Maintained by BuildSolver · Updated
Calculator · Ventilation
Dryer vent length calculator
The International Residential Code limits a clothes dryer exhaust duct to 35 feet from the transition duct connection to the outlet terminal, and every elbow takes part of that length away. A 4 inch radius mitered 90 degree elbow counts as 5 feet and a 45 degree elbow as 2 feet 6 inches. With three 90s, that leaves 20 feet of straight duct, so 20 feet of pipe lands exactly on the limit. If the dryer manual gives a shorter maximum, such as 25 feet, enter that figure instead. The 2009 edition of the code used 25 feet. For the bath fan on the same wall, use the bathroom exhaust fan calculator; for the air a building loses to exhaust, the makeup air unit size calculator.
- Use 35 ft, the IRC figure, or the maximum in the dryer manufacturer's installation instructions when it is lower, for example 25 ft.
- Pick the elbow type, count the 90 and 45 degree elbows, and enter the straight pipe from the transition duct connection to the outlet terminal.
- The result gives the longest straight duct the limit allows after the elbows, the equivalent length of your run, and whether it is within, at or over the limit.
Example result for the default inputs
35 ft limit, 3 x 90 degree and 0 x 45 degree 4 in radius mitered elbows, 20 ft of straight duct.
Allowable straight duct
20 ft
Elbows count as
15 ft
Spare length
0 ft
| Verdict | At the limit: no equivalent length to spare. |
|---|---|
| Elbows | 3 x 90 degree at 5 ft = 15 ft |
| Allowable straight duct | 35 - 15 = 20 ft |
| Your run | 20 + 15 = 35 ft equivalent length |
| Not counted | The transition duct from the dryer to the wall or floor connection. The length runs from that connection to the outlet terminal. |
| Which limit | The dryer manufacturer's installation instructions set the size and maximum length and, where they give elbow values, those replace this table. The 35 ft and the table apply when they give none. A manufacturer limit can be lower than 35 ft; enter that figure, not 35. |
- There is no spare length. Measure the installed run; one more elbow or a few feet of duct puts it over.
For estimation purposes only. Consult a licensed engineer for final designs.
Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.
Free without signup
How the elbows use up the length limit
The model code gives a duct a length budget, 35 feet, and charges each elbow against it. A 90 degree elbow in a 4 inch mitered duct costs 5 feet of that budget and a 45 degree elbow costs 2 feet 6 inches, so the straight duct that is left is the budget minus the elbows. If the dryer manufacturer states a shorter maximum, or gives its own elbow values, those take the place of the 35 feet and the table. Every formula below is that one subtraction, written out.
- Length limit
L_limit = 35 ft, or the dryer manufacturer's maximum35 ft is M1502.4.4.1, measured from the connection to the transition duct to the outlet terminal. A manufacturer limit such as 25 ft replaces it where the manual gives one.- Elbow equivalent length
L_fit = n45 x E45 + n90 x E90E is read from Table M1502.4.4.1. For 4 in radius mitered elbows E45 = 2 ft 6 in and E90 = 5 ft, so three 90s are 15 ft.- Longest straight duct
L_straight = L_limit - L_fit35 ft less 15 ft leaves 20 ft of straight pipe. With four 90s it is 15 ft.- Equivalent length of the run
L_eq = L_straight_planned + L_fit20 ft of pipe and three 90s is 35 ft, the Vent and Flue example that lands exactly on the limit.- Margin
margin = L_limit - L_eqZero is at the limit, positive is spare length and negative is over. Thirty feet of pipe and two 90s is 40 ft, 5 ft over.- Other elbow rows
E45, E90 by row of the tableA 6 in radius smooth elbow counts 1 ft at 45 degrees and 1 ft 9 in at 90. An 8 in elbow counts 1 ft and 1 ft 7 in, a 10 in elbow 9 in and 1 ft 6 in.
Eight dryer runs through the same formula
The first row is the Vent and Flue example: 20 ft of straight duct and three 4 in mitered 90s come to 35 ft, exactly on the limit. Row three is a 25 ft manufacturer limit with two 90s, which leaves 15 ft. The sixth is over on 35 ft, and the last has room on 35 ft but is over by half a foot on a 25 ft limit.
