For preliminary sizing and planning use. The tank size, its location and distances, the regulator and the piping are set by NFPA 58, NFPA 54, the authority having jurisdiction and your propane supplier. Not a substitute for a supplier's load survey or a licensed propane contractor's design.

Maintained by BuildSolver · Updated

Calculator · Propane tank

Propane tank size calculator

A propane tank has to answer two questions, how long the fuel lasts and whether the tank can turn enough liquid into gas on the coldest morning. The appliance inputs and the hours they run give the gallons a day, and the water capacity of the tank, filled to 80 percent, gives the days between fills. The Propane Education & Research Council's pocket guide supplies the 91,500 BTU per gallon, the typical appliance inputs and a table of vaporization rates by tank size and temperature. A typical single-family set built from its input ratings is 250,000 BTU/h, and with the default hours it burns 10.93 gallons a day, 327.9 gallons in 30 days. A 500 gallon tank holds 400 gallons and lasts 29.3 days with 20 percent kept in reserve. The same set needs a tank that gives 250,000 BTU/h or more at the winter low, and a 500 gallon tank gives 300,100 BTU/h at 0°F. To size the gas line, use the gas pipe sizing calculator. To size the furnace that burns most of the fuel, use the furnace size calculator.

  1. Take the input in BTU/h from each nameplate and enter the hours a day it runs at full input. PERC's Table 3A gives about 100,000 BTU/h for a single-family furnace when the nameplate is not at hand.
  2. Pick a standard tank and the share of the usable volume you want left at refill. A tank holds 80 percent of its water capacity, so a 500 gallon tank holds 400 gallons of propane.
  3. The result gives the gallons a day and a month and the days between fills. Pick the lowest outdoor temperature and check that the tank's vaporization capacity is above the connected load.

Aboveground ASME tanks of 120 to 2,000 gallons of water capacity, filled to 80 percent, on propane. The form opens on a typical single-family appliance set built from PERC Table 3A input ratings, 250,000 BTU/h, with the hours as an illustration and a 500 gallon tank at 0°F.

The input on the nameplate of the furnace or boiler, not its output. PERC Table 3A gives about 100,000 BTU/h for a single-family warm air furnace and 60,000 BTU/h for a multifamily unit. A spec sheet that prints MBH is 1,000 BTU/h per MBH.

The hours that would burn the same fuel at full input on a cold day. A furnace that runs a third of a 24 hour day at full input is 8 hours. The guide gives no duty cycle, so this number is yours.

PERC Table 3A lists 35,000 BTU/h for a 30 to 40 gallon storage heater, 50,000 for a 50 gallon one and 142,800, 285,000 and 428,400 for a tankless unit at 2, 4 and 6 GPM.

A storage heater for a household often fires a couple of hours a day. A tankless unit fires only while hot water runs.

PERC Table 3A lists 65,000 BTU/h for a freestanding range, 25,000 for a built-in oven and 40,000 for a built-in cooktop.

The hours that burn the same fuel at the input entered above. If burners and an oven run for different times, weight each by its input: the sum of (BTU/h x hours) divided by the sum of the BTU/h. A 25,000 BTU/h oven for 1 hour and a 40,000 BTU/h cooktop for 0.5 hour, entered as 65,000 BTU/h, is (25,000 x 1 + 40,000 x 0.5) / 65,000 = 0.7 hour.

Add a dryer (35,000 BTU/h in PERC Table 3A), a gas fireplace (40,000 direct vent, 80,000 for a gas log), a barbecue (40,000) or a generator from its nameplate. The guide advises allowing for appliances that may be installed later.

The hours at the total input entered above, weighted by input: the sum of (BTU/h x hours) divided by the sum of the BTU/h. A 35,000 BTU/h dryer for 1 hour and a 40,000 BTU/h fireplace for 4 hours, entered as 75,000 BTU/h, is (35,000 x 1 + 40,000 x 4) / 75,000 = 2.6 hours. Adding the hours (5) would overstate the use.

The nominal water capacity. The tank is filled to 80 percent of it. Dimensions vary by maker. The 320 gallon size in the PERC list is left out because other sources print 325 and 330.

The share of the usable volume you want left when the truck arrives. It is a percent of the usable volume, not of the water capacity that a tank gauge reads, so a reserve of 20 percent shows as 16 percent on the gauge. This is a choice, not a code number. 0 runs the tank to empty, which no supplier recommends.

