For estimation and planning use. A licensed plumber or engineer and the authority having jurisdiction decide the pipe sizes and the installation. The limits are those of the model International Plumbing Code tables, and the table in the edition adopted by your jurisdiction, with its local amendments, governs. Not a substitute for an engineer's drainage design.

Maintained by BuildSolver · Updated

Calculator · Plumbing

Sanitary drain pipe size calculator

A sanitary drain is sized from the drainage fixture units, or DFU, of the fixtures that discharge into it. This page takes that load, reads the smallest listed diameter from Table 710.1(1) of the International Plumbing Code for a building drain by its slope, or from Table 710.1(2) for a horizontal fixture branch, and applies the 3 inch minimum for a drain that serves a water closet. 20 DFU at 1/4 inch per foot with a water closet on the drain takes 3 inch, which carries 42 DFU, and the same load with no water closet fits 2 inch. The page sizes horizontal drains only. Vent pipe is sized on its own table, and water supply pipe on water supply fixture units, which are a different count. For other pipe, see the hydronic pipe size calculator and the gas pipe sizing calculator.

  1. Take the DFU value of each fixture from Table 709.1 and add them for the pipe. The page opens on a two-bath house with a kitchen and a laundry, 20 DFU.
  2. Choose a building drain, which is read by slope, or a horizontal fixture branch, which has no slope. Say whether a water closet drains to the pipe, since a drain that serves one is 3 inch or larger.
  3. The page takes the smallest diameter whose limit is at or above the load. 20 DFU at 1/4 inch per foot with a water closet takes 3 inch, which carries 42 DFU.

Horizontal building drains of 2 to 10 inch at 1/8, 1/4 and 1/2 inch per foot, up to 4,200 DFU, and horizontal fixture branches of 1-1/2 to 8 inch, up to 1,400 DFU. Stacks are not sized. The form opens on a two-bath house of 20 DFU.

A building drain collects the whole house, and its horizontal branches collect parts of it. A horizontal fixture branch is the pipe from one fixture or one group of fixtures to the stack or the drain.

Drainage fixture units connected to the pipe, the sum of the Table 709.1 values of its fixtures. The page opens on a two-bath house with a kitchen and a laundry, 20 DFU.

The fall the drain will be laid at. A flatter slope carries fewer DFU. Table 710.1(1) has no entry for 2 or 2-1/2 inch pipe at 1/8 inch per foot.

A drain or branch that serves a water closet is 3 inch or larger on this page. Say yes if a water closet connects anywhere upstream of the pipe.

Example result for the default inputs

Building drain, 20 DFU at 1/4 inch per foot: 3 inch.

Pipe size

3 inch

Capacity at that size

42 DFU

Load on that size

47.6 %

Calculation details
PipeBuilding drain, building sewer or horizontal branch of the building drain, Table 710.1(1)
Load20 DFU at 1/4 inch per foot, a water closet on the drain
Pipe size3 inch, the smallest listed size whose limit of 42 DFU is at or above 20 DFU
Same load at each slope1/8 inch per foot: 3 inch (36 DFU); 1/4 inch per foot: 3 inch (42 DFU); 1/2 inch per foot: 3 inch (50 DFU)
  • The load is the sum of the DFU values of Table 709.1 for the fixtures on the pipe, not a count of fixtures. This page takes that sum as typed and does not check it.
  • Table 704.1 sets the minimum slope of a drain, 1/4 inch per foot for 2-1/2 inch and smaller pipe, 1/8 inch per foot for 3 to 6 inch, 1/16 inch per foot for 8 inch and larger. Enter the slope the pipe will really be laid at.
  • A water closet on the drain makes 3 inch the minimum under the footnote of Table 710.1(1). The load alone would fit a smaller pipe.
  • Stacks, vents, sumps and ejectors, storm drainage and the water supply pipe are not sized here. The supply side counts water supply fixture units, which are not drainage fixture units.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the drain pipe size is read

This page reads a pipe size from a table and does not derive one. The load is the sum of the drainage fixture units of the fixtures on the pipe, from Table 709.1 of the International Plumbing Code. A building drain, a building sewer or a horizontal branch of the building drain is read from Table 710.1(1) by slope, and a horizontal fixture branch from Table 710.1(2). The size is the smallest listed diameter whose limit is at or above the load. Building drains of 2 to 10 inch and fixture branches of 1-1/2 to 8 inch are covered, and stacks, vents and the water supply are not.