| Run | Limit and elbows | 90s | 45s | Straight, ft | Elbows, ft | Allowed straight, ft | Margin, ft |
|---|---|---|---|---|---|---|---|
| Three 90s, 20 ft straight | 35 ft limit, 4 in mitered | 3 | 0 | 20 | 15 | 20 | 0, at limit |
| Four 90s, 10 ft straight | 35 ft limit, 4 in mitered | 4 | 0 | 10 | 20 | 15 | 5 spare |
| Manufacturer limit 25 ft, two 90s | 25 ft limit, 4 in mitered | 2 | 0 | 15 | 10 | 15 | 0, at limit |
| Straight through the wall, no elbows | 35 ft limit, 4 in mitered | 0 | 0 | 35 | 0 | 35 | 0, at limit |
| Two 90s and two 45s | 35 ft limit, 4 in mitered | 2 | 2 | 12 | 15 | 20 | 8 spare |
| Two 90s, 30 ft straight | 35 ft limit, 4 in mitered | 2 | 0 | 30 | 10 | 25 | 5 over |
| Three 90s, smooth 6 in radius | 35 ft limit, 6 in smooth | 3 | 0 | 20 | 5.25 | 29.75 | 9.75 spare |
| 25 ft limit, one 90, one 45, 18 ft | 25 ft limit, 4 in mitered | 1 | 1 | 18 | 7.5 | 17.5 | 0.5 over |
Behind those rows are the elbow values as printed in the code table.
| Elbow | 45 degree | 90 degree |
|---|---|---|
| 4 in radius mitered | 2 ft 6 in | 5 ft |
| 6 in radius smooth | 1 ft | 1 ft 9 in |
| 8 in radius smooth | 1 ft | 1 ft 7 in |
| 10 in radius smooth | 9 in | 1 ft 6 in |
Across the 2009, 2012 and 2021 editions the table stays the same. What changed is the length it is taken from: 25 ft in 2009, 35 ft from 2012. Where the dryer manufacturer gives its own maximum and its own elbow values, those are used instead.
Standards and data sources
- 2012 International Residential Code, section M1502 Clothes Dryer Exhaust (ICC page as reproduced by Dryerbox) - M1502.4.4.1 Specified length (35 ft, reduced by Table M1502.4.4.1, transition duct not included), M1502.4.4.2 Manufacturer's instructions, M1502.4.5 Length identification and the eight-row fitting equivalent length table this page uses.
- 2009 International Residential Code, section M1502 Clothes Dryer Exhaust (ICC page as reproduced by Dryerbox) - The same table with the same eight values, and the 25 ft maximum of that edition. Jurisdictions still on the 2009 text use 25 ft before the elbows, which is why the length limit is a field.
- 2021 International Residential Code, M1502.4 Dryer exhaust ducts (UpCodes, Colorado edition) - The same 35 ft and the same table, renumbered Table M1502.4.6.1, with the manufacturer's-instructions section and the label requirement.
- Vent and Flue, How Long Can a Dryer Vent Be? The 35-Foot Rule and Elbow Chart - A trade restatement of the 2021 and 2024 table, and the worked example this page opens on: 20 ft of straight duct and three 4 in radius mitered 90 degree elbows come to exactly 35 ft.
- jaspector, IRC 2024 dryer exhaust duct requirements (paraphrase of the model code) - The rule that the manufacturer's limit governs when it is lower, with the 25 ft manufacturer example and two 90 degree elbows that leaves 15 ft of straight run. The page itself says to confirm the wording against the adopted code.
Limitations of this calculator
- This page does arithmetic on the length limit and the fittings you enter. It does not approve a duct. The local authority having jurisdiction (AHJ) and the dryer manufacturer's installation instructions decide, and the code requires the installation instructions to be provided for the code official.
- The manufacturer's instructions can set a maximum shorter than 35 ft, and where they give their own elbow values those replace the code table. Enter the manufacturer's limit in the first field. The page applies the code table to the elbows either way, so check the manual's own elbow values when it has them.
- The 35 ft figure is the 2012 and later model code. The 2009 text had 25 ft, and a state or city can adopt an edition or amend it. The section numbers also move: M1502.4.4.1 in 2012, M1502.4.6.1 in 2021. Enter the limit your jurisdiction uses.
- A limit above 35 ft is not in the table. It is only valid when the dryer manufacturer's instructions give it, or when a listed dryer exhaust duct power ventilator is installed under its own instructions. The page warns above 35 ft and does not size a power ventilator.
- The length is the equivalent length of the duct from the connection to the transition duct to the outlet terminal. The transition duct itself, which the 2012 text limits to 8 ft, one piece, listed under UL 2158A and not concealed in construction, is not part of it.
- Only elbows are in the table. Tees, wall caps with extra restriction, transitions between sizes, flexible duct and other fittings are not counted here. Use the manufacturer's values for them.
- Duct material, size, supports, joint sealing, termination distance, the backdraft damper, clearance and the metal shield plates for a duct in a stud wall are separate rules in the same section. They are not checked.
- Where the duct is concealed in the construction, the 2012 text requires the equivalent length on a permanent label or tag within 6 ft of the exhaust duct connection. The wording differs in later editions. This page gives the number to write on it, not the label.
