Vent area only, from IRC R806.2 as published for the 2018 and 2021 editions. The edition and amendments the local jurisdiction has adopted decide. Vents count only by the net free area printed on the product. The page does not model airflow, moisture or unvented attics.

Maintained by BuildSolver · Updated

Calculator · Ventilation

Attic ventilation calculator

Enter the attic floor area and the ratings of your vents and this page gives the net free ventilating area IRC R806.2 asks for. A 1,500 sq ft attic at 1/150 needs 10.0 sq ft, 1,440 sq in: 720 sq in high and 720 sq in low, which is 40 ft of ridge vent rated 18 sq in per foot. At 1/300 the same attic needs 720 sq in, if both conditions of the exception are met. For the insulation on the same attic floor use the insulation R-value calculator; for ducts run through it, the duct heat loss calculator.

  1. The floor area of the vented attic in square feet, in plan, not the roof surface.
  2. 1/150 is the base rule. 1/300 is allowed only when both conditions of the R806.2 exception are met. Set the share of the area that goes in upper vents; 50 percent is an even split.
  3. Use the net free area per foot printed on the ridge and the soffit vent you plan to buy.
  4. The result gives the required net free area in square inches, the upper and lower parts, and the feet of ridge and continuous soffit vent that supply them.

Net free vent area of a vented attic under IRC R806.2, split high and low, with ridge and soffit vent feet. No airflow, no unvented attics.

The floor area of the vented attic space, not the roof surface and not the volume. For a hip roof or an attic split by a wall, add the vented parts.

1/300 needs a Class I or II vapor retarder on the warm side of the ceiling in Climate Zones 6, 7 and 8, and 40 to 50 percent of the area in upper vents.

Ridge, gable-top or other vents near the ridge. 50 is an even split. At 1/300 the code allows 40 to 50.

The net free area printed on the product, per foot of vent. 18.4 is the rating of one ridge vent in the Hansen source; use yours.

The net free area printed on the continuous soffit vent, per foot. 9 is an example value; use the figure on the package.

Example result for the default inputs

Attic 1,500 sq ft at 1/150, 50 % high, 18 sq in per ft ridge, 9 sq in per ft soffit.

Net free area required

1,440 sq in

Upper (exhaust) vents

720 sq in

Lower (intake) vents

720 sq in

Calculation details
Required net free area1,500 sq ft / 150 = 10.0 sq ft x 144 = 1,440 sq in
Upper vents1,440 sq in x 50 % = 720 sq in
Lower vents1,440 - 720 = 720 sq in
Ridge vent720 sq in / 18 sq in per ft = 40.0 ft, buy 40 ft
Continuous soffit vent720 sq in / 9 sq in per ft = 80.0 ft, buy 80 ft

For estimation purposes only. Consult a licensed engineer for final designs.

Get this result as a PDF, free account

Sign up with your email. Back on this page in the same browser, your inputs are filled in. No card.

Check the attic insulation

Free without signup

How the vent area is found

R806.2 sets the net free ventilating area as a fraction of the attic floor area: 1/150 as the base rule, 1/300 where both conditions of the exception are met. The page divides the floor area by the ratio, converts square feet to square inches (144 each), takes the share that goes high, and divides each part by the net free area of the vent per foot.

Required net free area
NFA (sq ft) = attic floor area / 150, or / 300A 1,500 sq ft attic at 1/150 needs 10.0 sq ft; at 1/300 it needs 5.0 sq ft.
Square inches
NFA (sq in) = NFA (sq ft) x 144Vents are rated in square inches. 10.0 sq ft is 1,440 sq in.
Upper and lower
upper = NFA x share, lower = NFA - upperAt 50 percent, the 1,500 sq ft attic needs 720 sq in high and 720 sq in low. At 1/300 the share must be 40 to 50 percent.
Ridge vent length
ft = upper sq in / NFA per ft of the ridge vent720 sq in at 18 sq in per ft is 40 ft. At 18.4 sq in per ft it is 39.1 ft.
Soffit vent length
ft = lower sq in / NFA per ft of the soffit vent720 sq in at 9 sq in per ft is 80 ft of continuous soffit vent, counted along both eaves together.

Six attics through the same formulas

Each row is worked with the same function as the form, with a ridge vent of 18 sq in per foot and a soffit vent of 9 sq in per foot. The second row is the first attic at 1/300: 720 sq in instead of 1,440.

Required net free area for six attics
AtticCaseRequired, sq inHigh, sq inLow, sq inRidge, ftSoffit, ft
Ranch house1,500 sq ft, 1/150, 50 % high1,44072072040.080.0
Same, 1/3001,500 sq ft, 1/300, 50 % high72036036020.040.0
Small cottage800 sq ft, 1/150, 50 % high76838438421.342.7
Two-story roof1,200 sq ft, 1/150, 50 % high1,15257657632.064.0
Large house2,400 sq ft, 1/150, 50 % high2,3041,1521,15264.0128.0
Cold-climate 1/3002,000 sq ft, 1/300, 40 % high96038457621.364.0

The area goes with the attic floor, not the roof: a 1,500 sq ft attic under a 6/12 roof has a roof surface of about 1,677 sq ft, and using that figure would ask for 1,610 sq in instead of 1,440.