Load in DFU
load = sum of (fixtures x DFU per fixture), Table 709.1Each fixture carries a drainage fixture unit value, and the pipe carries their sum. A private water closet of 1.6 gpf is 3 DFU, a lavatory 1 and a bathtub 2. The opening example, two baths with a kitchen sink, a dishwasher, a clothes washer and a laundry tray, adds up to 20 DFU.
Building drain, sewer or branch of the drain
size = smallest diameter in Table 710.1(1) whose limit at the slope is at or above the loadThe table lists a limit for each diameter at 1/8, 1/4 and 1/2 inch per foot. A 3 inch drain carries 36, 42 and 50 DFU at those slopes, and a 4 inch drain carries 180, 216 and 250. 20 DFU at 1/4 inch per foot is 47.6 percent of the 42 DFU of a 3 inch drain.
Water closet minimum
size = at least 3 inch when a water closet drains to the pipeA footnote of Table 710.1(1) sets 3 inch as the smallest building drain that serves a water closet. The same 20 DFU with no water closet fits a 2 inch drain, whose limit is 21 DFU at 1/4 inch per foot.
Horizontal fixture branch
size = smallest diameter in Table 710.1(2), horizontal fixture branch column, at or above the loadTable 710.1(2) has no slope. A 3 inch branch carries 20 DFU and a 4 inch branch 160. 24 DFU on a branch takes 4 inch, while the same 24 DFU on a building drain at 1/4 inch per foot with no water closet takes 2-1/2 inch.
Slope
the slope is an input, and the minimum slope depends on the diameterThe sources read print the minimum slope of Table 704.1 as 1/4 inch per foot for 2-1/2 inch and smaller pipe, 1/8 inch per foot for 3 to 6 inch, 1/16 inch per foot for 8 inch and larger. Nothing here checks the slope against the diameter, and it has no entry for 1/16 inch per foot. A flatter slope lowers the limit, so 200 DFU takes 4 inch at 1/4 inch per foot and 5 inch at 1/8.

Worked examples from the tables

The default case is a house with two baths, a kitchen sink, a dishwasher, a clothes washer and a laundry tray. Using the Table 709.1 values below it adds up to 20 DFU. At 1/4 inch per foot with a water closet on the drain it takes 3 inch, which is 47.6 percent of the 42 DFU limit. With no water closet the same load takes 2 inch, and at 1/8 inch per foot it takes 3 inch, because Table 710.1(1) lists no capacity for 2 or 2-1/2 inch pipe at that slope.

Fixtures behind the default load, with the DFU values of Table 709.1 for private use.

Fixtures and drainage fixture units of the default house
FixtureCountDFU eachDFU
Water closet, 1.6 gpf236
Lavatory or bidet212
Bathtub, with or without shower head224
Kitchen sink, domestic122
Dishwasher, domestic122
Clothes washer, residential122
Laundry tray or utility sink122

Table 710.1(1), the largest DFU on a building drain, as this page reads it.

Building drain capacity in drainage fixture units by diameter and slope
Diameter, inch1/8 per foot1/4 per foot1/2 per foot
2none listed2126
2-1/2none listed2431
3364250
4180216250
5390480575
67008401,000
81,6001,9202,300
102,9003,5004,200

Table 710.1(2), the largest DFU on a horizontal fixture branch.

Horizontal fixture branch capacity in drainage fixture units by diameter
Diameter, inchDFU
1-1/23
26
2-1/212
320
4160
5360
6620
81,400

Eight cases below run through the same functions the form uses. 200 DFU takes 4 inch at 1/4 inch per foot and 5 inch at 1/8. 24 DFU takes 2-1/2 inch on a building drain with no water closet and 4 inch on a horizontal fixture branch, since the two tables differ.