- Entries are in feet and whole elbow counts. Lengths from 10 to 150 ft for the limit, 0 to 150 ft for the straight run, and 0 to 20 elbows of each angle are accepted.
Common mistakes with dryer vent length
- Leaving the elbows out. Twenty feet of duct with three 4 in mitered 90 degree elbows reads as 20 ft on a tape and is 35 ft against the code, exactly the 35 ft limit. Each 90 degree elbow is 5 ft of the budget, not zero.
- Designing to 35 ft when the manual says less. Eighteen feet of duct, one 90 and one 45 degree elbow is 25.5 ft. Against 35 ft that is 9.5 ft to spare. Against a 25 ft manufacturer limit it is 0.5 ft over. Read the dryer manual first and enter its figure.
- Counting a 45 as half of a 90 in every row. In the 4 in mitered row a 45 is 2 ft 6 in and a 90 is 5 ft, half. In the 6 in smooth row they are 1 ft and 1 ft 9 in, which is not half. One 45 and one 90 together are 7.5 ft in the mitered row and 2.75 ft in the smooth row. Read the row that matches the fitting.
- Using the wrong elbow row. Three 90 degree elbows cost 15 ft as 4 in radius mitered fittings and 5.25 ft as 6 in radius smooth fittings, leaving 29.75 ft of straight duct instead of 20 ft. A smooth-radius elbow is a different fitting with a different count, so choose the row for the fitting that is on the wall.
- Treating a run at the limit as safe margin. Twenty feet and three 90s is exactly 35 ft with nothing left. One more 45 degree elbow adds 2 ft 6 in and the run is 37.5 ft, 2.5 ft over. Measure what was installed, including the offsets that were added to clear a joist.
- Counting the transition hose, or measuring the wrong end. The length runs from the connection to the transition duct to the outlet terminal. The short listed transition duct between the dryer and the wall is not in it, and the run does not stop at the wall: it ends at the terminal outside. Measure the pipe, then add the elbows.
Common questions about dryer vent length
What is the maximum length of a dryer vent?
35 feet under the 2012 and later International Residential Code (M1502.4.4.1 in 2012), measured from the connection to the transition duct to the outlet terminal, minus the equivalent length of every fitting. The transition duct is not in the length. The dryer manufacturer's instructions can set a shorter maximum, and the 2009 edition had 25 feet.
How much does each elbow take off the dryer vent length?
For 4 inch radius mitered elbows, 5 ft for a 90 degree elbow and 2 ft 6 in for a 45 degree elbow. For 6 inch radius smooth elbows it is 1 ft 9 in and 1 ft, for 8 inch 1 ft 7 in and 1 ft, and for 10 inch 1 ft 6 in and 9 in. That is Table M1502.4.4.1, renumbered M1502.4.6.1 in 2021.
How long can a dryer vent be with three 90 degree elbows?
20 feet of straight duct on a 35 foot limit with 4 inch radius mitered elbows: three elbows at 5 ft are 15 feet, and 35 minus 15 is 20. With four elbows it is 15 feet. On a 25 foot manufacturer limit with two 90s it is 15 feet.
Does the dryer manufacturer's limit override the code?
The code lets the manufacturer's installation instructions set the size and maximum length (M1502.4.4.2), and the code official is to be provided a copy of them at the concealment inspection. Where a manual gives a maximum shorter than 35 feet, design to the shorter figure. Where it gives its own elbow values, use them in place of the code table.
Can a dryer vent be longer than 35 feet?
Only if the dryer manufacturer's instructions allow a longer run, or a listed dryer exhaust duct power ventilator is installed and its instructions set the length. The code table does not give a longer length on its own. This page warns above 35 feet and does not size a power ventilator.
Does the transition duct count toward the length?
No. M1502.4.4.1 says the maximum length does not include the transition duct. The 2012 text limits the transition duct to 8 feet in one piece, listed and labeled under UL 2158A, and not concealed within construction. The length starts at its connection to the exhaust duct.
Is the limit 25 feet in some places?
It was 25 feet in the 2009 International Residential Code, with the same elbow table, and some jurisdictions are on that edition or amend the number. A dryer manual often states 25 feet too. Enter the lower figure that applies: 25 feet with two 90 degree elbows leaves 15 feet of straight duct.
What if the elbows are not in the code table?
Use the manufacturer's equivalent lengths for them. The code table lists mitered and smooth elbows at 45 and 90 degrees only, and the code points to it when the manufacturer gives no fitting values. For anything else, the dryer manual and the building department decide.
Does the length have to be marked anywhere?
In the 2012 text, where the exhaust duct is concealed within the building construction, the equivalent length is identified on a permanent label or tag within 6 feet of the exhaust duct connection. Later editions word this differently, so read the adopted code. The equivalent length to write on it is the straight duct plus the elbows.