Standards and data sources

Limitations of this calculator

  • This page works out the vent area R806.2 asks of a vented attic. It does not model airflow, heat, moisture or ice dams. A vent area that meets the code can still be undone by blocked soffits, insulation pushed into the eaves or a leaky ceiling.
  • The section is quoted from the 2021 edition (and 2018 for the same wording). The edition and any amendment the local jurisdiction has adopted decide. Some older editions and secondary summaries read the 1/300 conditions as alternatives; this page applies the 2018 and 2021 wording, in which both are needed.
  • 1/300 is allowed only if both conditions are met. The page checks the 40 to 50 percent upper share. It cannot check the vapor retarder in Climate Zones 6, 7 and 8; you confirm it.
  • Vent areas are the net free area printed on the product, which is smaller than the face size because of louvers and screens. A vent without a rating is not counted. The ridge and soffit ratings on this page are example values; use the figure on the package.
  • Only continuous ridge and soffit vents are converted to length. Box vents, gable vents and turbines are counted by their own NFA per piece: divide the required square inches by that figure.
  • Unvented attics built to R806.5, with insulation against the roof deck, need no vent area and are outside this page. Cathedral ceilings and rafter spaces with their own ventilation channels follow the same section but the 'attic floor area' is the area of the ceiling below the rafters; check the plans.
  • Values outside the field ranges are not accepted: attic floor area 100 to 20,000 sq ft, upper share 20 to 60 percent and vent ratings 1 to 100 sq in per foot.

Common mistakes when sizing attic ventilation

  1. Reading square feet as square inches. A 1,500 sq ft attic needs 10.0 sq ft of net free area, which is 1,440 sq in. Buying vents for 10.0 sq in leaves the attic with a hundred and forty-fourth part of what the code asks.
  2. Using the face size of the vent. A louvered vent that measures 8 by 16 in is 128 sq in on the face, but its net free area is what the label says, often half of that. The 1,440 sq in of the 1,500 sq ft attic is counted in net free area only.
  3. Using the roof area instead of the attic floor. The base is the attic floor area in plan, not the sloped roof surface. A 1,500 sq ft attic under a 6/12 roof has a roof surface of about 1,677 sq ft; using it gives 1,610 sq in instead of 1,440.
  4. Putting all the vent area at the ridge. Air enters low and leaves high. The page splits the 1,440 sq in into 720 high and 720 low. A ridge vent with no intake at the eaves draws its air from the house through the ceiling, or from nowhere.
  5. Taking 1/300 without its conditions. 1/300 halves the vent area, from 1,440 sq in to 720 sq in for the 1,500 sq ft attic. The exception applies only if the upper vents carry 40 to 50 percent of it, within 3 ft of the ridge, and, in Climate Zones 6, 7 and 8, a Class I or II vapor retarder is on the warm side of the ceiling. A missing condition puts the attic back on 1/150.
  6. Counting the soffit on one side only. The 80 ft of continuous soffit vent for the ranch house is the total along both eaves, about 40 ft on each side. A short run on one side leaves the other side of the attic unfed.

Common questions about attic ventilation

How much attic ventilation do I need?

IRC R806.2 asks for net free ventilating area of 1/150 of the attic floor area, which is 1 sq ft per 150 sq ft. A 1,500 sq ft attic needs 10.0 sq ft, 1,440 sq in, of net free area. Split evenly, that is 720 sq in high and 720 sq in low; at 1/150 the code does not fix the split.

When can I use 1/300 instead of 1/150?

When both conditions of the R806.2 exception are met: in Climate Zones 6, 7 and 8 a Class I or II vapor retarder is on the warm-in-winter side of the ceiling, and 40 to 50 percent of the area is in upper vents no more than 3 ft below the ridge, the rest in the bottom third of the attic. The 1,500 sq ft attic then needs 720 sq in.

What is net free area?

The total unobstructed area air can pass through, measured at the most restricted point. Louvers, screens and baffles take some of the face area, so the net free area is the figure printed on the product, not its size. Vents with no rating are not counted.

How many feet of ridge vent do I need?

Divide the upper-vent share by the net free area per foot. The 1,500 sq ft attic needs 720 sq in high: 40 ft of ridge vent at 18 sq in per ft, or 39.1 ft at 18.4. Round up and keep it clear of the rafter ends and the hips.

Should intake and exhaust be equal?

The code at 1/300 caps the upper share at 50 percent, so intake is at least equal to exhaust. Even split is the normal design. More exhaust than intake can pull conditioned air from the house. The page warns when the upper share is over 50 percent.

Is the area based on the roof or the attic floor?

It is the attic floor in plan, the area of the vented space. It is not the sloped roof surface and not the volume. For a hip roof or an attic split into parts, add the floor areas of the vented parts.

How much ventilation does a small or a large attic need?

An 800 sq ft attic at 1/150 needs 768 sq in, 384 high and 384 low. A 2,400 sq ft attic needs 2,304 sq in, 1,152 high and 1,152 low.

Does an unvented attic need vents?

No. An unvented attic built to R806.5, with insulation in contact with the underside of the roof deck, is a different design and has no vent area to size. This page is for vented attics.

Used on the same job