Pick the row at or below the coldest 24 hour average that the site sees. The table steps every 10°F and the page does not interpolate, so a colder row is the safe choice. Among the sizes offered, the source table has columns for 250, 500 and 1,000 gallons only (it also has a 150 gallon column, which the form omits).

PERC says continuous loading is not common on domestic installations and multiplies the table rates by 0.25 when it applies.

Example result for the default inputs

250,000 BTU/h connected, 1,000,000 BTU a day, 500 gallon tank.

Propane per day

10.93 gal

Propane per 30 days

327.9 gal

Usable in the tank

400.00 gal

Between fills

29.3 days

Calculation details
Space heating100,000 BTU/h for 8 h a day, 800,000 BTU
Water heater50,000 BTU/h for 2 h a day, 100,000 BTU
Range and oven65,000 BTU/h for 1 h a day, 65,000 BTU
Dryer and other appliances35,000 BTU/h for 1 h a day, 35,000 BTU
Connected load250,000 BTU/h
Energy per day1,000,000 BTU
Connected load as gas100.5 SCFH at 2,488 BTU per cubic foot
Tank500 gallon water capacity, 400.00 gal at 80 percent
Reserve at refill20 percent of the usable volume, 80.00 gal
Propane used between fills320.00 gal
Vaporization at the design low300,100 BTU/h at 0°F, covers the load
Margin against the connected load50,100 BTU/h
120 gallon tank96.00 gal usable, 7.0 days between fills, vaporization not checked or not tabulated
250 gallon tank200.00 gal usable, 14.6 days between fills, vaporization 180,600 BTU/h, short for the load
500 gallon tank400.00 gal usable, 29.3 days between fills, vaporization 300,100 BTU/h, covers the load
1,000 gallon tank800.00 gal usable, 58.6 days between fills, vaporization 534,500 BTU/h, covers the load
2,000 gallon tank1,600.00 gal usable, 117.1 days between fills, vaporization not checked or not tabulated
  • Preliminary sizing for a quote or a first talk with a propane supplier. The tank size, its distance from buildings and property lines, the regulator and the piping are set by NFPA 58 and NFPA 54, the authority having jurisdiction and the supplier.
  • Suppliers fill a tank to 80 percent of its water capacity, so a 500 gallon tank holds 400.00 gallons of propane when it is full. The filler's gauge and NFPA 58 decide the limit on the day.
  • The hours per day are your assumption. No open source gives a duty cycle for a furnace or a water heater, so enter the hours at full input on a cold day, and the gallons follow in direct proportion.
  • The PERC table gives 300,100 BTU/h for a 500 gallon tank at 0°F, against a connected load of 250,000 BTU/h. It assumes a tank that is half full, 70 percent relative humidity, intermittent loading and an aboveground tank.
  • The table assumes a half full tank, and a tank at the refill reserve you entered is down to 16 percent of the water capacity, which is always below half. A tank with less liquid vaporizes less, so the margin shrinks late in each interval.

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

How the propane use and the tank are calculated

This page turns the input of each gas appliance and the hours it runs into the gallons of propane burned in a day, then sets that against the usable volume of a standard tank to give the days between fills. It also checks the connected load against the vaporization capacity of the tank at the lowest winter temperature. Propane's heating value, the appliance load table and the vaporization table come from the Propane Education & Research Council's Technical Pocket Guide. Suppliers quote the 80 percent fill. Tank placement, the regulator and the pipe are outside the page, and the gas pipe sizing calculator covers the pipe.

