foot rule. Replacing like-for-like repeats whatever oversizing it had.
  2. Ignoring upgrades since the last install. New windows, attic insulation or air sealing lower the load. Enter the house with those upgrades in place.
  3. Upsizing to fix one hot room. A room that never cools is usually a duct or airflow problem. A bigger condenser short-cycles the rest of the house and still starves that room.
  4. Skipping the heating side on a heat pump swap. For heat pumps, the heating load at design temperature often governs. Check the capacity at design temperature, not only the 47°F rating.
  5. Treating the load as the equipment size. The load is the target. Manual S then checks a specific model's capacity at your design conditions before you quote it.

The problem

Where replacement quotes go wrong.

  • Manufacturer sizing tools point you toward their own equipment. You end up picking a brand before the homeowner has agreed to a price.
  • A square-foot rule ignores envelope, glass and climate, so it often lands a replacement a size too big, with short cycles and high indoor humidity to follow.
  • A spreadsheet Manual J usually gets done back at the office. By then the first quote has already gone out on a rule of thumb.

Whole-house Manual J in chat

Describe the home; get a sized result with citations.

  1. Describe the home. Square footage, location, wall construction, window count, insulation level. The chat asks follow-up questions when it needs them.
  2. Run the load. BuildSolver calculates cooling and heating per ACCA Manual J 8th Edition with IECC climate-zone defaults for the ZIP, and the same inputs always return the same load.
  3. Get the result. Block load, sensible/latent split and the nominal tonnage the load points to. Client PDF export with your company branding is on the Pro and Team plans.

The output is a Manual J load number. Quote from the load across brands and pick the model after the homeowner signs. Manual S equipment selection (Pro and Team plans) runs separately when you need to match a specific coil.

BuildSolver vs manufacturer software

BuildSolver next to manufacturer sizing software.

BuildSolver takes the job description in chat on your phone and returns a Manual J load you can match to any brand's equipment.

FeatureBuildSolverManufacturer software
InputsConversationalVaries by program
Brand lockNoneThat brand's equipment
PlatformWeb, mobile-firstVaries by program
Output transparencyCites ACCA Manual J 8th EditionVaries by program

Common questions about replacement sizing.

How do I size a replacement AC without blueprints?

You don't need them. Describe the home from your site-visit notes and BuildSolver runs ACCA Manual J on them. Manual J needs dimensions, construction, glass and location, and a site visit gives you all of it.

What's the rule of thumb vs Manual J for replacement?

A square-foot rule can't see envelope, glass or climate, which is why it tends to put a replacement one size too big. BuildSolver runs a whole-house Manual J from the same site-visit notes you would use for a rule of thumb.

Can I size a heat pump replacement the same way?

Yes. BuildSolver runs both cooling and heating loads per ACCA Manual J 8th Edition. For cold-climate heat pumps, the heating load at design temperature often drives the selection. On dual-fuel jobs, the furnace carries the coldest hours. The chat returns both loads and a heat pump size with its capacity at design temperature; the balance point comes from Manual S selection on the Pro and Team plans.

Is this for residential only?

BuildSolver's quick tools cover homes from 100 to 20,000 sq ft and 1 to 3 stories. For light commercial, multifamily or VAV systems, use a commercial load procedure and have a mechanical engineer review the design.

Do I need to know the current tonnage?

No. The unit being removed was often sized by rule of thumb when it went in, so its tonnage says little about the load. Manual J figures the load for the building as it is now, and on a rule-of-thumb install that load often comes in below the installed tonnage. Size to the load, then let Manual S (Pro and Team plans) pick the unit.

What does the calculator on this page need from me?

A ZIP code, conditioned floor area, stories, approximate year built, air tightness, foundation type, window type if known, occupants, and whether ducts run through an unconditioned attic. The existing unit's tonnage is optional and only shown next to the result for comparison.

Is the on-page number enough to write a quote?

It is a preliminary whole-house estimate for the first conversation. Before committing to equipment, run the room-by-room Manual J and a Manual S check (both on the Pro and Team plans), and use ACCA-approved software where a permit requires it.

Try it on your next replacement quote.

You can start in chat without an account, and a free account keeps your history. Describe your next change-out in chat.

Calculate yours