Preliminary numbers for estimating and for checking a quote. Equipment instructions, the edition of the NEC your jurisdiction enforces and the local authority having jurisdiction come first. A licensed electrician sizes and installs the circuit.

Maintained by BuildSolver · Updated

Calculator · Electrical

Standard breaker and fuse size calculator

Breakers and fuses come in the ratings of NEC Table 240.6(A), 38 of them from 10 A to 6,000 A, plus four fuse-only sizes. A calculated number rarely lands on one, so the question is which way to round. Loads round up. A wire rounds down, or up one size under 240.4(B): 500 kcmil copper at 380 A may sit on 400 A, but three sets at 1,140 A may not sit on 1,200 A, because above 800 A there is no rounding up. This page gives the rating either way. For the wire itself, use the wire size calculator.

  1. Choose whether you are protecting a wire, sizing a breaker or fuse for a load, or looking up the standard ratings around a number, and pick a breaker or a fuse.
  2. For a wire, enter the ampacity of one conductor after correction and adjustment, the number of parallel sets, the size if it is 14 to 10 AWG, and whether the circuit feeds more than one receptacle. For a load, enter the continuous and noncontinuous amps.
  3. The result shows the standard ratings either side, the rule that picks one of them, and the largest or smallest standard breaker or fuse.

Standard ratings for fuses and inverse time breakers, NEC Table 240.6(A), 2023 edition. Motors, air conditioners, taps and transformer secondaries follow their own rules and are not worked here.

A wire is protected at its ampacity, so the rating rounds down, or up one size where 240.4(B) allows. A load rounds up.

Fuses add four ratings breakers do not have: 1, 3, 6 and 601 A.

From Table 310.16 in the column the terminals allow, after the ambient correction and the conductor-count adjustment. The wire ampacity derating calculator works it out.

1 for a single conductor. A feeder of two sets of 500 kcmil is 2.

The small sizes carry a breaker limit of their own in 240.4(D): 15, 20 and 30 A on 14, 12 and 10 AWG copper, and 10 A on 14 AWG copper-clad aluminum (2023).

A branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads may not use the next size up (240.4(B)(1)).

Example result for the default inputs

Breaker protecting a conductor of 380 A ampacity. NEC 240.4 and Table 240.6(A).

Ampacity

380 A

Largest standard breaker

400 A

Calculation details
Ampacity protected380 A, the ampacity of the conductor after ambient correction and conductor-count adjustment (310.15).
Standard ratings either side350 A below and 400 A above, from Table 240.6(A).
Largest breaker380 A is not a standard rating. The next size up, 400 A, is allowed (240.4(B)): the circuit does not feed more than one receptacle for cord-and-plug loads, and 400 A does not exceed 800 A.
Adjustable-trip breakersAn adjustable-trip breaker is rated at its highest long-time pickup setting (240.6(B)), or at the setting itself where the adjusting means has restricted access (240.6(C)).
  • Rounding up protects the conductor; it does not raise its ampacity. The load on the conductor still may not exceed 380 A, and a continuous load still needs the conductor and the breaker at 125 percent of it.
  • The next size up does not apply to feeder and branch-circuit taps (240.21) or to transformer secondary conductors (240.4(F) and 240.21(C)), where the conductor rules are written separately.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the rating is picked

Table 240.6(A) lists the standard ratings for fuses and inverse time circuit breakers. Which way to round depends on the job. A load rounds up: the device is no smaller than the load, with 125 percent of the continuous part. A wire is protected at its ampacity, so the rating rounds down, except that 240.4(B) lets it go up one size when the ampacity falls between standard ratings, the circuit is not a multi-receptacle branch circuit, and the device is 800 A or less.