Energy content
91,500 BTU per gallon of propanePERC Table 1C gives 91,500 BTU per gallon, and Table 1A prints 91,502 with 4.2 lb per gallon at 60°F. The default day burns 1,000,000 BTU, which is 10.93 gallons.
Daily use
gallons per day = sum of (input BTU/h x hours per day) / 91,500The default set is a typical single-family set built from the input ratings of Table 3A, a 100,000 BTU/h furnace for 8 hours, a 50,000 BTU/h water heater for 2 hours, a 65,000 BTU/h range for 1 hour and a 35,000 BTU/h dryer for 1 hour. Only the input ratings come from the guide. The choice of appliances and the hours are this page's illustration.
Monthly use
gallons per 30 days = gallons per day x 30The default comes to 327.9 gallons in 30 days. That figure is only as good as the hours, so a cold month needs the hours of a cold month.
Usable volume
usable gallons = water capacity x 0.8Ferrellgas and AmeriGas both multiply the water capacity by 0.8. That gives 96, 200, 400 and 800 gallons for the 120, 250, 500 and 1,000 gallon tanks.
Days between fills
days = usable gallons x (1 - reserve) / gallons per dayA 500 gallon tank holds 400 gallons. With 20 percent kept in reserve, 320 gallons are used between fills, and at 10.93 gallons a day that lasts 29.3 days.
Gas flow
SCFH = connected load BTU/h / 2,488PERC divides the BTU/h load by 2,488 to get standard cubic feet per hour. The default 250,000 BTU/h is 100.5 SCFH at the full connected load. Carry the connected load of 250,000 BTU/h to the gas pipe sizing calculator, which takes the load in BTU/h, not the SCFH.
Vaporization
capacity = PERC Table 5 value for the tank and the design low, times 0.25 for continuous loadingLiquid propane has to boil off fast enough to feed the appliances. A 500 gallon tank at 0°F gives 300,100 BTU/h in Table 5, which covers the 250,000 BTU/h load with 50,100 BTU/h to spare. The table assumes a tank that is half full.

Worked examples

The default case is a typical single-family set built from the input ratings of Table 3A in the guide, a 100,000 BTU/h furnace, a 50,000 BTU/h water heater, a 65,000 BTU/h range and a 35,000 BTU/h dryer. That is 250,000 BTU/h connected, or 100.5 SCFH when divided by 2,488. With 8, 2, 1 and 1 hours at full input, the day burns 1,000,000 BTU, which is 10.93 gallons at 91,500 BTU per gallon. These input numbers come from the guide. Our choice of appliances and the hours are this page's illustration, and the guide gives no duty cycle.

The table below is Table 5 of the guide, the maximum intermittent withdrawal in BTU/h without tank frosting, for the lowest outdoor temperature averaged over 24 hours. It assumes a half-full aboveground tank at 70 percent relative humidity. For 500 gallons at 0°F it reads 300,100 BTU/h, 50,100 BTU/h above the default load, and 180,600 BTU/h for a 250 gallon tank, which falls 69,400 BTU/h short.

PERC Table 5, maximum intermittent withdrawal rate in BTU per hour by tank size and lowest outdoor temperature
Lowest 24 hour average150 gal250 gal500 gal1,000 gal
40°F214,900288,100478,800852,800
30°F187,000251,800418,600745,600
20°F161,800216,800360,400641,900
10°F148,000198,400329,700587,200
0°F134,700180,600300,100534,500
-10°F132,400177,400294,800525,400
-20°F108,800145,800242,300431,600
-30°F107,100143,500238,600425,000

Eight cases below run through the same function the form uses. Four of them keep the default load and change the tank, the winter low or the loading. At -20°F the 500 gallon tank gives 242,300 BTU/h, 7,700 BTU/h under the load, and under continuous loading it gives 75,025 BTU/h. A 1,000 gallon tank lasts 58.6 days and a 250 gallon tank 14.6 days.

Propane use, days between fills and vaporization check for eight example installations
CaseSetupResult
Typical single-family set, 500 gal250,000 BTU/h connected, 1,000,000 BTU a day, 500 gallon tank, 0°F low10.93 gal a day, 29.3 days between fills, 300,100 BTU/h covers 250,000 BTU/h
Same load, 250 gal tank250,000 BTU/h connected, 1,000,000 BTU a day, 250 gallon tank, 0°F low10.93 gal a day, 14.6 days between fills, 180,600 BTU/h is short of 250,000 BTU/h
Same load, 1,000 gal tank250,000 BTU/h connected, 1,000,000 BTU a day, 1,000 gallon tank, 0°F low10.93 gal a day, 58.6 days between fills, 534,500 BTU/h covers 250,000 BTU/h
Same load, 500 gal at -20°F250,000 BTU/h connected, 1,000,000 BTU a day, 500 gallon tank, -20°F low10.93 gal a day, 29.3 days between fills, 242,300 BTU/h is short of 250,000 BTU/h
Same load, continuous loading250,000 BTU/h connected, 1,000,000 BTU a day, 500 gallon tank, 0°F low, continuous loading10.93 gal a day, 29.3 days between fills, 75,025 BTU/h is short of 250,000 BTU/h
Apartment unit, 250 gal160,000 BTU/h connected, 477,500 BTU a day, 250 gallon tank, 20°F low5.22 gal a day, 30.7 days between fills, 216,800 BTU/h covers 160,000 BTU/h
Tankless heater added, 1,000 gal485,000 BTU/h connected, 1,042,500 BTU a day, 1,000 gallon tank, 0°F low11.39 gal a day, 56.2 days between fills, 534,500 BTU/h covers 485,000 BTU/h
Cabin, water heater and range, 120 gal100,000 BTU/h connected, 135,000 BTU a day, 120 gallon tank, no vaporization check1.48 gal a day, 52.1 days between fills, vaporization not checked