Drain pipe size for eight example loads
CaseSetupResult
Two-bath house, water closet on the drain20 DFU, building drain at 1/4 inch per foot, water closet on it3 inch, limit 42 DFU, 47.6% loaded
Same load, laundry drain with no water closet20 DFU, building drain at 1/4 inch per foot, no water closet2 inch, limit 21 DFU, 95.2% loaded
Same load with no water closet, at 1/8 inch per foot20 DFU, building drain at 1/8 inch per foot, no water closet3 inch, limit 36 DFU, 55.6% loaded
Small commercial building, 100 DFU100 DFU, building drain at 1/4 inch per foot, water closet on it4 inch, limit 216 DFU, 46.3% loaded
200 DFU at 1/4 inch per foot200 DFU, building drain at 1/4 inch per foot, water closet on it4 inch, limit 216 DFU, 92.6% loaded
200 DFU at 1/8 inch per foot200 DFU, building drain at 1/8 inch per foot, water closet on it5 inch, limit 390 DFU, 51.3% loaded
1,000 DFU at 1/2 inch per foot, the printed limit of 6 inch1,000 DFU, building drain at 1/2 inch per foot, water closet on it6 inch, limit 1,000 DFU, 100.0% loaded
24 DFU on a horizontal fixture branch24 DFU, horizontal fixture branch4 inch, limit 160 DFU, 15.0% loaded

Standards and data sources

Limitations of this calculator

  • Horizontal drains only. Stacks are not sized, although the stack columns of Table 710.1(2) exist, because a stack is sized by its branch intervals and its offsets and the page takes neither.
  • Building drains from 2 to 10 inch at 1/8, 1/4 and 1/2 inch per foot, and fixture branches from 1-1/2 to 8 inch. The 1/16 inch per foot column, the 1-1/4 and 1-1/2 inch building drain rows and the 12 and 15 inch rows are left out because the sources read did not confirm them across each other. A load above 4,200 DFU on a building drain, or 1,400 DFU on a branch, is refused.
  • The tables were read in the Maryland adoption of the 2024 IPC and in two study guides that reproduce the 2021 tables. ICC's own site returned an error to the reader, so the model code text itself was not read, and the 2018 edition was not compared cell by cell. Check the table in the edition your jurisdiction has adopted.
  • You type the load in. The page does not look up fixtures, apply the public-use values of Table 709.1, or add a continuous or intermittent flow from a pump or an indirect waste. A fixture with a larger trap carries a larger DFU value.
  • The 3 inch water closet minimum comes from the footnote of the building drain table. No source read prints it for the fixture branch table, so the page applies it there as the cautious reading, and it does not check the outlet of the fixture or its trap.
  • The slope is not checked against the diameter. Table 704.1 sets minimum slopes, and the page does not apply them, but it never names a 2 or 2-1/2 inch pipe at 1/8 inch per foot.
  • Venting, the length of the drain and the number of fittings, backwater valves, the size of a building sewer outside the building, sump and ejector discharge, storm drainage and grease interceptors are not covered. Local amendments change these tables in some jurisdictions, and the Universal Plumbing Code uses its own table.
  • This is a planning estimate, not a design drawing. A licensed plumber or engineer and the authority having jurisdiction decide the pipe sizes and the installation.