Load
rating >= noncontinuous + 1.25 x continuous210.20(A) for a branch circuit and 215.3 for a feeder. A 40 A continuous load needs 50 A and a 50 A device. A 45 A continuous load needs 56.3 A, which rounds up to 60 A. 100 A continuous plus 100 A noncontinuous is 225 A, itself a standard rating.
100 percent rated assembly
rating >= noncontinuous + 1.00 x continuousThe exception in 210.20(A) and 215.3, only where the assembly, device included, is listed for continuous operation at 100 percent of its rating. The same 45 A continuous load then takes 45 A.
Wire, main rule
rating <= ampacity240.4: a conductor is protected at its ampacity after correction and adjustment. 500 kcmil copper at 75°C (167°F) is 380 A, and the largest standard rating at or below it is 350 A.
Next size up, 240.4(B)
next standard rating above the ampacity, if it is 800 A or lessAllowed when the ampacity is not itself a standard rating and the circuit does not supply more than one receptacle for cord-and-plug loads. 380 A takes 400 A; two sets, 760 A, take 800 A. 1/0 copper at 150 A is a standard rating already, so it stays at 150 A.
Over 800 A, 240.4(C)
rating <= ampacityAbove 800 A there is no rounding up. Three sets of 500 kcmil carry 1,140 A, under the 1,200 A device, so the largest rating is 1,000 A. Three sets of 600 kcmil, 1,260 A, carry 1,200 A.
Small conductors, 240.4(D)
rating <= 15, 20, 30 A on 14, 12, 10 AWG copperAnd 15 A on 12 AWG and 25 A on 10 AWG aluminum, unless 240.4(E) or (G) says otherwise. 12 AWG copper at 25 A of ampacity is still held to 20 A.

Eight wires through the same rules

The first four rows are Charles R. Miller's service and feeder examples in Electrical Contractor, and the 17.6 A row is his receptacle circuit: 12 AWG THWN at 38°C (100°F) with six current-carrying conductors. Each row shows the standard ratings either side of the ampacity and the rule that picks the breaker.

Ampacity, the standard ratings either side, the rule and the largest breaker for eight conductors
ConductorAmpacity, ABelow / above, ARuleLargest breaker, A
500 kcmil copper, 380 A (400 A service)380350 / 400next size up, 240.4(B)400
2 sets of 500 kcmil, 760 A760700 / 800next size up, 240.4(B)800
3 sets of 500 kcmil, 1,140 A1,1401,000 / 1,200over 800 A, 240.4(C)1,000
3 sets of 600 kcmil, 1,260 A1,2601,200 / 1,600over 800 A, 240.4(C)1,200
2 AWG copper at 75°C (167°F), 115 A115110 / 125next size up, 240.4(B)125
1/0 copper at 75°C (167°F), 150 A150150 / 175standard already150
12 AWG on 11 receptacles, 17.6 A17.615 / 20receptacles, 240.4(B)(1)15
12 AWG copper at 75°C (167°F), 25 A2525 / 30small wire, 240.4(D)20

Table 240.6(A), standard ampere ratings

These ratings apply to fuses and inverse time circuit breakers. The 2023 edition added 10 A for breakers; before it, the smallest standard breaker was 15 A. Fuses also come in 1, 3, 6 and 601 A, the last one the start of the Class L range.

Standard ampere ratings for fuses and inverse time circuit breakers
DeviceRatings, A
Fuses and breakers10 · 15 · 20 · 25 · 30 · 35 · 40 · 45 · 50 · 60 · 70 · 80 · 90 · 100 · 110 · 125 · 150 · 175 · 200 · 225 · 250 · 300 · 350 · 400 · 450 · 500 · 600 · 700 · 800 · 1,000 · 1,200 · 1,600 · 2,000 · 2,500 · 3,000 · 4,000 · 5,000 · 6,000
Fuses only1 · 3 · 6 · 601

Standards and data sources

Limitations of this calculator

  • This page gives preliminary numbers for estimating and for checking a quote. A licensed electrician sizes and installs the circuit under the permit and the inspection of the local authority having jurisdiction (AHJ). Nothing here approves an installation.
  • The NEC text was read as Mike Holt, Charles R. Miller and an exam-prep summary of the 2023 edition print it, not in NFPA's own viewer. Most of the worked examples use 2017 numbering. Check the edition and the local amendments your AHJ enforces; 10 A became a standard breaker rating only in 2023.
  • Equipment with its own rules is not worked: motors (Article 430), air conditioners and heat pumps (Article 440, the nameplate MOCP), and the other circuits 240.4(G) lists. Those can call for a breaker larger than the wire ampacity. Use the motor, AC breaker and AC wire calculators for them.
  • Taps (240.21), transformer secondary conductors (240.4(F)) and flexible cords and fixture wires (240.5) are not worked, and the next size up does not apply to taps or secondaries.
  • Adjustable-trip breakers are noted, not worked. A breaker is rated at its highest long-time pickup setting unless the adjusting means has restricted access (240.6(B) and (C)).
  • The ampacity is your entry. Which column applies (60, 75 or 90°C, that is 140, 167 or 194°F), the ambient correction and the conductor-count adjustment come from Table 310.16 and 310.15; the wire ampacity derating calculator works them.
  • Which loads are continuous, the interrupting rating (110.9), the series rating of a panel and selective coordination are outside this page.