Standards and data sources

Limitations of this calculator

  • The hours a day are yours. No open source gives a duty cycle for a furnace or a water heater, so the gallons per day are only as good as the hours entered. The default hours (8, 2, 1 and 1) are an illustration, and a real quote uses the heat loss, the climate and the household.
  • The vaporization check comes from one table. PERC Table 5 covers 150, 250, 500 and 1,000 gallon aboveground tanks, one-half full, at 70 percent relative humidity, with a 24 hour average low. The form offers only the 250, 500 and 1,000 gallon columns, and the 120 and 2,000 gallon tanks have no column, so the page gives no figure for them. An underground tank holds a steadier temperature, and its rate is not in the table.
  • Temperatures step every 10°F and the page never interpolates. Pick the row at or below the coldest 24 hour average at the site. A short colder snap is not the same as a 24 hour average, and the supplier knows the local record.
  • The table assumes a tank one-half full. With a reserve of up to 60 percent of the usable volume, the tank holds at most 48 percent of its water capacity at refill, which is always below that half, and the page says so whenever it checks vaporization. A tank with less liquid has less wetted surface and vaporizes less. The table is a rule of thumb, as the guide itself says, and the maker's rating of the tank takes precedence.
  • The 80 percent is the fill that suppliers quote for the water capacity. NFPA 58 and the filler's gauge decide the limit on the day, and the table of maximum filling density in the code depends on the container and the temperature. The page uses 0.8 for every size.
  • One tank. Two tanks manifolded together add their volumes, but the page does not model their combined vaporization or their balance. Portable cylinders of 20 pounds and 100 pounds are not covered, since their fill is by weight and their vaporization is a separate question.
  • Tank placement is not covered. The distance from buildings, property lines, ignition sources and openings, the burial depth of an underground tank, the regulator and the piping all come from NFPA 58 and NFPA 54 and from the authority having jurisdiction.
  • Price, delivery minimums and contract terms are outside the page, and so is a propane supplier's own tank rental or purchase rule. Ask the supplier.
  • This is a planning estimate, not a design drawing. A licensed propane contractor, the manufacturer's data and the authority having jurisdiction decide the installation.

Common propane tank sizing mistakes

  1. Counting the water capacity as propane. A 500 gallon tank is a water capacity. Suppliers fill it to 80 percent, so it holds 400 gallons of propane, a 250 gallon tank holds 200 and a 1,000 gallon tank holds 800. On the default load of 10.93 gallons a day, the 500 gallon tank's 320 usable gallons last 29.3 days, where the full 500 gallons would have promised more.
  2. Taking the BTU/h load as a daily load. The 250,000 BTU/h of the default set is the rate when everything fires together. Divided by 91,500 it gives 2.73 gallons an hour at full input, and the day burns 10.93 gallons because the appliances run the equivalent of 4 hours at full input. Dividing the load by the heating value alone says nothing about a day.
  3. Sizing for the average and forgetting the cold morning. The tank may hold plenty of propane and still be unable to turn enough of it to gas. At 0°F a 250 gallon tank gives 180,600 BTU/h in PERC Table 5, 69,400 BTU/h short of the default 250,000 BTU/h load, while a 500 gallon tank gives 300,100 BTU/h and a 1,000 gallon tank 534,500 BTU/h. The guide's section on vaporization says to consider the lowest winter temperature at the location.
  4. Choosing the design low from a winter average. Table 5 is built on the lowest 24 hour average. Moving the same 500 gallon tank from 0°F to -20°F drops the rate from 300,100 to 242,300 BTU/h, which leaves the 250,000 BTU/h load 7,700 BTU/h short. A site that sees -20°F needs the -20°F row.
  5. Ignoring continuous loading. The table is for intermittent loading. Under continuous loading the guide multiplies the rates by 0.25, so the 300,100 BTU/h of the 500 gallon tank at 0°F becomes 75,025 BTU/h. A home rarely loads a tank that way, and a generator or a process heater can.
  6. Letting the tank run dry, or leaving out appliances to come. With no reserve the 500 gallon tank lasts 36.6 days against 29.3 days with 20 percent kept back, and a late delivery then means a cold house. The guide also says to allow for appliances added later. A 80,000 BTU/h gas log on top of the default set takes the load to 330,000 BTU/h, over the 300,100 BTU/h that the 500 gallon tank gives at 0°F.