Common drain sizing mistakes

  1. Counting fixtures and not DFU. A water closet is 3 DFU, a lavatory 1 and a bathtub 2, so those three fixtures add to 6 DFU counted one by one, and not 3 fixtures. Table 709.1 also lists a bathroom group as a single line at a lower value, which this page does not use. The 20 DFU of the opening house comes from 10 fixtures.
  2. Taking 2 inch pipe at 1/8 inch per foot. Table 710.1(1) has a dash for 2 and 2-1/2 inch at 1/8 inch per foot. 20 DFU with no water closet takes 2 inch at 1/4 inch per foot, and 3 inch at 1/8, where the limit is 36 DFU.
  3. Forgetting the water closet minimum. 20 DFU fits a 2 inch drain at 1/4 inch per foot, whose limit is 21 DFU, but a drain that serves a water closet is 3 inch or larger. The same load takes 3 inch with a water closet on it.
  4. Reading a building drain from the branch table. Table 710.1(2) is for horizontal fixture branches and has no slope. 24 DFU on a branch takes 4 inch, with a limit of 160 DFU, and on a building drain at 1/4 inch per foot with no water closet it takes 2-1/2 inch, with a limit of 24 DFU. The wrong table moves the answer from 2-1/2 to 4 inch.
  5. Ignoring the slope. A flatter drain carries less. 200 DFU takes 4 inch at 1/4 inch per foot, where the limit is 216 DFU, and 5 inch at 1/8, where the limit of a 4 inch drain is 180 DFU.
  6. Using drainage units for the vent or the supply. A vent is sized on its own table and the water supply pipe is sized on water supply fixture units, which are a different count from drainage fixture units. Any DFU total from this page answers the question of the drain only.

Common questions about drain pipe size

How do I size a sanitary drain pipe?

Add the drainage fixture units of the fixtures on the pipe, then take the smallest diameter in Table 710.1(1) whose limit at your slope is at or above that total. 20 DFU at 1/4 inch per foot with a water closet on the drain takes 3 inch, which carries 42 DFU. A horizontal fixture branch is read from Table 710.1(2) instead.

What is a drainage fixture unit?

Drainage fixture units, or DFU, are the values Table 709.1 gives a fixture for the load it puts on a drain. A water closet of 1.6 gpf is 3 DFU, a lavatory 1, a bathtub 2, and a drinking fountain is 0.5. The pipe carries the sum of its fixtures.

What size drain does a toilet need?

A building drain that serves a water closet is 3 inch or larger, by the footnote of Table 710.1(1). At 1/8, 1/4 or 1/2 inch per foot a 3 inch drain carries 36, 42 or 50 DFU.

How many DFU can a 4 inch drain carry?

180 DFU at 1/8 inch per foot, 216 at 1/4 and 250 at 1/2, from Table 710.1(1). As a horizontal fixture branch, a 4 inch pipe carries 160 DFU in Table 710.1(2).

What slope should a drain have?

Table 704.1 gives the minimum, which the sources read print as 1/4 inch per foot for 2-1/2 inch and smaller pipe, 1/8 inch per foot for 3 to 6 inch, 1/16 inch per foot for 8 inch and larger. The capacity at 1/8, 1/4 and 1/2 inch per foot is listed in Table 710.1(1), and a steeper slope carries more. 200 DFU takes 4 inch at 1/4 and 5 inch at 1/8.

What is the difference between Table 710.1(1) and Table 710.1(2)?

Table 710.1(1) sizes building drains, building sewers and the horizontal branches of the building drain by slope. Horizontal fixture branches and stacks are sized by Table 710.1(2), which has no slope. This page uses the first for a drain and the horizontal branch column of the second for a fixture branch.

Is this the same as a vent pipe or water pipe calculator?

No. This page sizes the pipe that carries waste out of the building. A vent is sized from its own table and the supply pipe from water supply fixture units, so a DFU total does not carry over to either.

Does the page size stacks?

No. The page covers horizontal drains only. A stack is sized by its branch intervals and its offsets, and the page takes neither.

Is there a limit on how many times I can run this?

No. This calculator runs in your browser with no daily limit and no signup.

Used on the same job

Count the fixture units, then read the table

The load comes first, as the sum of the Table 709.1 values of the fixtures on the pipe, and the table then gives the smallest diameter that carries it. Vent pipe, stacks and the water supply are sized separately. For the hot water side of the same fixtures, see the water heater size calculator, and for the condensate line of an air conditioner, the condensate drain calculator. You can also ask the assistant to go over a drain layout. Slope matters. A flatter run carries fewer fixture units in the same pipe.