Common mistakes with breaker and fuse sizes

  1. Rounding up on a receptacle circuit. 12 AWG THWN copper at 38°C (100°F) with six current-carrying conductors carries 17.6 A. On a branch circuit with more than one receptacle the next size up is not allowed, so the largest breaker is 15 A, too small for a 20 A circuit. The same wire on a single-outlet circuit could take 20 A. Miller's answer for the receptacle circuit is 10 AWG.
  2. Using the next size up above 800 A. Two sets of 500 kcmil go on 800 A, so three sets look right for 1,200 A. They carry 1,140 A, and above 800 A the ampacity must be at least the rating (240.4(C)), so the largest device is 1,000 A. Three sets of 600 kcmil (1,260 A) or four sets of 350 kcmil (1,240 A) carry 1,200 A.
  3. Rounding up from an ampacity that is already standard. 1/0 copper in the 75°C (167°F) column is 150 A, a standard rating, so it gets a 150 A breaker, not 175 A. Rounding up works only from an ampacity that falls between two standard ratings (240.4(B)(2)).
  4. Skipping 240.4(D) on small wire. 12 AWG copper is 25 A in the 75°C (167°F) column, and 25 A is a standard rating, but 240.4(D) holds it to 20 A. 10 AWG at 24 A after derating is not a 30 A wire either; it takes 25 A. Air conditioners and motors are the exceptions, through 240.4(G).
  5. Taking a load straight to the table. A 45 A continuous load is not a 45 A breaker. The breaker is at least 125 percent of it, 56.3 A, so 60 A. Only an assembly listed for 100 percent continuous operation takes 45 A, and most panel breakers are not listed that way.
  6. Looking for a 601 A breaker. 601 A is a fuse-only rating, the start of the Class L range. A wire of 600.5 A ampacity can take a 601 A fuse under the next size up, but a breaker on the same wire goes to 700 A. The fuse-only ratings are 1, 3, 6 and 601 A.

Common questions about standard breaker and fuse sizes

What are the standard breaker sizes?

NEC Table 240.6(A) lists 38 ratings for inverse time breakers and fuses, from 10 A to 6,000 A: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 A. Fuses add 1, 3, 6 and 601 A. The 10 A breaker rating is new in the 2023 edition.

What is the next size up rule?

240.4(B) lets a conductor be protected by the next standard rating above its ampacity when three conditions are met: the ampacity is not itself a standard rating, the circuit is not a branch circuit supplying more than one receptacle for cord-and-plug loads, and the device is 800 A or less. 500 kcmil copper at 380 A may go on 400 A. The rule protects the wire; it does not let the wire carry more than its ampacity.

What size breaker for a 115 amp wire?

125 A, under the next size up, if the circuit is not a multi-receptacle branch circuit. 2 AWG copper in the 75°C (167°F) column is 115 A, and 115 A is not a standard rating, so the next one, 125 A, is allowed. On a multi-receptacle branch circuit it drops to 110 A.

Is 10 amps a standard breaker size?

In the 2023 NEC, yes. Table 240.6(A) starts at 10 A for breakers and fuses, added with 10 A branch circuits on 14 AWG copper-clad aluminum. Under the 2020 and earlier editions the smallest standard breaker is 15 A and 10 A is a fuse-only rating. A 0.5 A load on this page takes a 10 A breaker or a 1 A fuse.

Can I use a nonstandard breaker or fuse rating?

Yes. 240.6(A) permits fuses and inverse time breakers with nonstandard ratings. The standard list matters for the rounding rules: the next size up in 240.4(B) and the 125 percent rule both land on a standard rating, and those are the sizes on the shelf.

How do I size a breaker for a continuous load?

Add the noncontinuous load to 125 percent of the continuous load and take the next standard rating (210.20(A), 215.3). A 40 A continuous load needs 50 A, a 50 A breaker. A continuous load is one that runs three hours or more. Only an assembly listed for 100 percent continuous operation may take the continuous load at 100 percent.

How is an adjustable-trip breaker rated?

At its highest long-time pickup setting (240.6(B)). Where the adjusting means is behind restricted access, such as a sealable cover or a locked door, it is rated at the setting (240.6(C)).

Does this page size motor or air conditioner breakers?

No. Motors (Article 430) and air conditioners and heat pumps (Article 440) have their own rules, and 240.4(G) sends their circuits there; the breaker can be larger than the wire ampacity. The motor circuit and AC breaker calculators work those.