Common questions about propane tank size

How many gallons of propane does a 500 gallon tank hold?

400 gallons. Suppliers fill a tank to 80 percent of its water capacity, and Ferrellgas and AmeriGas both give the rule as the capacity times 0.8. A 250 gallon tank holds 200 gallons, a 1,000 gallon tank 800 and a 120 gallon tank 96. The space left over is a cushion for the pressure that builds when the tank warms.

How many BTU are in a gallon of propane?

About 91,500 BTU. The Propane Education & Research Council's Technical Pocket Guide gives 91,500 in its energy table and 91,502 in its table of gas properties, with 4.2 lb per gallon at 60°F and 2,488 BTU per cubic foot of vapor. This calculator divides by 91,500.

How do I work out how much propane I use in a day?

Multiply each appliance's input in BTU/h by the hours it runs at full input in a day, add the results and divide by 91,500. A typical single-family set built from the input ratings in the guide, a 100,000 BTU/h furnace, a 50,000 BTU/h water heater, a 65,000 BTU/h range and a 35,000 BTU/h dryer, comes to 1,000,000 BTU a day with the default hours, which is 10.93 gallons. Hours are an assumption, since the guide gives no duty cycle.

How long will a propane tank last?

Divide the propane you can use by the gallons you burn in a day. A 500 gallon tank holds 400 gallons, and with 20 percent left as a reserve 320 gallons are used between fills. At 10.93 gallons a day that is 29.3 days. The same load lasts 14.6 days in a 250 gallon tank and 58.6 days in a 1,000 gallon tank.

What is vaporization capacity and why does it matter?

Propane leaves the tank as a gas, and the liquid has to boil off fast enough to meet the load. Cold air and a low liquid level slow it down. PERC Table 5 gives the BTU/h that a tank can supply without frosting, for example 300,100 BTU/h for a 500 gallon tank at 0°F. If the connected load is higher, the tank frosts, the rate falls further and the appliances can run short of gas.

Can one number tell me what size tank a house needs?

No. The size depends on the connected load, the hours the appliances run, the winter low and how often you want a delivery. With the default set of 250,000 BTU/h, a 500 or a 1,000 gallon tank covers the load at 0°F and a 250 gallon tank, which gives 180,600 BTU/h, does not. Try your own appliances and the coldest 24 hour average at the site.

Does the calculator size the gas pipe or place the tank?

No. It sizes the tank for the fuel and the vaporization. The pipe comes from the gas pipe sizing calculator, and the location of the tank, its distance from buildings and the regulator are set by NFPA 58, NFPA 54, the local authority having jurisdiction and the propane supplier.

Should the tank be filled to 100 percent?

No. A propane tank is filled to about 80 percent of its water capacity so that the liquid has room to expand as it warms. The filler uses the tank's gauge, and NFPA 58 sets the limit that applies, so this page uses 0.8 of the water capacity for the usable volume.

Is there a limit on how many times I can run this?

No. This calculator runs in your browser with no daily limit and no signup.

Used on the same job

Size the fuel, then ask the supplier

The gallons a day and the vaporization check tell you what to ask for. Your supplier picks the tank, its location and the regulator under NFPA 58 and the local authority. Size the gas line with the gas pipe sizing calculator, and the largest appliance from the furnace size calculator. You can also ask the assistant to go over a propane load.